| Plan Review Notes For Permit 22050860 |
| Permit Number |
22050860 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-28 08:46:26 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE | | | REPORT PREPARED BY A FLORIDA REGISTERED DESIGN | | | PROFESSIONAL. | | | 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH | | | TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY | | | LIMITATIONS 5.6.2 OF PRODUCT APPROVAL FL2533-R28. | | | 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL2533-R28 SYSTEM NO. R-24 DOES NOT MEET THE | | | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 | | | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT | | | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR | | | EXPOSURE CATEGORY C AS PER LIMITATIONS #5.7.3. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|