| 2022-10-20 15:21:24 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22050891 |
| | 10/18/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE FOLLOWING ITEMS SHOWN ON THE PLANS: |
| | * POTABLE WATER SERVICE BACKFLOW PREVENTER. |
| | * GREASE AND SOLIDS INTERCEPTORS. |
| | * SAND INTERCEPTOR. |
| | THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT |
| | BE APPROVED UNTIL PERMIT APPLICATIONS FOR THOSE ITEMS |
| | HAVE BEEN SUBMITTED. YOU CAN SUBMIT AN APPLICATION TBD |
| | (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| | SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE |
| | THE REVIEW STATUS TO PASS. |
| | |
| | 2) SEPARATE PERMITS AND PLANS ARE ALSO REQUIRED FOR THE |
| | POOL, IRRIGATION SYSTEM, AND THE IRRIGATION SYSTEM |
| | BACKFLOW PREVENTER- SEC. 107.2.1 WPB. COMPLETE REVIEWS |
| | OF THOSE ITEMS ARE NOT BEING CONDUCTED AT THIS TIME. |
| | CONCERNING THE POOL- SHEET P103A SHOWS A FLOOR DRAIN IN |
| | THE POOL EQUIPMENT ROOM AND FLOOR DRAINS THAT APPEAR TO |
| | BE BELOW THE POOL SHELL POSSIBLY FOR POOL LEAKAGE OR |
| | DRAINAGE. THESE DRAINS ARE DISCHARGING INTO THE |
| | SANITARY SYSTEM. PLEASE BE ADVISED THAT POOL WASTEWATER |
| | SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM IN |
| | ACCORDANCE WITH SEC. 90-126(5) WPB CODE OF ORDINANCES. |
| | REVIEW THE INFORMATION BELOW: |
| | |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| | KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED |
| | TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| | STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| | FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 3) PLUMBING FIXTURE CALCULATIONS- SHEETS LS100, LS101, |
| | LS2102, LS103, LS104, P SHEETS: |
| | |
| | A) LEVEL-1: PROVIDE 2 WATER CLOSETS FOR MALE USE AND 2 |
| | WATER CLOSETS FOR FEMALE USE- TABLE 403.1 FBC P. THE |
| | FLOOR PLAN SHOWS ONE SINGLE USER TOILET ROOM WITH ONE |
| | WATER CLOSET IN THE BOH WHICH WILL NOT MEET COMPLIANCE. |
| | FIXTURES ARE REQUIRED FOR PUBLIC AND EMPLOYEE USE, AND |
| | SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE |
| | REQUIRED- SEC. 403.2 & 403.3. LAVATORIES FOR EACH |
| | SEPARATE TOILET ROOM ARE ALSO REQUIRED PER SEC. 403.7. |
| | B) LEVEL-1: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS |
| | FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC. |
| | 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| | FOR STANDING PERSONS. |
| | C) LEVEL-1: PLEASE REVISE THE CALCULATION TABLE TO SHOW |
| | THE TOTAL PROVIDED NUMBER OF FIXTURES. |
| | D) LEVEL-2: OCCUPANT LOAD, RESTROOM LOCATIONS AND |
| | PLUMBING PIPING DETAILS HAVE BEEN PROVIDED FOR THE |
| | FUTURE OFFICE/STORAGE TENANT. PLEASE PROVIDE THE |
| | FIXTURE CALCULATIONS PER TABLE 403.1. PLEASE NOTE A |
| | MINIMUM OF TWO DRINKING FOUNTAINS FOR PUBLIC AND |
| | EMPLOYEE USE ARE REQUIRED- TABLE 403.1 AND SEC. 410.3. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| | FOR STANDING PERSONS. |
| | E) LEVEL-3: PLEASE LABEL THE RESTROOMS IN THE OFFICE |
| | AND BREAKROOM AS MALE, FEMALE, OR UNISEX- SEC. 403.4 |
| | FBC P. |
| | F) LEVEL-3: BASED ON THE CALCULATIONS A 3RD FEMALE |
| | WATER CLOSET IS REQUIRED FOR THE A-3 AREA. THERE ARE |
| | ONLY 2 AVAILABLE IN THE SPA BATHROOMS- TABLE 403.1 FBC |
| | P. |
| | G) LEVEL-3: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS |
| | FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC. |
| | 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| | FOR STANDING PERSONS. |
| | H) LEVEL-3: SHOW THE LOCATION OF THE REQUIRED SERVICE |
| | SINK FOR THE OCCUPANCIES- TABLE 403.1. |
| | I) LEVEL-4: THE CALCULATION TABLE DOES NOT ACCOUNT FOR |
| | THE BAR AND DINING AREAS WHICH HAVE RATIOS OF 1 PER 40 |
| | AND 1 PER 75 FOR WATER CLOSETS AND LAVATORIES- TABLE |
| | 403.1. PLEASE PROVIDE A BREAKDOWN CALCULATION THAT |
| | INCLUDES THE SQ. FOOTAGE AND ASSOCIATED OCCUPANT LOADS |
| | OF ALL AMENITY AREAS AND REVISE THE TABLE ACCORDINGLY. |
| | J) LEVEL-4: SEC. 454.1.6.1.1 EXCEPTION FBC B ALLOWS FOR |
| | THE BUILDING TO PROVIDE THE REQUIRED NUMBER OF POOL |
| | BATHROOM FIXTURES HOWEVER INDIVIDUAL CALCULATION TABLES |
| | HAVE BEEN PROVIDED FOR THE ASSEMBLY OCCUPANCY AND THE |
| | POOL. PLEASE CLARIFY IF THE BATHROOMS BY THE DECK AND |
| | BAR ARE DESIGNATED FOR THE POOL AND LABEL THEM |
| | ACCORDINGLY. PLEASE NOTE SEC. 403.6.1 FBC P REQUIRES |
| | WOMEN'S POOL RESTROOMS TO HAVE A RATIO OF THREE TO TWO |
| | WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL |
| | OF WATER CLOSETS AND URINALS PROVIDED FOR MEN. IT |
| | APPEARS ONE ADDITIONAL FEMALE WATER CLOSET IS REQUIRED. |
| | LAVATORY COUNTS SHALL BE EQUAL. |
| | K) LEVEL-4: PROVIDE AN AREA CALCULATION FOR THE POOL |
| | DECK TO SHOW COMPLIANCE WITH TABLE AND SEC. 403.6.1. |
| | THE FIXTURE COUNT OF TABLE 403.6 IS DEEMED TO BE |
| | ADEQUATE FOR THE POOL AND POOL DECK AREA THAT IS UP TO |
| | THREE TIMES THE AREA OF THE POOL SURFACE PROVIDED. |
| | L) LEVEL-4: CORRECT THE ASSEMBLY CALCULATION FOR MALE |
| | WATER CLOSETS TO INDICATE 1.39 REQUIRED. THE PLANS |
| | APPEAR TO INDICATE A SHORTAGE OF ONE MALE WATER CLOSET, |
| | ONE MALE LAVATORY, TWO FEMALE WATER CLOSETS, AND ONE |
| | FEMALE LAVATORY FOR THE ASSEMBLY OCCUPANCY. |
| | M) LEVEL-4: SHOW THE LOCATION OF THE REQUIRED SERVICE |
| | SINK FOR THE OCCUPANCIES- TABLE 403.1. |
| | |
| | 4) LS100: PLEASE UPDATE THE APPLICABLE CODE REFERENCES |
| | TO INDICATE THE 2020 FLORIDA BUILDING CODE 7TH EDITION |
| | WHICH IS THE CURRENT CODE IN EFFECT- SEC. 107.2.1 WPB. |
| | A) PLEASE ADD THE 2020 FBC ACCESSIBILITY 7TH EDITION TO |
| | THE APPLICABLE CODES LIST. COMPLIANCE WITH THE FBC ACC |
| | REQUIRES THAT A PERCENTAGE OF THE NEW DWELLING UNITS |
| | SHALL BE DESIGNED AND CONSTRUCTED MOBILITY FEATURES |
| | COMPLYING WITH SECS. 809.2- 809.4 AND COMMUNICATION |
| | FEATURES COMPLYING WITH SEC. 809.5. FACILITIES |
| | REGULATED BY THE DEPARTMENT OF HOUSING AND URBAN |
| | DEVELOPMENT (HUD)- SEC. 233.2 SHALL HAVE THE NUMBER OF |
| | UNITS IN COMPLIANCE DETERMINED BY HUD. FACILITIES NOT |
| | SUBJECT TO HUD SHALL HAVE AT LEAST 5% OF THE UNITS |
| | DESIGNED AND CONSTRUCTED WITH MOBILITY FEATURES AND 2% |
| | WITH COMMUNICATION FEATURES. TO HELP EXPEDITE THE |
| | REVIEW PLEASE PROVIDE A LIST OF APARTMENTS THAT ARE |
| | MEETING COMPLIANCE. PLEASE NOTE THE UNITS SHALL BE |
| | DISPERSED AMONG THE VARIOUS TYPES OF UNITS IN THE |
| | FACILITY- SEC. 233.3.5. CONCERNING THE TOILET AND |
| | BATHING FACILITIES PLEASE REFER TO SEC. 809.4 WHICH |
| | REFERENCES SECS. 603-610 FOR FIXTURE COMPLIANCE. |
| | CONCERNING PLUMBING FIXTURES AND APPLIANCES IN THE |
| | KITCHENS PLEASE REFER TO SECS. 809.3 & 804. |
| | B) COMPLIANCE WITH OTHER FEDERAL LAWS SUCH AS THE FAIR |
| | HOUSING ACT AND SECTION 504 OF THE REHABILITATION ACT |
| | OF 1973, AS AMENDED IS REQUIRED. PLEASE REFER TO THE |
| | FAIR HOUSING DESIGN ACT MANUAL FOR FURTHER INFORMATION- |
| | SEE PAGE 1 OF THE INTRODUCTION. CLARIFY HOW COMPLIANCE |
| | WITH THE ACT AND SAFE HARBOR FOR THE FACILITY IS BEING |
| | PROVIDED. |
| | |
| | 5) SHEET A408 DETAILS 1-6: PLEASE PROVIDE THE FOLLOWING |
| | FBC ACC COMPLIANCE INFORMATION: |
| | A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE |
| | WATER CLOSETS, LAVATORIES, AND URINAL- SECS. 604.3, |
| | 605.3 & 606.2. |
| | B) DIAMETERS OF THE TURNING CIRCLES- SEC. 304.3 FBC |
| | ACC. |
| | C) ACCESSIBLE SHOWER DIMENSIONS- SECS. 213.3.6, 608.2.1 |
| | AND/OR 608.2.2 FBC ACC. |
| | D) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | ACCESSIBLE SHOWERS- SECS. 608.2.1 AND/OR 608.2.2. |
| | E) SHOW THE SAUNA AND STEAM ROOM BENCH LOCATIONS AND |
| | CLEAR FLOOR SPACE DIAGRAMS WITH DIMENSIONS- SEC. 612.2 |
| | PLEASE PROVIDE ENLARGED BENCH DETAILS- SECS. 903.3- |
| | 903.7. |
| | F) SHOW THE REQUIRED TURNING SPACES WITH DIMENSIONS |
| | INSIDE THE SAUNAS AND STEAM ROOMS- SECS. 612.3 & 304.1. |
| | |
| | 6) A408: PROVIDE THE STANDARD TOILET COMPARTMENT |
| | DIMENSIONS- SEC. 405.3.1 FBC P. |
| | |
| | 7) A810: PROVIDE ACCESSIBLE SHOWER DETAILS PER FBC ACC. |
| | A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECS. 608.3.1 AND/OR 608.3.2. |
| | B) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS- |
| | SECS. 608.5.1 AND/OR 608.5.2. |
| | C) LOCATION OF ACCESSIBLE SEATS AND MOUNTING DETAILS |
| | (IF APPLICABLE)- SECS. 610.3, 610.3.1, & 610.3.2. |
| | |
| | 8) SHEETS A600- A-611, & A640- A645, A660- A665, |
| | A670-A681: A THOROUGH REVIEW OF THE RESIDENTIAL BATH |
| | AND KITCHEN PLUMBING FIXTURE INSTALLATIONS CANNOT BE |
| | CONDUCTED WITHOUT THE NECESSARY CODE REFERENCE DATA |
| | INFORMATION PROVIDED AS REQUESTED IN COMMENTS 4A & 4B |
| | ABOVE. TO HELP EXPEDITE THE RE- REVIEW PLEASE LABEL ALL |
| | UNITS THAT ARE ACCESSIBLE OR FHDA COMPLIANT AND PROVIDE |
| | COMPLETE KITCHEN AND BATH COMPLIANCE DETAILS. |
| | |
| | 9) SHEET P100: THE DRAINAGE FROM THE SAND INTERCEPTOR |
| | SHALL DISCHARGE INTO THE SANITARY SEWER AND NOT INTO |
| | THE STORM DRAIN PER SEC. 90- 203(A) WPB CODE OF |
| | ORDINANCES. SEC. 90-203. - PROHIBITED GENERAL |
| | PROHIBITION. EXCEPT AS PROVIDED IN SECTION 90-205, AND |
| | EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY |
| | DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE |
| | PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM |
| | WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED |
| | ENTIRELY OF STORMWATER. |
| | IF YOU HAVE FURTHER QUESTIONS PLEASE CONTACT- |
| | |
| | TRACY L. WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |
| | CITY OF WEST PALM BEACH |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS ST., 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 561-494-1120 |
| | FAX: 561-494-1116 |
| | CELL 561-351-0510 |
| | [email protected] |
| | |
| | 10) SHEETS P100 & P501 DETAIL 6: AS NOTED IN COMMENT #1 |
| | THE SAND INTERCEPTOR SHALL BE INSTALLED UNDER A |
| | SEPARATE PERMIT, HOWEVER PLEASE CLARIFY IF THE UNIT IS |
| | ALSO AN OIL INTERCEPTOR PER SEC. 1003.4- 1003.4.2.1 FBC |
| | P. |
| | PLEASE NOTE THAT OIL/SAND INTERCEPTORS SHALL BE LISTED |
| | OR COMPLY WITH SEC. 1003.4.2.1 GENERAL DESIGN |
| | REQUIREMENTS- OIL SEPARATORS SHALL HAVE A DEPTH OF NOT |
| | LESS THAN 2 FEET BELOW THE INVERT OF THE DISCHARGE |
| | DRAIN. THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE |
| | NOT LESS THAN AN 18-INCH WATER SEAL. THE DETAIL SHOWS |
| | THE DEPTH IS TOO SHALLOW. PLEASE PROVIDE MORE |
| | INFORMATION ABOUT THE UNIT INCLUDING HOW IT WILL BE |
| | PROTECTED FROM VEHICULAR DAMAGE ABOVE. CLARIFY IF THE |
| | PIT ACCESS LID SHOWN IN THE DETAIL IS HEAVY DUTY |
| | TRAFFIC RATED AND IS EQUIPPED WITH AN ACCESS |
| | RESTRICTOR- SEC. 107.2.1 WPB. |
| | A) PROVIDE DIMENSIONED CONCRETE VAULT CONSTRUCTION AND |
| | BURIAL DETAILS- SEC. 107.2.1 WPB. |
| | |
| | 11) P100, P101C & P503: AS NOTED IN COMMENT #1 THE |
| | GREASE AND SOLIDS INTERCEPTORS SHALL BE INSTALLED UNDER |
| | A SEPARATE PERMIT. A COMPLETE PLAN SUBMITTAL WILL BE |
| | REQUIRED AT THAT TIME WHICH SHALL INCLUDE THE FOLLOWING |
| | ITEMS: |
| | A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF |
| | RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKES, MODELS AND |
| | CAPACITIES OF THE UNITS. |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| | FOR GRAVITY TYPES. |
| | D) DIMENSIONED TANK BURIAL, ANCHORING, AND BACKFILLING |
| | DETAILS. |
| | E) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND |
| | SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL |
| | VENTS, AND SAMPLING PORTS. |
| | F) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY |
| | DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS |
| | RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR |
| | CLEANOUTS, AND SAMPLING PORTS (IF INSTALLED). |
| | |
| | 12) P100: PLEASE INDICATE THE SIZE OF THE MAIN STORM |
| | DRAIN PIPE EXISTING ON THE NORTH SIDE OF THE BUILDING- |
| | SEC. 107.2.1 WPB. |
| | |
| | 13) P101A: THE MAIN SOIL, WASTE AND VENT STACK |
| | CONNECTIONS TO THE BUILDING DRAIN ARE SHOWN HOWEVER |
| | THERE ARE NO CONTINUOUS ISOMETRIC DRAWINGS SUBMITTED |
| | THAT CLEARLY SHOW STACK RUNS FROM THE FOUNDATION TO THE |
| | ROOF- SEC. 904.2, 904.3, & 904.4. TO HELP EXPEDITE THE |
| | REVIEW PLEASE PROVIDE THE ISOMETRICS WHICH SHALL ALSO |
| | SHOW THE LOCATIONS OF RELIEF VENTS WHERE REQUIRED PER |
| | SEC. 908.1 AND SEC. 107.3.5.3.1 WPB. |
| | A) PLEASE NOTE SEC. 913.2 PROHIBITS EITHER VERTICAL OR |
| | HORIZONTAL OFFSETS IN THE WASTE STACK SERVING THE |
| | WASHING MACHINES IN THE DWELLING UNITS BETWEEN THE |
| | LOWEST AND HIGHEST FIXTURE DRAIN CONNECTIONS. PLEASE |
| | PROVIDE THE ISO FOR THE STACK. |
| | B) PLEASE NOTE SEC. 913.3 REQUIRES A STACK VENT FOR THE |
| | WASTE STACK WHICH SHALL NOT BE LESS THAN THE SIZE OF |
| | THE WASTE STACK. |
| | |
| | 14) P101A: PROVIDE A 3-INCH VENT AT (S20). THE PLAN |
| | SHOWS A 2-INCH- SEC. 904.4 FBC P. |
| | |
| | 15) P101A: (S16) NOTE INDICATES A 4-INCH SANITARY BUT |
| | IT APPEARS TO BE AN 8-INCH. PLEASE SEE THE RISER ON |
| | SHEET P101C. |
| | |
| | 16) P101B: PLEASE SHOW THE LOCATION OF THE 8-INCH RISER |
| | CALLED OUT IN NOTE (S21)- SEC. 107.2.1 WPB. |
| | |
| | 17) P102A, P104A, P105, P106: THE 4-INCH VENT STACK |
| | CONTINUATION FROM THE 1ST FLOOR IS NOT SHOWN- SEC. |
| | 904.4 FBC P. IT RE-APPEARS ON P107. |
| | |
| | 18) P201B, P201C: TO HELP EXPEDITE THE REVIEW PLEASE |
| | PROVIDE COMPLETE WATER RISER DRAWINGS THAT SHOW THE |
| | UPFEEDING LINES FROM THE GROUND FLOOR AND THE |
| | DOWNFEEDING LINES FROM THE TOP FLOORS INCLUDING THE HW |
| | RECIRCULATION SYSTEM LOOP FROM THE HOT WATER HEATERS ON |
| | THE ROOF DOWN THROUGH THE BUILDING- SEC. 607.2 FBC P. |
| | AND SEC. 107.3.5.1.3 WPB. PLEASE NOTE THAT THE |
| | DEVELOPED LENGTH OF HOT WATER OR TEMPERED WATER PIPING |
| | FROM THE SOURCE OF HOT WATER TO FIXTURES REQUIRING HOT |
| | OR TEMPERED WATER SHALL NOT EXCEED 50 FT. |
| | |
| | 19) P202B, P202C: THE HWR LINE DOES NOT APPEAR TO BE |
| | MAKING A CONNECTION BACK INTO THE HW LINE. PLEASE REFER |
| | TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE IS THE HOT |
| | WATER SOURCE AND THE 1/2-INCH HW FIXTURE SUPPLY PIPES |
| | TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2 FT. |
| | ALLOWABLE LENGTHS FROM THE HW SOURCE. |
| | |
| | 20) P203A, P203B, P203C: THE HWR LINES DO NOT APPEAR TO |
| | BE MAKING COMPLETE LOOPS DOWN TO ALL THE LAVATORIES. |
| | PLEASE REFER TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE |
| | IS THE HOT WATER SOURCE AND THE 1/2-INCH HW FIXTURE |
| | SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THEIR |
| | MAXIMUM 2 FT. ALLOWABLE LENGTHS FROM THE HW SOURCE. |
| | |
| | 21) P202B, P202C, P203A, P203B, P203C: INDICATE HOW |
| | TEMPERED WATER WILL BE PROVIDED TO THE PUBLIC |
| | LAVATORIES- SEC. 419.5 FBC P. |
| | |
| | 22) P203B NOTE D15: PLEASE INDICATE THE MAKE AND MODEL |
| | OF THE ASSE 1013 RPZ TO PROTECT THE POTABLE WATER LINE |
| | TO THE IRRIGATION SYSTEM- SECS. 608.3 & 608.17.5 FBC P. |
| | TO HELP EXPEDITE THE REVIEW PLEASE ADD A BACKFLOW |
| | ASSEMBLY SCHEDULE FOR ALL DEVICES TO SHEET P503- SEC. |
| | 107.2.1 WPB. |
| | |
| | 23) P204A: PROVIDE A WATER RISER DRAWING FOR THE |
| | RESTROOMS- SEC. 107.3.5.1.3 WPB. PLEASE NOTE COMMENTS |
| | 18 & 19 ABOVE PERTAINING TO THE HW SOURCE AND TEMPERED |
| | WATER REQUIREMENT. |
| | |
| | 24) P204B: PLEASE MODIFY NOTE D23 TO INDICATE ASSE 1022 |
| | APPROVED BACKFLOW PREVENTERS FOR CARBONATED BEVERAGE |
| | DISPENSERS, AND ASSE 1024 APPROVED BACKFLOW PREVENTERS |
| | FOR NON- CARBONATED BEVERAGES- SECS. 608.17.1.1 & |
| | 608.17.1.2 FBC P. |
| | |
| | 25) P210: PLEASE SHOW THE COOLING TOWER MAKEUP WATER |
| | LINE CONTINUATION TO THE TOWERS- SEC. 107.2.1 WPB. |
| | |
| | 26) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD |
| | NOTES TO INDICATE WATER HAMMER ON LINES SUPPLYING THE |
| | DISHWASHERS, WASHING MACHINES AND REFRIGERATOR ICE |
| | MAKERS- SEC. 604.9 FBC P. |
| | |
| | 27) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD |
| | NOTES INDICATING BACKFLOW PREVENTERS WILL BE INSTALLED |
| | ON LINES SUPPLYING THE REFRIGERATOR ICE MAKERS- SEC. |
| | 608.3 FBC P. PLEASE SPECIFY THE MAKE AND MODEL OF THE |
| | DEVICES AND INCLUDE IN THE SCHEDULE ON P503. |
| | A) PLEASE INDICATE THE TYPE, SIZE AND R-VALUE OF HW AND |
| | HWR PIPE INSULATION PER TABLE C403.2.10 FBC EC. NOTES |
| | OR DETAILS SHALL BE PLACED ON THE DWELLING UNIT PLANS |
| | AND THE NON-RESIDENTIAL PLANS AND RISERS. |
| | |
| | 28) P329: PLEASE INDICATE WHICH SHEET HAS THE SANITARY |
| | PIPING LAYOUT AND ISOMETRIC DRAWINGS FOR THESE UNITS C1 |
| | & D1- SEC. 107.2.1 WPB. |
| | |
| | 29) P330- P340: THESE TYPICAL UNIT PLANS DO NOT HAVE |
| | SANITARY PIPING LAYOUT AND ISOMETRIC DRAWINGS- SEC. |
| | 107.2.1 WPB. |
| | |
| | 30) P421: PLEASE PROVIDE THE AREA PLANS AND DRAINAGE |
| | CALCULATIONS THAT MATCH WITH THESE STORM WATER |
| | ISOMETRIC DRAWINGS- SEC. 107.2.1 WPB AND SEC. 1106.1 |
| | FBC P. |
| | |
| | 31) P402C: PLEASE PROVIDE A BRIDGE ROOF DRAINAGE PLAN |
| | AND DRAINAGE CALCULATIONS- SEC. 1106.1 FBC P. |
| | |
| | 32) P421, P422, P423: TO HELP EXPEDITE THE REVIEW, |
| | PLEASE INDICATE THE ROOF DRAINAGE GPM'S AT THE ROOF |
| | DRAINS AND THE ACCUMULATIVE FLOW THROUGH THE BUILDING |
| | TO THE GROUND LEVEL MAIN STORM DRAINS- SEC. 1106.1, |
| | TABLES 1106.2 & 1106.3 FBC P. |
| | |
| | 31) P501 DETAIL 10: PLEASE SHOW A DEDICATED SHUTOFF |
| | VALVE FOR THE COLD WATER FEED TO THE WATER HEATER- SEC. |
| | 503.1 FBC P. |
| | |
| | 32) LS104, P104C, P104D: SHEET LS104 SHOWS TWO BARS ON |
| | THE DECK, PRIVATE AND OUTDOOR DINING, GRILLS, AND A |
| | MAIN KITCHEN AND SHOW KITCHEN. THE PLUMBING PLANS DO |
| | NOT SHOW ANY PIPING AT THE LOCATION OF THE BAR ON THE |
| | NW SIDE OF THE DECK, AND DO NOT SHOW ANY MEANS OF |
| | SEPARATING AND DISPOSING OF GREASE FROM THE FIXTURE |
| | DRAINAGE FLOWS INTO THE SANITARY SYSTEM- SEC. 1003.3.1 |
| | FBC P, AND SEC. 107.2.1 WPB. PLEASE REFER TO COMMENT |
| | #11 FOR GREASE INTERCEPTOR SUBMITTAL REQUIREMENTS AS |
| | APPLICABLE. |
| | |
| | 33) P203A P503: THE LOCATIONS OF THE STEAM GENERATORS |
| | IN THE STEAM ROOMS, THE WATER SUPPLY TO THE UNITS, AND |
| | DRAINAGE DISPOSAL DETAILS ARE NOT SHOWN ON THE PLANS- |
| | SEC. 107.2.1 WPB. |
| | |
| | 34) P502, P503: PLEASE LABEL THE TWO UNIDENTIFIED |
| | PIECES OF EQUIPMENT IN THE CORNER OF THE BOILER ROOM |
| | AND PROVIDE EQUIPMENT SCHEDULES- SEC. 107.2.1 WPB. |
| | |
| | 35) P502: PLEASE INDICATE THE SIZE OF THE WATER SUPPLY |
| | PIPE LEAVING THE BOILER ROOM TO SUPPLY THE BUILDING, |
| | AND INCLUDE THE TEMPERATURE OF THE WATER- SEC. 607.1 |
| | FBC P. |
| | |
| | 36) P101B: AN OIL INTERCEPTOR MAY BE REQUIRED TO |
| | RECEIVE THE DRAINAGE FROM THE TRASH COMPACTOR FOR |
| | SEPARTION AND DISPOSAL. PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR REVIEW- SEC. 1003.4 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |