| Plan Review Notes For Permit 22050844 |
| Permit Number |
22050844 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-28 08:36:34 | THE ENERGY CALCULATIONS AND MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS WERE SUBMITTED THIS CYCLE. THE DRAWING | | | SUBMITTED ON A-1 IS WITH THE DUCT WORK FOR SUPPLY AND | | | RETURN BEING DRAWN ON THE ELECTRICAL DRAWING. | | | THEMECHANICAL EQUIPMENT SIZING CALCULATIONS CALLS FOR | | | .66 OF A TON FOR THIS NEW ADDITION. PLEASE EXPLAIN IS | | | THIS A NEW MECHANICAL UNIT? IS THE EXISTING UNIT TO | | | PROVIDE THE ADDITIONAL LOAD? IF IT IS PLEASE PROVIDE | | | THE CALCULATIONS INDICATING THE THE EXISTING MECHANICAL | | | SYSTEM IS SIZED TO HANDLE THE ADDITIONAL ALMOST 3/4 | | | TONS NEEDED FOR THE NEW ADDITION. IF THERE IS TO BE A | | | NEW MECHANICAL SYSTEM PLEASE INDICATE THIS ON THE | | | DRAWING AND INCLUDE THE SIZE OF THE MECHANICAL SYSTEM | | | AND THE LOCATION OF THE CONDENSING UNIT ON THE DRAWING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|