| 2022-10-24 12:00:29 | NEW RESIDENTIAL HI RISE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE FIRE SERVICE ELEVATOR LOBBY |
| | DIMENSIONS PER FBC 3007.6.4 |
| | |
| | 2) PLEASE SHOW THE ELEVATOR HOIST WAY PROTECTION FOR |
| | THE 4TH FLOOR PER FBC 3006.3 |
| | |
| | 3) PLEASE SHOW THE DEAD END CORRIDOR DIMENSIONS FOR ALL |
| | FLOORS - FBC 1020.4 |
| | |
| | 4) DRAWING A125 HAS ARROWS POINTING TO - SINK, |
| | ELEVATOR, DOORS ETC. - AND NOT THE ACTUAL MECHANICAL |
| | CHASE AS NOTED. |
| | |
| | 5) DRAWING A670 - STUDIO "A" AND "D" ROOM NOTATIONS NOT |
| | CORRECT - BATH IN THE KITCHEN, KITCHEN IN THE CLOSET - |
| | ETC. |
| | |
| | 6) PLEASE SHOW THE POOL BARRIER - FBC 454.1.3.1.9 |
| | |
| | 7) PLEASE SHOW THE COMMON AREA RESTROOM WALL FINISH - |
| | (DRYWALL IS NOT CONSIDERED A HARD SURFACE) - FBC |
| | 1210.2.2 |
| | |
| | 8) UNIT BATHROOMS - PLEASE SHOW THAT GRAB BAR BACKING |
| | AT SHOWERS AND BATH TUBS ARE REQUIRED ON ALL 3 WALLS - |
| | FBC FHA REQUIREMENT 6 |
| | |
| | 9) LEVEL 4 COMMON RESTROOM - PLEASE SHOW THE DOOR |
| | MANEUVERING CLEARANCE TO EXIT THE RESTROOM FBC FHA - |
| | ANSI 4.13.6 |
| | |
| | 10) LEVEL 4 - COMMON AREA BAR - PLEASE SHOW |
| | ACCESSIBILITY DETAILS - SINK FLOOR SPACE, BAR SEATING |
| | COUNTER HEIGHT ETC. FBC FHA REQUIREMENT 2 |
| | |
| | 11) KITCHEN G-1 AND G-5 - A 5 FOOT TURNING RADIUS IS |
| | REQUIRED - FBC FHA REQUIREMENT 7 |
| | |
| | 12) KITCHEN L-2 NEED 40 INCHES CLEARANCE BETWEEN THE |
| | REFRIGERATOR AND THE KITCHEN ISLAND - FBC FHA |
| | REQUIREMENT 7 |
| | |
| | 13) DRAWING A704 - RAMP HAND RAIL EXTENSIONS INSIDE THE |
| | BUILDING APPEAR TO BE IN COLUMNS - PLEASE CLARIFY THE |
| | HAND RAIL EXTENSIONS - FBC FHA REQUIREMENT 2 ANSI 4.8.5 |
| | |
| | 14) FLOORING - THE FOLLOWING ACUSTICAL TEST REPORTS ARE |
| | REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |