| 2022-07-07 09:10:46 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 22050866 |
| | 7/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS RISER IS INCOMPLETE BECAUSE IT DOES NOT |
| | INCLUDE THE EXISTING GAS PIPING AND APPLIANCES ALREADY |
| | CONNECTED TO THE METER AND APPROVED UNDER PERMITS- |
| | 02101227 & 15110062. PLEASE REFER TO SECS. G2412.2 & |
| | G2412.3 FBC RES AND PROVIDE A COMPLETE GAS RISER THAT |
| | SHOWS ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT |
| | THE RESIDENCE. THE RISER SHALL SHOW: |
| | A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | B) TYPES AND SIZES OF PIPING. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS, |
| | AND PIPE UNIONS. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | G) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | H) PIPE SIZING TABLES. |
| | |
| | 2) PLEASE CORRECT THE SURVEY DRAWING TO SHOW THE |
| | GENERATOR SHALL BE LOCATED A MINIMUM OF 10 FT. FROM THE |
| | AIR INTAKE OPENINGS INTO THE BUILDING INCLUDING |
| | OPERABLE WINDOWS AND DOORS- SEC. R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |