2022-08-01 20:14:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A SEPARATE PERMIT APPLICATION WILL BE REQUIRED FOR
 EACH BUILDING WHERE WORK IS BEING PERFORMED. FBC
 107.2.1 105.1
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 4. PROVIDE LOAD CALCULATION TO INCLUDE BOTH EXISTING
 AND ALL NEW LOADS. NEC 220 FBC 107.2.1
  
 5. SPECIFY HOW MANY UNITS ARE BEING REMOVED IN EACH
 BUILDING. FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved