Plan Review Notes
Plan Review Notes For Permit 22050891
Permit Number 22050891
Review Stop P
Sequence Number 1
Notes
Date Text
2022-10-20 15:21:241ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22050891
 10/18/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE FOLLOWING ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * GREASE AND SOLIDS INTERCEPTORS.
 * SAND INTERCEPTOR.
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL PERMIT APPLICATIONS FOR THOSE ITEMS
 HAVE BEEN SUBMITTED. YOU CAN SUBMIT AN APPLICATION TBD
 (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 2) SEPARATE PERMITS AND PLANS ARE ALSO REQUIRED FOR THE
 POOL, IRRIGATION SYSTEM, AND THE IRRIGATION SYSTEM
 BACKFLOW PREVENTER- SEC. 107.2.1 WPB. COMPLETE REVIEWS
 OF THOSE ITEMS ARE NOT BEING CONDUCTED AT THIS TIME.
 CONCERNING THE POOL- SHEET P103A SHOWS A FLOOR DRAIN IN
 THE POOL EQUIPMENT ROOM AND FLOOR DRAINS THAT APPEAR TO
 BE BELOW THE POOL SHELL POSSIBLY FOR POOL LEAKAGE OR
 DRAINAGE. THESE DRAINS ARE DISCHARGING INTO THE
 SANITARY SYSTEM. PLEASE BE ADVISED THAT POOL WASTEWATER
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM IN
 ACCORDANCE WITH SEC. 90-126(5) WPB CODE OF ORDINANCES.
 REVIEW THE INFORMATION BELOW:
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 3) PLUMBING FIXTURE CALCULATIONS- SHEETS LS100, LS101,
 LS2102, LS103, LS104, P SHEETS:
  
 A) LEVEL-1: PROVIDE 2 WATER CLOSETS FOR MALE USE AND 2
 WATER CLOSETS FOR FEMALE USE- TABLE 403.1 FBC P. THE
 FLOOR PLAN SHOWS ONE SINGLE USER TOILET ROOM WITH ONE
 WATER CLOSET IN THE BOH WHICH WILL NOT MEET COMPLIANCE.
 FIXTURES ARE REQUIRED FOR PUBLIC AND EMPLOYEE USE, AND
 SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE
 REQUIRED- SEC. 403.2 & 403.3. LAVATORIES FOR EACH
 SEPARATE TOILET ROOM ARE ALSO REQUIRED PER SEC. 403.7.
 B) LEVEL-1: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS
 FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC.
 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 C) LEVEL-1: PLEASE REVISE THE CALCULATION TABLE TO SHOW
 THE TOTAL PROVIDED NUMBER OF FIXTURES.
 D) LEVEL-2: OCCUPANT LOAD, RESTROOM LOCATIONS AND
 PLUMBING PIPING DETAILS HAVE BEEN PROVIDED FOR THE
 FUTURE OFFICE/STORAGE TENANT. PLEASE PROVIDE THE
 FIXTURE CALCULATIONS PER TABLE 403.1. PLEASE NOTE A
 MINIMUM OF TWO DRINKING FOUNTAINS FOR PUBLIC AND
 EMPLOYEE USE ARE REQUIRED- TABLE 403.1 AND SEC. 410.3.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 E) LEVEL-3: PLEASE LABEL THE RESTROOMS IN THE OFFICE
 AND BREAKROOM AS MALE, FEMALE, OR UNISEX- SEC. 403.4
 FBC P.
 F) LEVEL-3: BASED ON THE CALCULATIONS A 3RD FEMALE
 WATER CLOSET IS REQUIRED FOR THE A-3 AREA. THERE ARE
 ONLY 2 AVAILABLE IN THE SPA BATHROOMS- TABLE 403.1 FBC
 P.
 G) LEVEL-3: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS
 FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC.
 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 H) LEVEL-3: SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINK FOR THE OCCUPANCIES- TABLE 403.1.
 I) LEVEL-4: THE CALCULATION TABLE DOES NOT ACCOUNT FOR
 THE BAR AND DINING AREAS WHICH HAVE RATIOS OF 1 PER 40
 AND 1 PER 75 FOR WATER CLOSETS AND LAVATORIES- TABLE
 403.1. PLEASE PROVIDE A BREAKDOWN CALCULATION THAT
 INCLUDES THE SQ. FOOTAGE AND ASSOCIATED OCCUPANT LOADS
 OF ALL AMENITY AREAS AND REVISE THE TABLE ACCORDINGLY.
 J) LEVEL-4: SEC. 454.1.6.1.1 EXCEPTION FBC B ALLOWS FOR
 THE BUILDING TO PROVIDE THE REQUIRED NUMBER OF POOL
 BATHROOM FIXTURES HOWEVER INDIVIDUAL CALCULATION TABLES
 HAVE BEEN PROVIDED FOR THE ASSEMBLY OCCUPANCY AND THE
 POOL. PLEASE CLARIFY IF THE BATHROOMS BY THE DECK AND
 BAR ARE DESIGNATED FOR THE POOL AND LABEL THEM
 ACCORDINGLY. PLEASE NOTE SEC. 403.6.1 FBC P REQUIRES
 WOMEN'S POOL RESTROOMS TO HAVE A RATIO OF THREE TO TWO
 WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS PROVIDED FOR MEN. IT
 APPEARS ONE ADDITIONAL FEMALE WATER CLOSET IS REQUIRED.
 LAVATORY COUNTS SHALL BE EQUAL.
 K) LEVEL-4: PROVIDE AN AREA CALCULATION FOR THE POOL
 DECK TO SHOW COMPLIANCE WITH TABLE AND SEC. 403.6.1.
 THE FIXTURE COUNT OF TABLE 403.6 IS DEEMED TO BE
 ADEQUATE FOR THE POOL AND POOL DECK AREA THAT IS UP TO
 THREE TIMES THE AREA OF THE POOL SURFACE PROVIDED.
 L) LEVEL-4: CORRECT THE ASSEMBLY CALCULATION FOR MALE
 WATER CLOSETS TO INDICATE 1.39 REQUIRED. THE PLANS
 APPEAR TO INDICATE A SHORTAGE OF ONE MALE WATER CLOSET,
 ONE MALE LAVATORY, TWO FEMALE WATER CLOSETS, AND ONE
 FEMALE LAVATORY FOR THE ASSEMBLY OCCUPANCY.
 M) LEVEL-4: SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINK FOR THE OCCUPANCIES- TABLE 403.1.
  
 4) LS100: PLEASE UPDATE THE APPLICABLE CODE REFERENCES
 TO INDICATE THE 2020 FLORIDA BUILDING CODE 7TH EDITION
 WHICH IS THE CURRENT CODE IN EFFECT- SEC. 107.2.1 WPB.
 A) PLEASE ADD THE 2020 FBC ACCESSIBILITY 7TH EDITION TO
 THE APPLICABLE CODES LIST. COMPLIANCE WITH THE FBC ACC
 REQUIRES THAT A PERCENTAGE OF THE NEW DWELLING UNITS
 SHALL BE DESIGNED AND CONSTRUCTED MOBILITY FEATURES
 COMPLYING WITH SECS. 809.2- 809.4 AND COMMUNICATION
 FEATURES COMPLYING WITH SEC. 809.5. FACILITIES
 REGULATED BY THE DEPARTMENT OF HOUSING AND URBAN
 DEVELOPMENT (HUD)- SEC. 233.2 SHALL HAVE THE NUMBER OF
 UNITS IN COMPLIANCE DETERMINED BY HUD. FACILITIES NOT
 SUBJECT TO HUD SHALL HAVE AT LEAST 5% OF THE UNITS
 DESIGNED AND CONSTRUCTED WITH MOBILITY FEATURES AND 2%
 WITH COMMUNICATION FEATURES. TO HELP EXPEDITE THE
 REVIEW PLEASE PROVIDE A LIST OF APARTMENTS THAT ARE
 MEETING COMPLIANCE. PLEASE NOTE THE UNITS SHALL BE
 DISPERSED AMONG THE VARIOUS TYPES OF UNITS IN THE
 FACILITY- SEC. 233.3.5. CONCERNING THE TOILET AND
 BATHING FACILITIES PLEASE REFER TO SEC. 809.4 WHICH
 REFERENCES SECS. 603-610 FOR FIXTURE COMPLIANCE.
 CONCERNING PLUMBING FIXTURES AND APPLIANCES IN THE
 KITCHENS PLEASE REFER TO SECS. 809.3 & 804.
 B) COMPLIANCE WITH OTHER FEDERAL LAWS SUCH AS THE FAIR
 HOUSING ACT AND SECTION 504 OF THE REHABILITATION ACT
 OF 1973, AS AMENDED IS REQUIRED. PLEASE REFER TO THE
 FAIR HOUSING DESIGN ACT MANUAL FOR FURTHER INFORMATION-
 SEE PAGE 1 OF THE INTRODUCTION. CLARIFY HOW COMPLIANCE
 WITH THE ACT AND SAFE HARBOR FOR THE FACILITY IS BEING
 PROVIDED.
  
 5) SHEET A408 DETAILS 1-6: PLEASE PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCE INFORMATION:
 A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE
 WATER CLOSETS, LAVATORIES, AND URINAL- SECS. 604.3,
 605.3 & 606.2.
 B) DIAMETERS OF THE TURNING CIRCLES- SEC. 304.3 FBC
 ACC.
 C) ACCESSIBLE SHOWER DIMENSIONS- SECS. 213.3.6, 608.2.1
 AND/OR 608.2.2 FBC ACC.
 D) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWERS- SECS. 608.2.1 AND/OR 608.2.2.
 E) SHOW THE SAUNA AND STEAM ROOM BENCH LOCATIONS AND
 CLEAR FLOOR SPACE DIAGRAMS WITH DIMENSIONS- SEC. 612.2
 PLEASE PROVIDE ENLARGED BENCH DETAILS- SECS. 903.3-
 903.7.
 F) SHOW THE REQUIRED TURNING SPACES WITH DIMENSIONS
 INSIDE THE SAUNAS AND STEAM ROOMS- SECS. 612.3 & 304.1.
  
 6) A408: PROVIDE THE STANDARD TOILET COMPARTMENT
 DIMENSIONS- SEC. 405.3.1 FBC P.
  
 7) A810: PROVIDE ACCESSIBLE SHOWER DETAILS PER FBC ACC.
 A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECS. 608.3.1 AND/OR 608.3.2.
 B) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS-
 SECS. 608.5.1 AND/OR 608.5.2.
 C) LOCATION OF ACCESSIBLE SEATS AND MOUNTING DETAILS
 (IF APPLICABLE)- SECS. 610.3, 610.3.1, & 610.3.2.
  
 8) SHEETS A600- A-611, & A640- A645, A660- A665,
 A670-A681: A THOROUGH REVIEW OF THE RESIDENTIAL BATH
 AND KITCHEN PLUMBING FIXTURE INSTALLATIONS CANNOT BE
 CONDUCTED WITHOUT THE NECESSARY CODE REFERENCE DATA
 INFORMATION PROVIDED AS REQUESTED IN COMMENTS 4A & 4B
 ABOVE. TO HELP EXPEDITE THE RE- REVIEW PLEASE LABEL ALL
 UNITS THAT ARE ACCESSIBLE OR FHDA COMPLIANT AND PROVIDE
 COMPLETE KITCHEN AND BATH COMPLIANCE DETAILS.
  
 9) SHEET P100: THE DRAINAGE FROM THE SAND INTERCEPTOR
 SHALL DISCHARGE INTO THE SANITARY SEWER AND NOT INTO
 THE STORM DRAIN PER SEC. 90- 203(A) WPB CODE OF
 ORDINANCES. SEC. 90-203. - PROHIBITED GENERAL
 PROHIBITION. EXCEPT AS PROVIDED IN SECTION 90-205, AND
 EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY
 DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE
 PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM
 WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED
 ENTIRELY OF STORMWATER.
 IF YOU HAVE FURTHER QUESTIONS PLEASE CONTACT-
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS ST., 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-494-1120
 FAX: 561-494-1116
 CELL 561-351-0510
 [email protected]
  
 10) SHEETS P100 & P501 DETAIL 6: AS NOTED IN COMMENT #1
 THE SAND INTERCEPTOR SHALL BE INSTALLED UNDER A
 SEPARATE PERMIT, HOWEVER PLEASE CLARIFY IF THE UNIT IS
 ALSO AN OIL INTERCEPTOR PER SEC. 1003.4- 1003.4.2.1 FBC
 P.
 PLEASE NOTE THAT OIL/SAND INTERCEPTORS SHALL BE LISTED
 OR COMPLY WITH SEC. 1003.4.2.1 GENERAL DESIGN
 REQUIREMENTS- OIL SEPARATORS SHALL HAVE A DEPTH OF NOT
 LESS THAN 2 FEET BELOW THE INVERT OF THE DISCHARGE
 DRAIN. THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE
 NOT LESS THAN AN 18-INCH WATER SEAL. THE DETAIL SHOWS
 THE DEPTH IS TOO SHALLOW. PLEASE PROVIDE MORE
 INFORMATION ABOUT THE UNIT INCLUDING HOW IT WILL BE
 PROTECTED FROM VEHICULAR DAMAGE ABOVE. CLARIFY IF THE
 PIT ACCESS LID SHOWN IN THE DETAIL IS HEAVY DUTY
 TRAFFIC RATED AND IS EQUIPPED WITH AN ACCESS
 RESTRICTOR- SEC. 107.2.1 WPB.
 A) PROVIDE DIMENSIONED CONCRETE VAULT CONSTRUCTION AND
 BURIAL DETAILS- SEC. 107.2.1 WPB.
  
 11) P100, P101C & P503: AS NOTED IN COMMENT #1 THE
 GREASE AND SOLIDS INTERCEPTORS SHALL BE INSTALLED UNDER
 A SEPARATE PERMIT. A COMPLETE PLAN SUBMITTAL WILL BE
 REQUIRED AT THAT TIME WHICH SHALL INCLUDE THE FOLLOWING
 ITEMS:
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 B) EQUIPMENT SCHEDULE INDICATING THE MAKES, MODELS AND
 CAPACITIES OF THE UNITS.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) DIMENSIONED TANK BURIAL, ANCHORING, AND BACKFILLING
 DETAILS.
 E) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL
 VENTS, AND SAMPLING PORTS.
 F) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY
 DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS
 RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR
 CLEANOUTS, AND SAMPLING PORTS (IF INSTALLED).
  
 12) P100: PLEASE INDICATE THE SIZE OF THE MAIN STORM
 DRAIN PIPE EXISTING ON THE NORTH SIDE OF THE BUILDING-
 SEC. 107.2.1 WPB.
  
 13) P101A: THE MAIN SOIL, WASTE AND VENT STACK
 CONNECTIONS TO THE BUILDING DRAIN ARE SHOWN HOWEVER
 THERE ARE NO CONTINUOUS ISOMETRIC DRAWINGS SUBMITTED
 THAT CLEARLY SHOW STACK RUNS FROM THE FOUNDATION TO THE
 ROOF- SEC. 904.2, 904.3, & 904.4. TO HELP EXPEDITE THE
 REVIEW PLEASE PROVIDE THE ISOMETRICS WHICH SHALL ALSO
 SHOW THE LOCATIONS OF RELIEF VENTS WHERE REQUIRED PER
 SEC. 908.1 AND SEC. 107.3.5.3.1 WPB.
 A) PLEASE NOTE SEC. 913.2 PROHIBITS EITHER VERTICAL OR
 HORIZONTAL OFFSETS IN THE WASTE STACK SERVING THE
 WASHING MACHINES IN THE DWELLING UNITS BETWEEN THE
 LOWEST AND HIGHEST FIXTURE DRAIN CONNECTIONS. PLEASE
 PROVIDE THE ISO FOR THE STACK.
 B) PLEASE NOTE SEC. 913.3 REQUIRES A STACK VENT FOR THE
 WASTE STACK WHICH SHALL NOT BE LESS THAN THE SIZE OF
 THE WASTE STACK.
  
 14) P101A: PROVIDE A 3-INCH VENT AT (S20). THE PLAN
 SHOWS A 2-INCH- SEC. 904.4 FBC P.
  
 15) P101A: (S16) NOTE INDICATES A 4-INCH SANITARY BUT
 IT APPEARS TO BE AN 8-INCH. PLEASE SEE THE RISER ON
 SHEET P101C.
  
 16) P101B: PLEASE SHOW THE LOCATION OF THE 8-INCH RISER
 CALLED OUT IN NOTE (S21)- SEC. 107.2.1 WPB.
  
 17) P102A, P104A, P105, P106: THE 4-INCH VENT STACK
 CONTINUATION FROM THE 1ST FLOOR IS NOT SHOWN- SEC.
 904.4 FBC P. IT RE-APPEARS ON P107.
  
 18) P201B, P201C: TO HELP EXPEDITE THE REVIEW PLEASE
 PROVIDE COMPLETE WATER RISER DRAWINGS THAT SHOW THE
 UPFEEDING LINES FROM THE GROUND FLOOR AND THE
 DOWNFEEDING LINES FROM THE TOP FLOORS INCLUDING THE HW
 RECIRCULATION SYSTEM LOOP FROM THE HOT WATER HEATERS ON
 THE ROOF DOWN THROUGH THE BUILDING- SEC. 607.2 FBC P.
 AND SEC. 107.3.5.1.3 WPB. PLEASE NOTE THAT THE
 DEVELOPED LENGTH OF HOT WATER OR TEMPERED WATER PIPING
 FROM THE SOURCE OF HOT WATER TO FIXTURES REQUIRING HOT
 OR TEMPERED WATER SHALL NOT EXCEED 50 FT.
  
 19) P202B, P202C: THE HWR LINE DOES NOT APPEAR TO BE
 MAKING A CONNECTION BACK INTO THE HW LINE. PLEASE REFER
 TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE IS THE HOT
 WATER SOURCE AND THE 1/2-INCH HW FIXTURE SUPPLY PIPES
 TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2 FT.
 ALLOWABLE LENGTHS FROM THE HW SOURCE.
  
 20) P203A, P203B, P203C: THE HWR LINES DO NOT APPEAR TO
 BE MAKING COMPLETE LOOPS DOWN TO ALL THE LAVATORIES.
 PLEASE REFER TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE
 IS THE HOT WATER SOURCE AND THE 1/2-INCH HW FIXTURE
 SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THEIR
 MAXIMUM 2 FT. ALLOWABLE LENGTHS FROM THE HW SOURCE.
  
 21) P202B, P202C, P203A, P203B, P203C: INDICATE HOW
 TEMPERED WATER WILL BE PROVIDED TO THE PUBLIC
 LAVATORIES- SEC. 419.5 FBC P.
  
 22) P203B NOTE D15: PLEASE INDICATE THE MAKE AND MODEL
 OF THE ASSE 1013 RPZ TO PROTECT THE POTABLE WATER LINE
 TO THE IRRIGATION SYSTEM- SECS. 608.3 & 608.17.5 FBC P.
 TO HELP EXPEDITE THE REVIEW PLEASE ADD A BACKFLOW
 ASSEMBLY SCHEDULE FOR ALL DEVICES TO SHEET P503- SEC.
 107.2.1 WPB.
  
 23) P204A: PROVIDE A WATER RISER DRAWING FOR THE
 RESTROOMS- SEC. 107.3.5.1.3 WPB. PLEASE NOTE COMMENTS
 18 & 19 ABOVE PERTAINING TO THE HW SOURCE AND TEMPERED
 WATER REQUIREMENT.
  
 24) P204B: PLEASE MODIFY NOTE D23 TO INDICATE ASSE 1022
 APPROVED BACKFLOW PREVENTERS FOR CARBONATED BEVERAGE
 DISPENSERS, AND ASSE 1024 APPROVED BACKFLOW PREVENTERS
 FOR NON- CARBONATED BEVERAGES- SECS. 608.17.1.1 &
 608.17.1.2 FBC P.
  
 25) P210: PLEASE SHOW THE COOLING TOWER MAKEUP WATER
 LINE CONTINUATION TO THE TOWERS- SEC. 107.2.1 WPB.
  
 26) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD
 NOTES TO INDICATE WATER HAMMER ON LINES SUPPLYING THE
 DISHWASHERS, WASHING MACHINES AND REFRIGERATOR ICE
 MAKERS- SEC. 604.9 FBC P.
  
 27) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD
 NOTES INDICATING BACKFLOW PREVENTERS WILL BE INSTALLED
 ON LINES SUPPLYING THE REFRIGERATOR ICE MAKERS- SEC.
 608.3 FBC P. PLEASE SPECIFY THE MAKE AND MODEL OF THE
 DEVICES AND INCLUDE IN THE SCHEDULE ON P503.
 A) PLEASE INDICATE THE TYPE, SIZE AND R-VALUE OF HW AND
 HWR PIPE INSULATION PER TABLE C403.2.10 FBC EC. NOTES
 OR DETAILS SHALL BE PLACED ON THE DWELLING UNIT PLANS
 AND THE NON-RESIDENTIAL PLANS AND RISERS.
  
 28) P329: PLEASE INDICATE WHICH SHEET HAS THE SANITARY
 PIPING LAYOUT AND ISOMETRIC DRAWINGS FOR THESE UNITS C1
 & D1- SEC. 107.2.1 WPB.
  
 29) P330- P340: THESE TYPICAL UNIT PLANS DO NOT HAVE
 SANITARY PIPING LAYOUT AND ISOMETRIC DRAWINGS- SEC.
 107.2.1 WPB.
  
 30) P421: PLEASE PROVIDE THE AREA PLANS AND DRAINAGE
 CALCULATIONS THAT MATCH WITH THESE STORM WATER
 ISOMETRIC DRAWINGS- SEC. 107.2.1 WPB AND SEC. 1106.1
 FBC P.
  
 31) P402C: PLEASE PROVIDE A BRIDGE ROOF DRAINAGE PLAN
 AND DRAINAGE CALCULATIONS- SEC. 1106.1 FBC P.
  
 32) P421, P422, P423: TO HELP EXPEDITE THE REVIEW,
 PLEASE INDICATE THE ROOF DRAINAGE GPM'S AT THE ROOF
 DRAINS AND THE ACCUMULATIVE FLOW THROUGH THE BUILDING
 TO THE GROUND LEVEL MAIN STORM DRAINS- SEC. 1106.1,
 TABLES 1106.2 & 1106.3 FBC P.
  
 31) P501 DETAIL 10: PLEASE SHOW A DEDICATED SHUTOFF
 VALVE FOR THE COLD WATER FEED TO THE WATER HEATER- SEC.
 503.1 FBC P.
  
 32) LS104, P104C, P104D: SHEET LS104 SHOWS TWO BARS ON
 THE DECK, PRIVATE AND OUTDOOR DINING, GRILLS, AND A
 MAIN KITCHEN AND SHOW KITCHEN. THE PLUMBING PLANS DO
 NOT SHOW ANY PIPING AT THE LOCATION OF THE BAR ON THE
 NW SIDE OF THE DECK, AND DO NOT SHOW ANY MEANS OF
 SEPARATING AND DISPOSING OF GREASE FROM THE FIXTURE
 DRAINAGE FLOWS INTO THE SANITARY SYSTEM- SEC. 1003.3.1
 FBC P, AND SEC. 107.2.1 WPB. PLEASE REFER TO COMMENT
 #11 FOR GREASE INTERCEPTOR SUBMITTAL REQUIREMENTS AS
 APPLICABLE.
  
 33) P203A P503: THE LOCATIONS OF THE STEAM GENERATORS
 IN THE STEAM ROOMS, THE WATER SUPPLY TO THE UNITS, AND
 DRAINAGE DISPOSAL DETAILS ARE NOT SHOWN ON THE PLANS-
 SEC. 107.2.1 WPB.
  
 34) P502, P503: PLEASE LABEL THE TWO UNIDENTIFIED
 PIECES OF EQUIPMENT IN THE CORNER OF THE BOILER ROOM
 AND PROVIDE EQUIPMENT SCHEDULES- SEC. 107.2.1 WPB.
  
 35) P502: PLEASE INDICATE THE SIZE OF THE WATER SUPPLY
 PIPE LEAVING THE BOILER ROOM TO SUPPLY THE BUILDING,
 AND INCLUDE THE TEMPERATURE OF THE WATER- SEC. 607.1
 FBC P.
  
 36) P101B: AN OIL INTERCEPTOR MAY BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM THE TRASH COMPACTOR FOR
 SEPARTION AND DISPOSAL. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR REVIEW- SEC. 1003.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  