2022-10-24 12:00:29NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE FIRE SERVICE ELEVATOR LOBBY
 DIMENSIONS PER FBC 3007.6.4
  
 2) PLEASE SHOW THE ELEVATOR HOIST WAY PROTECTION FOR
 THE 4TH FLOOR PER FBC 3006.3
  
 3) PLEASE SHOW THE DEAD END CORRIDOR DIMENSIONS FOR ALL
 FLOORS - FBC 1020.4
  
 4) DRAWING A125 HAS ARROWS POINTING TO - SINK,
 ELEVATOR, DOORS ETC. - AND NOT THE ACTUAL MECHANICAL
 CHASE AS NOTED.
  
 5) DRAWING A670 - STUDIO "A" AND "D" ROOM NOTATIONS NOT
 CORRECT - BATH IN THE KITCHEN, KITCHEN IN THE CLOSET -
 ETC.
  
 6) PLEASE SHOW THE POOL BARRIER - FBC 454.1.3.1.9
  
 7) PLEASE SHOW THE COMMON AREA RESTROOM WALL FINISH -
 (DRYWALL IS NOT CONSIDERED A HARD SURFACE) - FBC
 1210.2.2
  
 8) UNIT BATHROOMS - PLEASE SHOW THAT GRAB BAR BACKING
 AT SHOWERS AND BATH TUBS ARE REQUIRED ON ALL 3 WALLS -
 FBC FHA REQUIREMENT 6
  
 9) LEVEL 4 COMMON RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE TO EXIT THE RESTROOM FBC FHA -
 ANSI 4.13.6
  
 10) LEVEL 4 - COMMON AREA BAR - PLEASE SHOW
 ACCESSIBILITY DETAILS - SINK FLOOR SPACE, BAR SEATING
 COUNTER HEIGHT ETC. FBC FHA REQUIREMENT 2
  
 11) KITCHEN G-1 AND G-5 - A 5 FOOT TURNING RADIUS IS
 REQUIRED - FBC FHA REQUIREMENT 7
  
 12) KITCHEN L-2 NEED 40 INCHES CLEARANCE BETWEEN THE
 REFRIGERATOR AND THE KITCHEN ISLAND - FBC FHA
 REQUIREMENT 7
  
 13) DRAWING A704 - RAMP HAND RAIL EXTENSIONS INSIDE THE
 BUILDING APPEAR TO BE IN COLUMNS - PLEASE CLARIFY THE
 HAND RAIL EXTENSIONS - FBC FHA REQUIREMENT 2 ANSI 4.8.5
  
 14) FLOORING - THE FOLLOWING ACUSTICAL TEST REPORTS ARE
 REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  