2022-09-08 15:07:15ELECTRIC REVIEW FAILED
 1) PLANS DETAIL AN EXISTING 150 AMP MAIN BREAKER. OUR
 RECORDS INDICATE AN EXISTING 200 AMP MAIN BREAKER.
 PLEASE PROVIDE A CORRECTED ELECTRIC DIAGRAM INDICATING
 ACCURATE EXISTING CONDITIONS. IN ADDITION OUR RECORDS
 INDICATE NO PERMITTING FOR A GENERATOR. PLEASE PROVIDE
 DOCUMENTATION DETAILING THE PERMITTED GENERATOR
 INSTALLATION. FBC 107.2 AND NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  