2022-10-17 17:10:38FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) E-102A MAIN ELECTRICAL ROOM LAYOUT
  
 110.26(C)(2)(A,B) EGRESS PATH CROSSING IN FRONT OF
 MS-R2 AT THE DOOR, YOU HAVE TO TRAVEL THROUGH THE
 REQUIRED WORKING SPACE IN ORDER TO EXIT THE ROOM.
 PLEASE PROVIDE A CLEAR UNOBSTRUCTED PATH.
  
 110.26(C)(2)(B) EXTRA WORKING SPACE. WHERE THE DEPTH OF
 THE WORKING SPACE IS TWICE THAT REQUIRED BY
 110.26(A)(1), A SINGLE ENTRANCE SHALL BE PERMITTED. IT
 SHALL BE LOCATED SUCH THAT THE DISTANCE FROM THE
 EQUIPMENT TO THE
 NEAREST EDGE OF THE ENTRANCE IS NOT LESS THAN THE
 MINIMUM CLEAR DISTANCE SPECIFIED IN TABLE 110.26(A)(1)
 FOR EQUIPMENT OPERATING AT THAT VOLTAGE AND IN THAT
 CONDITION.
  
 2) E-301, 302 LOAD CALCULATIONS LOAD CALCULATIONS SHOWN
 USE A DEMANDED LOAD CALCULATION AND THEN AGAIN DEMAND
 IT FOR A FINAL LOAD??? PLEASE SHOW HOW YOUR LOAD CALC
 COMPLIES WITH 220.84 OR WHATEVER YOU ARE USING.
  
 3) E-502 RISER DIAGRAM PLEASE SHOW COMPLIANCE WITH
 700.3(F) FOR BACKUP GENERATOR.
  
 700.3 (F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR
 REPAIR OF THE ALTERNATE SOURCE OF POWER.
  
 4) THE FOLLOWING SYSTEMS SHALL BE REQUIRED TO GET
 SEPARATE PERMITS LIGHTNING PROTECTION, POOL, GENERATOR,
 FIRE ALARM, BDA, SECURITY, ACCESS CONTROL ECT. ECT.