| Plan Review Notes For Permit 22050844 |
| Permit Number |
22050844 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-28 13:35:33 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC R 301.2.1 PROVIDE WIND DESIGN PRESSURES ON PLAN | | | FOR ROOFING ZONES. | | | 2.) FBC B 107.2.1, PROVIDE PRODUCT APPROVALS FOR | | | ROOFING MATERIALS, WINDOWS, & DOORS. | | | 3.) FBC R 301.1.3, PROVIDE THE REINFORCEMENT DETAILS ON | | | PLAN FOR THE TIE BEAM AND/OR BOND BEAMS. | | | |
|