| Date |
Text |
| 2022-12-01 11:38:34 | 2ND REVIEW FMC |
| | PERMIT: 22050891 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M201A1: NEW AHU-1-1B FOR THE CART STORAGE IS |
| | NEW, PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. ALSO SHOW THIS NEW AHU ON THE SCHEDULE |
| | SHEET M502 |
| | |
| | 2) SHEET M201A1: REVISE THE DRAWING TO SHOW THE OUTDOOR |
| | AIR DUCT FOR THIS SYSTEM. |
| | |
| | 3) SHEET M201A1: EF-A IS MISSING FROM THE BOH AREA ON |
| | THIS REVISED DRAWING, EXPLAIN WHY IT WAS REMOVED. |
| | |
| | 4) SHEET M201A1: SHOW THE OUTDOOR AIR DUCT WORK FOR |
| | AHU-1-9 IN THE BIKE STORAGE RESIDENTIAL ROOM AND SHOW |
| | THE OUTDOOR AIR CALCULATIONS ON SHEET M502 FMC TABLE |
| | 403.3.1.1 |
| | |
| | 5) SHEET M201B1: REVISE THIS DRAWING TO SHOW THE |
| | OUTDOOR AIR FOR AHU-1-17 FOR THIS CONDITIONED SPACE. |
| | FMC TABLE 403.3.1.1 |
| | |
| | 6) SHEET M501: DUCT CONSTRUCTION SCHEDULE DOES NOT LIST |
| | THE DRYER DUCT THAT WAS ASKED FOR IN THE 1ST REVIEW |
| | COMMENTS. THE DRYER DUCT SHALL MEET FMC 504.8.1 |
| | 504.8.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A |
| | SMOOTH INTERIOR FINISH AND SHALL BE CONSTRUCTED OF |
| | METAL A MINIMUM 0.016 INCH (0.4 MM) THICK. THE EXHAUST |
| | DUCT SIZE SHALL BE 4 INCHES (102 MM) NOMINAL IN |
| | DIAMETER. |
| | |
| | 7) THE DRYER DUCT LENGTH MUST MEET THE REQUIREMENTS OF |
| | FMC 504.8.4.1 FOR LENGTH OR USE THE MANUFACTURERS |
| | INSTRUCTIONS ACCORDING TO FMC 504.8.4.2 |
| | |
| | 8) DRYER SPECS WERE NOT SUBMITTED IN THIS CYCLE FOR |
| | REVIEW. PLEASE PROVIDE THE DRYER SPECS. FBC 107.3.5 |
| | |
| | 9) PROVIDE THE MANUFACTURERS DUCTING REQUIREMENTS ON |
| | THE MECHANICAL DRAWINGS FOR THE RESIDENTIAL DRYERS. FMC |
| | 504504.8.4.2 |
| | |
| | 10) COMMENT 25 FROM 1ST REVIEW WAS NOT ANSWERED. SHEETS |
| | M301- M313 WERE NOT REVISED TO SHOW THE TRANSFER DUCTS. |
| | UNIT TYPE A AND INIT TYPE B STILL DOES NOT SHOW THE |
| | TRANSFER AIR GRILLE FOR THE DRYER. PLEASE CORRECT THE |
| | DRAWING. FBC 107.3.5 |
| | |
| | 11) COMMENT 26 FROM 1ST CYCLE REVIEW WAS NOT ANSWERED. |
| | 26) SHEET M305: PLEASE REVISE THE UNIT TYPE J TO |
| | INCLUDE THE MISSING DUCTWORK. FBC 107.3.5 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |