Plan Review Notes
Plan Review Notes For Permit 22050844
Permit Number 22050844
Review Stop M
Sequence Number 2
Notes
Date Text
2022-10-28 08:36:34THE ENERGY CALCULATIONS AND MECHANICAL EQUIPMENT SIZING
 CALCULATIONS WERE SUBMITTED THIS CYCLE. THE DRAWING
 SUBMITTED ON A-1 IS WITH THE DUCT WORK FOR SUPPLY AND
 RETURN BEING DRAWN ON THE ELECTRICAL DRAWING.
 THEMECHANICAL EQUIPMENT SIZING CALCULATIONS CALLS FOR
 .66 OF A TON FOR THIS NEW ADDITION. PLEASE EXPLAIN IS
 THIS A NEW MECHANICAL UNIT? IS THE EXISTING UNIT TO
 PROVIDE THE ADDITIONAL LOAD? IF IT IS PLEASE PROVIDE
 THE CALCULATIONS INDICATING THE THE EXISTING MECHANICAL
 SYSTEM IS SIZED TO HANDLE THE ADDITIONAL ALMOST 3/4
 TONS NEEDED FOR THE NEW ADDITION. IF THERE IS TO BE A
 NEW MECHANICAL SYSTEM PLEASE INDICATE THIS ON THE
 DRAWING AND INCLUDE THE SIZE OF THE MECHANICAL SYSTEM
 AND THE LOCATION OF THE CONDENSING UNIT ON THE DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  