| Date |
Text |
| 2022-08-12 11:20:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION OF SMOKE CONTROL NOR A |
| | RATIONAL ANALYSIS DOCUMENT. |
| | |
| | PER NFPA 1 |
| | |
| | 11.8* SMOKE CONTROL. |
| | 11.8.1 NEWLY INSTALLED SMOKE-CONTROL SYSTEMS SHALL BE |
| | IN SPECTED BY THE AHJ AND TESTED IN ACCORDANCE WITH THE |
| | CRITERIA |
| | ESTABLISHED IN THE APPROVED DESIGN DOCUMENTS, NFPA 204 |
| | AND |
| | NFPA 92. |
| | 11.8.2 SMOKE-CONTROL SYSTEMS SHALL HAVE AN APPROVED |
| | MAINTE NANCE AND TESTING PROGRAM TO ENSURE OPERATIONAL |
| | INTEGRITY IN |
| | ACCORDANCE WITH THIS SECTION. COMPONENTS OF SUCH |
| | SYSTEMS |
| | SHALL BE OPERATED, MAINTAINED, AND TESTED IN ACCORDANCE |
| | WITH |
| | THEIR OPERATION AND MAINTENANCE MANUALS. |
| | 11.8.2.1 TESTING. OPERATIONAL TESTING OF THE |
| | SMOKE-CONTROL SYS TEM SHALL BE IN ACCORDANCE WITH NFPA |
| | 92, AND SHALL INCLUDE ALL |
| | EQUIPMENT RELATED TO THE SYSTEM INCLUDING, BUT NOT |
| | LIMITED TO, |
| | INITIATING DEVICES, FANS, DAMPERS, CONTROLS, DOORS, AND |
| | WINDOWS. |
| | 11.8.2.1.1 AN APPROVED WRITTEN SCHEDULE FOR SUCH |
| | OPERATIONAL |
| | TESTS SHALL BE ESTABLISHED. |
| | 11.8.2.2 TEST RECORDS SHALL BE MAINTAINED ON THE |
| | PREMISE |
| | AND MUST INDICATE THE DATE OF SUCH TESTING, THE |
| | QUALIFIED SER VICE PERSONNEL, AND ANY CORRECTIVE |
| | MEASURES NEEDED OR TAKEN |
| | |
| | PLEASE PROVIDE THE PROPOSED DOCUMENTS REGARDING THE |
| | BUILDINGS' SMOKE CONTROL FOR REVIEW. |
| | |
| | |
| | 2) THERE IS AN INDICATION OF A COMMAND CENTER BUT NO |
| | INDICATION OF WHAT EQUIPMENT/LIFE SAFETY MONIOTRING |
| | WILL BE INCLUDED WITHIN THE COMMAND CENTER |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE |
| | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL |
| | BE APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER |
| | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| | HOUR. |
| | |
| | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| | 10 FT (3050 MM). |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE. |
| | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION |
| | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | NFPA 101 |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF |
| | COMPLIANCE. |
| | |
| | |
| | 3) IT APPEARS THAT THE FIRE PUMP IS ELECTRIC, BUT THERE |
| | IS NO DETAILED BACKUP POWER SOURCE NOR THE FUEL SUPPLY |
| | OF THE BACKUP POWER SOURCE. |
| | |
| | PER NFPA 70 AND NFPA 20 |
| | |
| | NFPA 20 |
| | |
| | 9.3 ALTERNATE POWER. |
| | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT |
| | LEAST |
| | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE |
| | THE |
| | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY |
| | OF THE |
| | FIRE DEPARTMENT APPARATUS. |
| | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT |
| | DESCRIBED IN |
| | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE |
| | PROVIDED |
| | WHERE THE NORMAL SOURCE IS NOT RELIABLE. |
| | 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE |
| | PUMP |
| | SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE |
| | PUMP, |
| | BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP |
| | ELECTRIC |
| | MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE |
| | MEET ING 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS |
| | STANDARD. |
| | 9.3.4 WHERE PROVIDED, THE ALTERNATE SOURCE OF POWER |
| | SHALL BE |
| | SUPPLIED FROM ONE OF THE FOLLOWING SOURCES: |
| | (1) A GENERATOR INSTALLED IN ACCORDANCE WITH SECTION |
| | 9.6 |
| | (2) ONE OF THE SOURCES IDENTIFIED IN 9.2.2(1), |
| | 9.2.2(2), 9.2.2(3), |
| | OR 9.2.2(5) WHERE THE POWER IS PROVIDED INDEPENDENT OF |
| | THE |
| | NORMAL SOURCE OF POWER |
| | 9.3.5 WHERE PROVIDED, THE ALTERNATE SUPPLY SHALL BE |
| | ARRANGED |
| | SO THAT THE POWER TO THE FIRE PUMP IS NOT DISRUPTED |
| | WHEN OVER |
| | |
| | NFPA 70 |
| | |
| | ARTICLE 695 FIRE PUMPS |
| | |
| | 695.3 POWER SOURCE(S) FOR ELECTRIC MOTOR-DRIVEN FIRE |
| | PUMPS. ELECTRIC MOTOR-DRIVEN FIRE PUMPS SHALL HAVE A |
| | RELI ABLE SOURCE OF POWER. |
| | (A) INDIVIDUAL SOURCES. WHERE RELIABLE, AND WHERE CA |
| | PABLE OF CARRYING INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR |
| | RRENT OF THE FIRE PUMP MOTOR(S) AND THE PRESSURE MAINTE |
| | NANCE PUMP MOTOR(S) AND THE FULL-LOAD CURRENT OF THE |
| | ASSO CIATED FIRE PUMP ACCESSORY EQUIPMENT WHEN |
| | CONNECTED TO |
| | THIS POWER SUPPLY, THE POWER SOURCE FOR AN ELECTRIC |
| | MOTOR |
| | DRIVEN FIRE PUMP SHALL BE ONE OR MORE OF THE FOLLOWING. |
| | |
| | 1) ELECTRIC UTILITY SERVICE CONNECTION. |
| | A FIRE PUMP SHALL BE PERMITTED TO BE SUPPLIED BY A |
| | SEPARATE SERVICE, OR FROM A |
| | CONNECTION LOCATED AHEAD OF AND NOT WITHIN THE SAME |
| | CABI NET, ENCLOSURE, VERTICAL SWITCHGEAR SECTION, OR |
| | VERTICAL |
| | SWITCHBOARD SECTION AS THE SERVICE DISCONNECTING MEANS. |
| | THE CONNECTION SHALL BE LOCATED AND ARRANGED SO AS TO |
| | MINI MIZE THE POSSIBILITY OF DAMAGE BY FIRE FROM WITHIN |
| | THE |
| | PREMISES AND FROM EXPOSING HAZARDS. A TAP AHEAD OF THE |
| | SER VICE DISCONNECTING MEANS SHALL COMPLY WITH |
| | 230.82(5). THE |
| | SERVICE EQUIPMENT SHALL COMPLY WITH THE LABELING |
| | REQUIRE MENTS IN 230.2 AND THE LOCATION REQUIREMENTS IN |
| | 230.72(B). |
| | [20:9.2.2(1)] |
| | |
| | 2) ON-SITE POWER PRODUCTION FACILITY. A FIRE PUMP SHALL |
| | BE PERMITTED TO BE SUPPLIED BY AN ON-SITE POWER |
| | PRODUCTION |
| | FACILITY. THE SOURCE FACILITY SHALL BE LOCATED AND |
| | PROTECTED TO |
| | MINIMIZE THE POSSIBILITY OF DAMAGE BY FIRE. |
| | [20:9.2.2(3)] |
| | (3) DEDICATED FEEDER. A DEDICATED FEEDER SHALL BE |
| | PERMIT TED WHERE IT IS DERIVED FROM A SERVICE |
| | CONNECTION AS DE SCRIBED IN 695.3(A)(1). [20:9.2.2(3)] |
| | (B) MULTIPLE SOURCES. IF RELIABLE POWER CANNOT BE OB |
| | TAINED FROM A SOURCE DESCRIBED IN 695.3(A), POWER SHALL |
| | BE |
| | SUPPLIED BY ONE OF THE FOLLOWING: [20:9.3.2] |
| | (1) INDIVIDUAL SOURCES. AN APPROVED COMBINATION OF TWO |
| | OR MORE OF THE SOURCES FROM 695.3(A). |
| | (2) INDIVIDUAL SOURCE AND ON-SITE STANDBY GENERATOR. |
| | AN APPROVED COMBINATION OF ONE OR MORE OF THE SOURCES |
| | IN |
| | 695.3(A) AND AN ON-SITE STANDBY GENERATOR COMPLYING |
| | WITH |
| | 695.3(D). [20:9.3.4] |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS IN |
| | COMPLIANCE AND/OR CONFIRM THAT THE FIRE PUMP WILL BE |
| | BACKED-UP BY THE DIESEL GENERATOR AND THAT THE |
| | GENERATOR COMPLIES WITH NFPA 110 & 37. |
| | |
| | |
| | |
| | 4) SHEET FA 201 - THERE IS A TWO-WAY COMMUNCATION RISER |
| | DIAGRAM. |
| | |
| | ANY TWO-WAY COMMUNCATION SYSTEM SHALL BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | HOWEVER, ANY SYSTEM SHALL BE SUBMITTED TO THE FIRE |
| | MARSHAL AND MARK FILLA PALM BEACH COUNTY RADIO MANAGER. |
| | |
| | DAQ TESTS AND RSSI/DBM LEVELS WILL NEED TO BE COMPLETED |
| | AT SUBSTANTIAL CONSTRUCTION (WALLS AND WINDOWS) PRIOR |
| | TO ANY PERMIT SUBMITTALS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON |
| | THIS SHEET. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| 2022-07-28 10:56:59 | |
| | |