| 2022-10-18 15:12:47 | ROOFING REVIEW: |
| | |
| | 1-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS |
| | REQUIRED BY FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL. PLEASE ADVISE IF |
| | SUBMITTING NOW OR IF SUBMITTING LATER AS DEFERRED |
| | SUBMITTAL.): |
| | |
| | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | PRODUCTS ALREADY REVIEWED AND APPROVED: |
| | (1) STEEL PANELS NOA 21-0506.08. |
| | (2) POLYGLASS POLYSTICK UDERLAYMENT NOA 21-0602.14 |
| | |