2022-12-06 15:17:47NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS APPEAR TO SHOW A DEAD END CORRIDOR ON THE
 SOUTH SIDE OF THE SOUTH STAIR ON THE 4TH FLOOR - PLEASE
 SHOW THE DEAD END CORRIDOR DIMENSIONS FOR THE 4TH FLOOR
 - FBC 1020.4
  
 2) TOILET REAR WALLS ARE SHOWN TO HAVE TILE - PLEASE
 SHOW THE WALL FINISH FOR THE SIDE WALLS WITHIN 2' OF
 TOILETS - PLEASE SHOW THE COMMON AREA RESTROOM WALL
 FINISH - (DRYWALL IS NOT CONSIDERED A HARD SURFACE) -
 FBC 1210.2.2
  
 3) BRIDGE RAMP HANDRAIL INSIDE OF BUILDING NEAR THE
 HALLWAY - DRAWING A704 - RAMP HAND RAIL EXTENSIONS
 INSIDE THE BUILDING APPEAR TO BE IN COLUMNS - PLEASE
 CLARIFY THE RAMP HAND RAIL EXTENSIONS - FBC FHA
 REQUIREMENT 2 ANSI 4.8.5
  
 4) DRAWINGS A106 AND LS103 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
 5) DRAWINGS SHOW UNIT FLOORING USING 1/4" SOUND PAD -
 THE FLOORING SYSTEM WILL NEED TO BE TESTED AFTER
 INSTALLATION OR PROVIDE THE FOLLOWING TEST REPORTS
 BEFORE INSTALLATION - PLEASE STATE ON THE DRAWINGS YOUR
 INTENTIONS. YOU CAN ADD THE FLOORING SYSTEM TEST
 REPORTS TO THE DEFERRED DOCUMENTS LIST ON THE DRAWINGS.
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED
 BEFORE FLOORING INSTALLATION OR A FIELD TEST AFTER
 INSTALLATION:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  