| 2022-06-13 11:30:01 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R27 COVERS MULTIPLE ROOF SYSTEMS FOR |
| | WOOD DECKS; SYSTEM NO. W-1 THRU W-105. PLEASE SELECT |
| | SYSTEM NO. THAT MEETS OR EXCEEDS EXPOSURE CATEGORY C |
| | ZONE 3 DESIGN PRESSURE REQUIREMENTS OR PROVIDE SIGNED |
| | AND SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R35 |
| | COVERS MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; |
| | ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, |
| | ALLOWABLE SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT |
| | PRODUCT TYPES, ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS & ATTACHMENT LIMITATIONS TO BE USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED METAL ROOF SYSTEM TO |
| | BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND |
| | REQUEST. |
| | 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW |
| | ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF |
| | SLOPE(S), MEAN ROOF HEIGHT(S). SECOND REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |