Plan Review Notes For Permit 22050844
Permit Number 22050844
Review Stop R
Sequence Number 1
Notes
Date Text
2022-07-28 11:14:11PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW DENIED:
  
 1.) FBC R 301.2.1, PROVIDE THE WINDLOAD DESIGN
 PRESSURES FOR ROOF ZONES 1, 2, & 3.
 2.) FBC R 301.2.1, PROVIDE FASTENER SPACING FOR ROOFING
 MATERIALS THAT MEETS THE DESIGN PRESSURES FOR THE ROOF
 ZONES 1, 2, & 3.
 2.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVALS FOR
 THE ROOFING MATERIALS TO BE USED.
  
 NOTE: A ROOFING SUB-PERMIT WILL BE REQUIRED PRIOR TO
 ANY ROOF WORK.
  
  
  