| 2022-12-06 17:37:23 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 22050891 |
| | 12/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. THE REQUESTED PERMIT APPLICATIONS FOR THE |
| | POTABLE WATER BACKFLOW PREVENTER AND THE SAND |
| | INTERCEPTOR WERE NOT PROVIDED. |
| | |
| | THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT |
| | BE APPROVED UNTIL PERMIT APPLICATIONS FOR THE BACKFLOW |
| | AND INTERCEPTOR HAVE BEEN SUBMITTED. YOU CAN SUBMIT AN |
| | APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A |
| | CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected]. YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND |
| | I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) FAILED. NO CORRECTIONS WERE MADE TO SHOW POOL |
| | WASTEWATER IN THE POOL EQUIPMENT ROOM VIA THE FLOOR |
| | DRAINS WILL BE DECHLORINATED AND DISCHARGED INTO THE |
| | CITY STORMWARTER SYSTEM- SEC. 90-205(1) WPB CODE OF |
| | ORDINANCES. |
| | |
| | |
| | 3) FAILED. PLUMBING FIXTURE CALCULATIONS- SHEETS LS100, |
| | LS101, LS2102, LS103, LS104, P SHEETS. CONCERNING THE |
| | REQUIRED NUMBER OF PLUMBING FIXTURES FOR LEVELS 3 & 4 |
| | WHICH ARE NOW GROUPED TOGETHER IN THE CALCULATION |
| | TABLES, THE ARCHITECT'S NARRATIVE RESPONSE CITES SEC. |
| | 403.3.3 OF THE FBC- P. "THE REQUIRED PUBLIC AND |
| | EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE |
| | THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE |
| | PROVIDED WITH TOILET FACILITIES". THIS SECTION DOES NOT |
| | APPEAR TO APPLY TO THE POOL DECK AND AMENITY AREAS |
| | WHICH THE ARCHITECT STATES IN THE NARRATIVE ARE |
| | "NONCOMMERCIAL PRIVATE SPACES". CONCERNING THE LEVEL 4 |
| | POOL AND AMENITY BATHROOMS, THE ARCHITECT STATES "PER |
| | EXCEPTION B ADDITIONAL FIXTURES ARE LOCATED INSIDE THE |
| | BUILDING". IT APPEARS THE EXCEPTION BEING CITED IS THE |
| | EXCEPTION UNDER SEC. 454.1.6.1.1 FBC B WHICH IS COPIED |
| | HERE FOR CLARITY. |
| | |
| | EXCEPTION: WHEN A PUBLIC SWIMMING POOL MEETS ALL OF THE |
| | FOLLOWING CONDITIONS THE FOLLOWING SHALL APPLY: |
| | 1. THE POOL SERVES ONLY A DESIGNATED GROUP OF DWELLING |
| | UNITS, |
| | 2. THE POOL IS NOT FOR THE USE OF THE GENERAL PUBLIC, |
| | AND |
| | 3. A BUILDING PROVIDES SANITARY FACILITIES; |
| | THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE |
| | DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE |
| | 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE |
| | THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE |
| | BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO |
| | CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE. |
| | AN ADDITIONAL SET OF FIXTURES SHALL BE PROVIDED IN THE |
| | MEN'S RESTROOM FOR EVERY 7,500 SQUARE FEET OR MAJOR |
| | FRACTION THEREOF FOR POOLS GREATER THAN 10,000 SQUARE |
| | FEET. |
| | WOMEN'S RESTROOMS SHALL HAVE A RATIO OF THREE TO TWO |
| | WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL |
| | OF WATER CLOSETS AND URINALS PROVIDED FOR MEN. |
| | LAVATORY COUNTS SHALL BE EQUAL. |
| | |
| | BASED ON THIS EXCEPTION IT APPEARS THE ARCHITECT IS |
| | CHOOSING THE BUILDING REQUIREMENT TO REGULATE THE |
| | FIXTURE COUNT WHICH IS ACCEPTABLE HOWEVER THE EXCEPTION |
| | ALSO REQUIRES THE THREE TO TWO WATER CLOSET RATIO FOR |
| | WOMEN IN THE RESTROOMS. PLEASE REVISE THE PLANS |
| | ACCORDINGLY. |
| | A SECOND OPTION WOULD BE TO LABEL THE BATHROOMS BY THE |
| | POOL AS POOL BATHROOMS FOR MALE AND FEMALE AND SHOW |
| | SEPARATE CALCULATIONS FOR THE POOL (NOTE: THE CALCS |
| | ASSUME A DECK AREA THREE TIMES THE SQUARE FOOTAGE OF |
| | THE POOL). CALCULATIONS WOULD THEN HAVE TO SHOW THE TWO |
| | REMAINING UNISEX RESTROOMS WOULD ACCOMMODATE THE |
| | REMAINING ASSEMBLY OCCUPANT LOAD ON THE FLOOR. |
| | |
| | CONCERNING THE POOL BATHROOMS PLEASE NOTE THE FOLLOWING |
| | REQUIREMENTS. |
| | |
| | A) SEC. 403.6.1 FBC P: POOL BATHROOMS FOR FEMALE USE |
| | SHALL HAVE A RATIO OF THREE TO TWO WATER CLOSETS |
| | PROVIDED AS THE COMBINED TOTAL OF WATER CLOSETS AND |
| | URINALS PROVIDED FOR MALE USE. |
| | |
| | B) SEC. 454.1.6.1.1 FBC B REQUIRES EACH BATHROOM TO |
| | CONTAIN A DIAPER CHANGING STATION- SEC. 454.1.6.1.1. |
| | |
| | C) SEC. 454.1.6.1.3 FBC B REQUIRES EACH BATHROOM TO |
| | CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3. |
| | |
| | D) SEC. 454.1.6.1.4 REQUIRES A HOSE BIB WITH A VACUUM |
| | BREAKER TO BE INSTALLED WITHIN 25 FT. OF EACH BATHROOM. |
| | |
| | 4) A408 DETAIL 2- FBC ACC COMPLIANCES |
| | A) PROVIDE THE SHOWER DIMENSIONS AND OPENING WIDTHS- |
| | SEC. 608.2.3 |
| | B) SHOW THE 30X60-INCH CLEAR FLOOR APPROACH SPACES AT |
| | THE SHOWERS- SEC. 608.2.2.1. |
| | C) SHOW THE SHOWER GRAB BAR LENGTHS AND MOUNTING |
| | HEIGHTS- SECS. 608.3.3 & 609.4. PLEASE NOTE THE DETAILS |
| | ON SHEET A810 ARE NOT COMPLIANT FOR THE ALTERNATE-TYPE |
| | SHOWERS SHOWN ON THE PLAN. |
| | D) SHOW THE SHOWER CONTROL LOCATIONS- SEC. 608.5.3. |
| | PLEASE NOTE THE DETAILS ON SHEET A810 ARE NOT COMPLIANT |
| | FOR THE ALTERNATE-TYPE SHOWERS SHOWN ON THE PLAN. |
| | |
| | 5) A408 DETAIL 2: PROVIDE THE DIMENSIONS OF THE |
| | STANDARD WATER CLOSET COMPARTMENTS- WIDTHS AND DEPTHS- |
| | SEC. 405.3.1 FBC P. |
| | |
| | 6) A408 DETAIL 4: THE DOORS ARE SWINGING INTO THE CLEAR |
| | FLOOR SPACES FOR THE LAVATORIES AND THE 30X48 CLEAR |
| | FLOOR SPACE WHICH SHOULD BE LOCATED BEYOND THE ARC OF |
| | THE DOOR- SEC. 603.2.3 EXCEPTION 2 FBC ACC. |
| | |
| | 7) A408 DETAIL 4: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | AND DIMENSIONS POSITIONED FOR A FORWARD APPROACH TO THE |
| | LAVATORIES- SEC. 606.2 FBC ACC. PARALLEL APPROACHES TO |
| | ACCESSIBLE LAVATORIES ARE NOT ALLOWED. |
| | |
| | 8) SHEETS A600- A-611, & A640- A645, A660- A665, |
| | A670-A681 & A810: IN RESPONSE TO THE PREVIOUS COMMENT |
| | REQUESTING THE DESIGN INTENTION FOR THE DWELLING UNITS |
| | THE ARCHITECT STATES IN THE NARRATIVE- "DRAWINGS |
| | ILLUSTRATE FHA REQUIREMENTS". HOWEVER NO DESIGN |
| | STANDARD IS INDICATED ON THE PLAN. PLEASE NOTE THERE |
| | ARE SEVEN DIFFERENT COMPLIANCE PATHS THAT WILL PROVIDE |
| | SAFE HARBOR FOR THE RESIDENTIAL DWELLING UNITS |
| | INDICATED IN THE FAIR HOUSING DESIGN ACT MANUAL. SINCE |
| | MOST OF THE UNITS FLOOR PLANS SHOWN ARE LABELED AS TYPE |
| | B IT APPEARS THAT THE DESIGN STANDARD USED IS THE |
| | ICC/ANSI A117.1. TYPE B UNITS ARE SPECIFIED IN SEC. |
| | 1001.1 OF THE ANSI STANDARD. SEC. 1001.1 REFERS TO SEC. |
| | 1002.11.2 WHICH STATES A MINIMUM OF ONE BATHROOM SHALL |
| | HAVE FIXTURES INSTALLATIONS IN COMPLIANCE WITH SECS. |
| | 603- 610. LOOKING AT THE CLEAR FLOOR SPACE OUTLINES FOR |
| | THE FIXTURES SHOWN ON THE PLANS IT APPEARS MANY OF THE |
| | BATHROOMS WILL NOT COMPLY AS TYPE B, BUT RATHER AS TYPE |
| | A BECAUSE THE FIXTURE CLEARANCES SHOWN DO NOT PROVIDE |
| | THE GREATER ACCESS PROVIDED UNDER TYPE B. AS STATED IN |
| | THE FIRST REVIEW A COMPLETE FHA REVIEW CANNOT BE |
| | COMPLETED WITHOUT THE DIMENSIONS OF THE CLEAR FLOOR |
| | SPACES WHICH STILL HAVE NOT BEEN PROVIDED. |
| | |
| | |
| | 9) IN RESPONSE TO COMMENT #13, NEW SHEETS P360, P361, |
| | 362 HAVE BEEN SUBMITTED PER THE ENGINEER'S NARRATIVE |
| | AND ALSO DETAIL 13. |
| | A) P360: CORRECT THE NOTE AT THE TOP OF THE RISER TO |
| | INDICATE P361 FOR CONTINUATION- SEC. 107.2.1 WPB. |
| | B) P360, P361, P362: MANY OF THE VENT SIZES ARE NOT |
| | SHOWN INCLUDING THE STACK VENTS ON P362, AND FOR |
| | CLARITY PLEASE EXTEND THE SOME OF BLUE LINES |
| | REPRESENTING VENTS ON P360 A LITTLE HIGHER SO THEY CAN |
| | BE LOCATED EASIER- SEC. 107.2.1 WPB. |
| | C) P360, P361, P362: VENT STACKS ARE REQUIRED FOR THE |
| | DRAINAGE STACKS THAT HAVE FIVE BRANCH INTERVALS OR |
| | MORE. PLEASE SHOW THESE VENTS IN BLUE LINES |
| | CONTINUOUSLY FROM THE POINTS OF CONNECTIONS AT OR BELOW |
| | THE LOWEST HORIZONTAL BRANCH, AND WHERE THEY ARE |
| | CONNECTING TO THE BUILDING DRAIN, SHOW THE CONNECTIONS |
| | DOWNSTREAM OF THE DRAINAGE STACK WITHIN A DISTANCE OF |
| | 10 TIMES THE DIAMETER OF THE STACK- SEC. 904.4 FBC P. |
| | IF NOT ABLE TO SHOW THE RUNS PLEASE LABEL THEM AS VENT |
| | STACKS. |
| | D) P362: THIS SHEET IS TITLED PH1 TO ROOF, BUT IT SHOWS |
| | CONTINUATIONS FROM P361 WHICH WOULD INDICATE LEVEL 7 TO |
| | ROOF. PLEASE CORRECT. |
| | E) P360, P361, & P362: PLEASE LABEL THE WASTE STACKS |
| | FOR WASHING MACHINES AND SINKS TO VERIFY THERE ARE NOT |
| | OFFSETS BETWEEN THE LOWEST FIXTURE DRAIN AND CONNECTION |
| | AND HIGHEST DRAIN CONNECTION- SEC.913.2 FBC P. |
| | F) P361 & P362: PLEASE LABEL THE RELIEF VENT LOCATIONS |
| | AND WHICH FLOOR INTERVALS THEY ARE LOCATED AT. SHOW THE |
| | VENT SIZES, AND FOR CLARITY, SHOW THE VENT RUNS |
| | CONTINUOUSLY FROM THE LOWER AND UPPER POINTS OF |
| | CONNECTIONS- SEC. 908.2 FBC P. |
| | G) I WAS NOT ABLE TO LOCATED DETAIL 13. |
| | |
| | 10) IN RESPONSE TO COMMENT #18, NEW SHEETS P220, P221, |
| | & P222 HAVE BEEN SUBMITTED. PLEASE SHOW THE DW RISER |
| | NUMBERS ON SHEET P222 AS THEY ARE SHOWN ON P220 & P221. |
| | |
| | 11) IN RESPONSE TO COMMENT #21 THE ENGINEER REFERENCES |
| | NOTES 41 & 43 ON SHEET P001, HOWEVER THE LAVATORY |
| | DETAIL 10 ON P501 DOES NOT SHOW THE TEMPERED WATER |
| | MIXING VALVE. PLEASE REVISE THE DETAIL TO SHOW THE |
| | LOCATION OF THE VALVE AND PIPING CONNECTIONS. PLEASE |
| | NOTE A DEDICATED FULL OPEN SHUTOFF VALVE IS REQUIRED |
| | FOR THE COLD WATER LINE TO THE POINT OF USE WATER |
| | HEATER- SEC. 503.1 FBC P. |
| | |
| | 12) IN RESPONSE TO COMMENT #25 A DOUBLE CHECK VALVE |
| | BACKFLOW ASSEMBLY IS SPECIFIED FOR THE MAKEUP WATER |
| | LINE TO THE COOLING TOWERS, HOWEVER AN RPZ IS REQUIRED |
| | PER SEC. E TABLE 1.1 WPB UTILITIES CROSS-CONNECTION |
| | MANUAL. PLEASE CORRECT THE NOTE AND ADD THE MAKE AND |
| | MODEL OF THE ASSEMBLY TO THE BACKFLOW SCHEDULE ON P504. |
| | |
| | 13) IN RESPONSE TO COMMENT #26, WATER HAMMER ARRESTORS |
| | ARE PROVIDED FOR THE WASHING MACHINE SUPPLY LINES |
| | HOWEVER NOT PROVIDED FOR THE ICE MAKER AND DISHWASHER |
| | LINES- SEC. 604.9 FBC P. |
| | |
| | 14) IN RESPONSE TO COMMENT #29 THE ENGINEER REFERENCES |
| | SHEET P329 FOR THE SANITARY PLAN AND RISER WHICH ARE |
| | NOT SHOWN ON THE PLAN- SECS. 107.2.1 & 107.3.5.1.3 WPB. |
| | |
| | 15) IN RESPONSE TO COMMENT #29 THE SANITARY RISERS AND |
| | LAYOUT PLANS WERE NOT PROVIDED FOR THE DWELLING UNIT |
| | PLANS ON P333- P340- SEC. 107.2.1 & 107.3.5.1.3 WPB. |
| | |
| | 16) IN RESPONSE TO COMMENTS 30-32 STORM DRAINAGE AREA |
| | PLANS HAVE BEEN SUBMITTED. |
| | |
| | A) SHEET P402: IT APPEARS SECONDARY OR OVERFLOW DRAINS |
| | HAVE NOT BEEN PROVIDED IN AREAS L1- L8 WHERE THERE THE |
| | SIZING TABLE SHOWS VERTICAL WALL CALCULATIONS- SEC. |
| | 1108.1 FBC P. |
| | |
| | B) SHEET P404: IT APPEARS SECONDARY OR OVERFLOW DRAINS |
| | HAVE NOT BEEN PROVIDED IN AREAS T8, T9, T29, T30, T43, |
| | T44, T45, & T46 WHERE THE SIZING TABLE SHOWS VERTICAL |
| | WALL CALCULATIONS- SEC. 1108.1 FBC P. SECONDARY DRAINS |
| | ARE SHOWN ON THE PLANS IN OTHER AREAS NOT HAVING |
| | VERTICAL WALL CALCULATIONS SUCH AS T3, T4, T5 ETC. |
| | PLEASE CLARIFY. |
| | |
| | 17) IN RESPONSE TO COMMENT #32 A GREASE WASTE LINE HAS |
| | BEEN ADDED ON SHEET P104C. PLEASE SHOW THE NEW LINE |
| | CONNECTION ON SHEET P101C- SEC. 107.2.1 WPB. PLEASE |
| | REVISE THE GREASE WASTE CALCULATIONS ON SHEET P505- |
| | SEC. 1003.3.4 FBC P. |
| | |
| | 18) IN RESPONSE TO COMMENT #33 DRAINS HAVE BEEN |
| | PROVIDED IN THE STEAM ROOMS, HOWEVER THE PLAN DOES NOT |
| | SHOW DRAINS IN THE SHOWERS- SEC. 417.3 FBC P. PLEASE |
| | PROVIDE A SHOWER PAN DETAIL- SEC. 417.5.2. |
| | |
| | 19) IN REPONSE TO COMMENT #33 STEAM GENERATOR SPEC |
| | SHEETS HAVE BEEN SUBMITTED INDICATING THE UNITS ARE |
| | EQUIPPED WITH 3/4-INCH SAFETY VALVES REQUIRING INDIRECT |
| | WASTE PIPES AND WASTE RECEPTORS. PLEASE PROVIDE |
| | DETAILS- SEC. 107.2.1 WPB. |
| | |
| | 20) NO RESPONSE WAS MADE TO COMMENT #36 COPIED HERE. |
| | P101B: AN OIL INTERCEPTOR MAY BE REQUIRED TO RECEIVE |
| | THE DRAINAGE FROM THE TRASH COMPACTOR FOR SEPARATION |
| | AND DISPOSAL. PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR REVIEW- SEC. 1003.4 FBC P. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |