Plan Review Notes
Plan Review Notes For Permit 22050857
Permit Number 22050857
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2022-08-05 15:25:37NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 1ST REVIEW
  
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE (EC)
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR THIS SITE
 IS X-500 AND AE 6 WITH A BASE FLOOD ELEVATION (BFE) OF
 6?0? NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 8?0? NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
  
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
 SEC. 18-34 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, BUILDING.
 (A) SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIR, RECONSTRUCTION, REHABILITATION, ALTERATION,
 ADDITION OR OTHER IMPROVEMENT OF A BUILDING OR
 STRUCTURE FOR WHICH THE CUMULATIVE COST IN ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
 VALUE ...
  
 2. PROVIDE A CURRENT BOUNDARY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PLEASE REFERENCE PLAN PAGE A-1.0 FOR THE FOLLOWING
 COMMENTS:
 3A) NOTE STATES FLOOD OPENINGS ARE GREENHECK MODEL
 AFJ601X ACCOUSTICAL VENTS.
 THESE ARE NOT APPROVED VENTS FOR FLOOD WATERS.
  
 4. INSTALL FLOOD OPENINGS PER FEMA TECH. BULLETIN #1,
 SECTION 9.
  
 5. PLAN PAGE A-1.0 SHOWS 3-24X36 FLOOD OPENINGS
 (GREENHECK) LOCATED ON ONE WALL. SECTION A9B) OF THE EC
 SHOWS 5 FLOOD OPENINGS. PLEASE CLARIFY.
 YOU MAY USE NON-ENGINERED FLOOD OPENINGS PER SECTION
 9.2 OF FEMA TECHNICAL BULLITEN #1 OR ENGINEERED FLOOD
 OPENINGS PER SECTION 9.3 OF FEMA TECHNICAL BULLITEN #1.
  
 NOTICE ONLY: GARAGE IS 498 SF.
  
 6. SECTION A2 OF EC STATES CITY IS WELLINGTON. THIS
 MUNICIPALITY IS WEST PALM BEACH. PLEASE CORRECT.
  
 7. SECTION C2(G) STATES HIGHEST ADJACENT GRADE AS 6.1'.
 HIGHEST ADJACENT GRADE IS 7.8' LOCATED AT EAST
 ELEVATION OF LOT. PLEASE CORRECT.
  
 NOTICE; SUBMIT A REVISION TO PLAN PAGE A-1.0 UNDER
 MASTER PERMIT 18060620 WITH THE CORRECT NUMBER OF FLOOD
 OPENINGS LOCATED ON ADJACENT WALLS PER FEMA TECHNICAL
 BULLETIN #1.
  
 8. IF ENGINEERED FLOOD VENTS ARE USED, PROVIDE THE
 FLORIDA PRODUCT APPROVALS AND THE ICC-ES REPORT FOR
 EACH TYPE OF VENT INSTALLED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  