2022-10-17 13:24:521ST REVIEW FMC
 PERMIT: 22050891
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADD A NOTE ON THE MECHANICAL DRAWING STATING THAT
 THE GENERATOR WILL REQUIRE A SEPARATE APPLICATION WITH
 DOCUMENTS AND SEPARATE PLAN REVIEW AS THE GENERATOR
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 REFRIGERATION EQUIPMENT WILL REQUIRE A SEPARATE PERMIT
 APPLICATION AND A SEPARATE REVIEW AS IT WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 4) SHEET M201A1: THE BATHROOM IN THE BOH AREA IS
 MISSING AN EXHAUST FAN AND EXHAUST DUCT. PLEASE REVISE
 THE DRAWING TO INCLUDE THE EXHAUST FAN, DUCT AND DUCT
 TERMINATION LOCATION. FMC 501.3
  
 5) SHEET M201A1: THERE IS A SYMBOL IN THE BATHROOM IN
 THE BOH AREA THAT APPEARS TO BE A DAMPER. PLEASE
 IDENTIFY AND STATE THE PURPOSE OF THIS ITEM. FBC
 107.3.5
  
 6) SHEET M201A1: THE MAIL ROOM SHOWS ONLY RETURN AIR
 DUCTWORK, PLEASE INDICATE THE SUPPLY AIR FOR THIS AREA?
 FBC 107.3.5
  
 7) SHEET M201A1: THE LOUNGE, GALLERY AND CONCIERGE
 AREAS DO NOT SHOW ANY RETURN DUCTWORK, PLEASE SHOW THE
 RETURN AIR PATH FROM THESE AREAS TO THE AHU-1-1. FMC
 601.6
  
 8) SHEET M201A1: THE DUCT SMOKE DETECTOR IS SHOWN IN
 THE RETURN SIDE OF AHU-1-1. REVISE THE DRAWING TO SHOW
 A DUCT SMOKE DETECTOR IN THE SUPPLY DUCT OF AHU1-1. FMC
 606.2.1
  
 9) SHEET M201A1: THE EF-A IN THE BOH AREA IS NOT LISTED
 IN THE FAN SCHEDULE ON SHEET M502. PLEASE IDENTIFY THIS
 EF AND EXPLAIN WHAT IT IS EXHAUSTING. FBC 107.3.5
  
 10) SHEET M201B1: THE STAIR WAY 2 CORRIDOR IS AN EXIT
 PASSAGEWAY. REVISE THE MECHANICAL DRAWING TO REMOVE ALL
 DUCTWORK FROM THIS EXIT PASSAGEWAY. FMC 601.3
  
 11) SHEET M201B1: EF-1-4 EXHAUST TERMINATION LOCATION
 MUST MEET THE EXCEPTION OF FMC 501.3.1
  
 12) SHEET M201B1: EF-1-3 APPEARS TO BE EXHAUSTING INTO
 THE LOADING DOCK ACCORDING TO LS101. PLEASE REVISE THE
 DRAWING TO SHOW THAT EF-1-3 IS EXHAUSTING TO THE
 EXTERIOR OF THE BUILDING AND MEETING THE TERMINATION
 REQUIREMENTS OF FMC 501.3.1
  
 13) SHEET M201B1: PLEASE EXPLAIN AHU-1-17 BEING IN THE
 RETAIL/OFFICE TRASH COMPACTOR AREA. FBC 107.3.5
  
 14) SHEET M201A1, SHEET M301: IT APPEARS THAT THE
 EXHAUST DUCTS FOR STUDIO UNITS C AND D PASS THROUGH
 RATED WALLS INTO STUDIO B UNIT. PLEASE REVISE THE
 DRAWING TO INDICATE HOW THESE PENETRATIONS WILL BE
 PROTECTED. FMC 607.5
  
 15) SHEET M202A1: PLEASE EXPLAIN THE 18 X 10 INCH OA
 DUCTWORK PASSING THROUGH THE RATED WALL OF THE CORRIDOR
 AND STUDIO A. WHAT IS IT???S PURPOSE? FBC 107.3.5
  
 16) SHEET M202A1: ALL OF THE EXHAUST IN THE LIVING
 UNITS MUST MEET THE 3 FEET CLEARANCE FROM OPENINGS FOR
 EXHAUST TERMINATION LOCATION. FMC 501.3.1-3
  
 17) ALL SHEETS SHOWING THE BATHROOMS HAVING RETURN AIR
 DUCTS, REVISE THESE DRAWINGS TO REMOVE THE RETURN AIR
 DUCTS FROM THE BATHROOMS. FMC 601.5;7
  
 18) SHEET M202B1: NOTES 60 61 ARE FOR THE EXHAUST FAN
 OUT SIDE OF THE TRASH CHUTE. PLEASE SHOW THE RATED
 SHAFT THAT THIS SUBDUCT WILL ENTER. FBC 107.3.5
  
 19) SHEET M203A1: REVISE THE DRAWING TO INDICATE THE
 BATHROOM EXHAUST CFM???S. FMC TABLE 403.3.1.1
  
 20) * SHOW THAT THE OUTDOOR AIR DUCTS FOR EACH UNIT
 SHALL NOT TERMINATE AT A WALL REGISTER IN THE
 FIRE-RESISTANCE-RATED WALL. FMC 607.5.3 EXCEPTION 3.5
  
 21) SHEET M203B1: NOTES 60 61 ARE FOR THE EXHAUST FAN
 OUT SIDE OF THE TRASH CHUTE. PLEASE SHOW THE RATED
 SHAFT THAT THIS SUBDUCT WILL ENTER. FBC 107.3.5
  
 22) SHEET M203B2: REVISE THE DRAWING TO EXPLAIN THE 16
 X 30 AND 18 X 36 OA DUCTS IN THE OFFICE AREA OF THIS
 FLOOR. ALSO NOTE WHERE THEY ORIGINATE. FBC 107.3.5
  
 23) PROVIDE THE DRYER DUCT MATERIAL, SIZE AND LENGTH
 FOR EACH UNIT INCLUDE ALL 45 AND 90 DEGREE BENDS, OR
 PROVIDE THE SPECIFIC DRYERS TO BE USED AND THE DRYER
 MAX. LENGTH CHART FROM THE MANUFACTURER. FMC 504.8.4
 AND 504.8.4.2
  
 24) PROVIDE DUCT SIZES AND MOTOR CFM???S FOR THE
 KITCHEN HOODS OF EACH UNIT. FMC 505.1 AND 505.2
  
 25) SOME OF THE UNITS HAVE THE TRANSFER GRILLES FOR THE
 MAKE UP AIR FOR THE DRYER EXHAUST AND SOME DO NOT.
 PLEASE SHOW THE DRYER EXHAUST CFM???S OR PROVIDE THE
 MAKE UP AIR TRANSFER GRILLE FOR THE DRYERS IN EACH
 UNIT. FMC 504.6
  
 26) SHEET M305: PLEASE REVISE THE UNIT TYPE J TO
 INCLUDE THE MISSING DUCTWORK. FBC 107.3.5
  
 27) SHEET M502: THE BEAUTY AND NAIL SALONS LISTED
 TOGETHER IN THE VENTILATION CALCULATIONS SHOULD BE
 SEPARATED AND LIST EACH SEPARATELY AS THEY ARE LISTED
 SEPARATELY IN FMC TABLE 403.3.1.1. ALSO ADDA NOTE FOR
 THE REQUIREMENTS IN FMC TABLE 403.3.1.1 FOOTNOTE H.
  
 28) PROVIDE A TRASH CHUTE AND VENT RISER DIAGRAM. FMC
 601.1 AND NFPA 82-2014
  
 29) PROVIDE A PARKING GARAGE MECHANICAL VENTILATION
 DESIGN ACCORDING TO FMC 404.1
  
 30) SHEET M203A2: PLEASE SPECIFY WHICH OA UNIT IS
 SUPPLYING THE 38 X 14 INCH OA SD-28. FBC 107.3.5
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  