Plan Review Notes
Plan Review Notes For Permit 22050891
Permit Number 22050891
Review Stop G
Sequence Number 2
Notes
Date Text
2022-12-06 12:23:182ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 22050891
 12/6/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 1) SHEETS FG001, FG101B, FG200, FG201: THERE ARE TWO
 FUTURE RETAIL SPACES HOWEVER ONLY ONE SPECIFICATION
 TABLE WAS PROVIDED ON SHEET FG001 FOR RETAIL 137. THE
 TABLE INDICATES A 4-INCH PIPE FROM THE MP REGULATOR TO
 THE APPLIANCES. BASED ON TABLE 402.4(2) FBC FG, THE
 PIPE IS UNDERSIZED AND MUST BE INCREASED TO 5-INCH.
 A) PLEASE PROVIDE THE SPECIFICATION TABLE FOR FUTURE
 RETAIL 143.
  
 2) FG201: THE 2-INCH SCH 40 GALV. STEEL @14 IN.WC IS
 UNDERSIZED TO SUPPLY BOTH BOILERS PER TABLE 402.4(2)
 AND MUST BE INCREASED TO 2-1/2 INCHES.
  
 3) FG1001, FG201: THE PIPE SIZING TABLE 402.4(2) DOES
 NOT PROVIDE THE GAS PIPE DATA FROM THE MP REG TO THE
 POOL HEATERS. BASED ON THE RISER THE RUN APPEARS TO BE
 APPROXIMATELY 50 FT. TO THE 1ST OF THE 4 POOL HEATERS
 WHICH WOULD REQUIRE A MINIMUM 2-1/2 INCH PIPE, HOWEVER
 THE RISER INDICATES 2-INCH.
  
 4) FG200: AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE
 ESTIMATED OR MAXIMUM GAS LOAD AT THE FUTURE KITCHEN-
 SEC. 402.3 FBC FG.
  
 5) FG201: AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE
 PIPES SIZES FROM THE 2-INCH GAS HEADER TO EACH POOL
 HEATER- SEC. 402.3 FBC FG.
  
 6) FG201, FG301: THE GWH SCHEDULE SPECIFIES 6-INCH FLUE
 AND AIR INTAKE DUCTS BUT THE PLAN SHOWS 4-INCH- SEC.
 624.1 FBC FG.
  
 7) FG202, FG303: THE AIR INTAKE EXHAUST SPECS FOR THE
 WATER HEATERS SPECIFY THE MATERIAL TO BE PVC/CPVC FOR
 EITHER VERTICAL CAT IV VENTING, OR VERTICAL DIRECT
 VENTING. THE PLAN SHOWS POLYPROPLYENE DUCTS WHICH DO
 NOT APPEAR TO MEET THE MANUFACTURER'S SPECIFICATIONS.
 THE SPECS ALSO REFERENCE TABLE V FOR MAXIMUM AND
 MINIMUM VENT LENGTHS. PLEASE PROVIDE THE TABLE AND ALSO
 INDICATE CAT IV OR DIRECT VENT SYSTEM.
  
 8) FG202, FG303: THE SUBMITTED AIR INTAKE AND EXHAUST
 SPECS FOR THE BOILERS SPECIFY A DIRECT VENT SYSTEM BUT
 DO NOT SPECIFY THE TYPE OF DUCT MATERIAL. THE SPECS
 ALSO REFERENCE LENGTH TABLES L AND N WHICH ARE NOT
 INCLUDED IN THE SUBMITTAL. PLEASE PROVIDE A COMPLETE
 SUBMTTAL FOR REVIEW.
  
 9) FG202, FG303: THE AIR INTAKE AND EXAHUST DUCT SPECS
 INDICATE A CONDENSATE DRAIN SHALL BE INSTALLED IN THE
 VENT PIPING FOR BOTH THE WATER HEATERS AND THE BOILERS.
 REFER TO THE MANUFACTURER'S GUIDELINES AND PROVIDE A
 CONDENSATE DISPOSAL PLAN INCLUDING TYPE AND SIZE OF
 PIPING, PIPING RUNS AND DISPOSAL LOACTIONS- SECS. 307.2
 & 307.3 FBC FG.
  
 10) FG103A, FG304, FG305: BASED ON THE SUBMITTED SPECS
 FOR THE POOL HEATER VENTING SYSTEM PLEASE PROVIDE ON
 THE PLAN OR IN A DIAGRAM, THE AIR INTAKE AND EXHAUST
 DUCT TYPES AND SIZES, AND RUN LENGTHS- SEC. 617.1 FBC
 FG.
  
 11) FG001: PLEASE SEE COMMENT #16 FROM THE 1ST REVIEW
 COPIED BELOW HERE AND PROVIDE A NOTE ON THE PLAN TO
 VERIFY COMPLIANCE WILL BE MET.
  
 REFER TO SEC. C408.2 FBC ENERGY- PRIOR TO FINAL
 PLUMBING AND GAS APPROVAL, THE LICENSED DESIGN
 PROFESSIONAL, MECHANICAL ENGINEER, OR APPROVED AGENCY
 SHALL PROVIDE EVIDENCE OF MECHANICAL AND SERVICE WATER
 HEATING COMMISSIONING WITH THE APPLICABLE PROVISIONS OF
 SEC. C408. PLEASE SUBMIT A COMMISSIONING PLAN- SEC.
 C408.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  