Plan Review Notes
Plan Review Notes For Permit 22050891
Permit Number 22050891
Review Stop M
Sequence Number 2
Notes
Date Text
2022-12-01 11:38:342ND REVIEW FMC
 PERMIT: 22050891
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M201A1: NEW AHU-1-1B FOR THE CART STORAGE IS
 NEW, PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. ALSO SHOW THIS NEW AHU ON THE SCHEDULE
 SHEET M502
  
 2) SHEET M201A1: REVISE THE DRAWING TO SHOW THE OUTDOOR
 AIR DUCT FOR THIS SYSTEM.
  
 3) SHEET M201A1: EF-A IS MISSING FROM THE BOH AREA ON
 THIS REVISED DRAWING, EXPLAIN WHY IT WAS REMOVED.
  
 4) SHEET M201A1: SHOW THE OUTDOOR AIR DUCT WORK FOR
 AHU-1-9 IN THE BIKE STORAGE RESIDENTIAL ROOM AND SHOW
 THE OUTDOOR AIR CALCULATIONS ON SHEET M502 FMC TABLE
 403.3.1.1
  
 5) SHEET M201B1: REVISE THIS DRAWING TO SHOW THE
 OUTDOOR AIR FOR AHU-1-17 FOR THIS CONDITIONED SPACE.
 FMC TABLE 403.3.1.1
  
 6) SHEET M501: DUCT CONSTRUCTION SCHEDULE DOES NOT LIST
 THE DRYER DUCT THAT WAS ASKED FOR IN THE 1ST REVIEW
 COMMENTS. THE DRYER DUCT SHALL MEET FMC 504.8.1
 504.8.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A
 SMOOTH INTERIOR FINISH AND SHALL BE CONSTRUCTED OF
 METAL A MINIMUM 0.016 INCH (0.4 MM) THICK. THE EXHAUST
 DUCT SIZE SHALL BE 4 INCHES (102 MM) NOMINAL IN
 DIAMETER.
  
 7) THE DRYER DUCT LENGTH MUST MEET THE REQUIREMENTS OF
 FMC 504.8.4.1 FOR LENGTH OR USE THE MANUFACTURERS
 INSTRUCTIONS ACCORDING TO FMC 504.8.4.2
  
 8) DRYER SPECS WERE NOT SUBMITTED IN THIS CYCLE FOR
 REVIEW. PLEASE PROVIDE THE DRYER SPECS. FBC 107.3.5
  
 9) PROVIDE THE MANUFACTURERS DUCTING REQUIREMENTS ON
 THE MECHANICAL DRAWINGS FOR THE RESIDENTIAL DRYERS. FMC
 504504.8.4.2
  
 10) COMMENT 25 FROM 1ST REVIEW WAS NOT ANSWERED. SHEETS
 M301- M313 WERE NOT REVISED TO SHOW THE TRANSFER DUCTS.
 UNIT TYPE A AND INIT TYPE B STILL DOES NOT SHOW THE
 TRANSFER AIR GRILLE FOR THE DRYER. PLEASE CORRECT THE
 DRAWING. FBC 107.3.5
  
 11) COMMENT 26 FROM 1ST CYCLE REVIEW WAS NOT ANSWERED.
 26) SHEET M305: PLEASE REVISE THE UNIT TYPE J TO
 INCLUDE THE MISSING DUCTWORK. FBC 107.3.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  