| Date |
Text |
| 2022-07-12 17:19:56 | 2ND REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22050729 |
| | 7/12/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 01 & 02: THE BUILDING PLAN REVIEWER HAS |
| | DETERMINED THE TOILET ROOM STRUCTURE IS NOT A TEMPORARY |
| | INSTALLATION AND HAS CONVERTED THE PERMIT TYPE TO BLD |
| | RES. THE PLUMBING CANNOT BE APPROVED AT THIS TIME UNTIL |
| | NEW PLANS DESIGNED IN ACCORDANCE WITH THE FBC RES 2020 |
| | CODE ARE SUBMITTED ADDRESSING ALL OF THE BUILDING PLAN |
| | REVIEW COMMENTS- SEC. 107.2.1 WPB. |
| | |
| | 2) SHEET 02: PLEASE NOTE THE CURRENT PLANS DO NOT SHOW |
| | A FLOOR FOR THE STRUCTURE OR ANY TYPE OF MOUNTING |
| | SURFACE TO SECURELY ANCHOR THE TOILET DRAIN FLANGE AND |
| | THE TOILET- SEC. P2705.1 FBC RES. A) REFER TO SEC. |
| | P3005.1.4 AND NOTE WATER CLOSET CONNECTION BETWEEN |
| | FLANGE AND PIPE. |
| | ONE-QUARTER BENDS 3 INCHES IN DIAMETER SHALL BE |
| | ACCEPTABLE FOR WATER CLOSET OR SIMILAR CONNECTIONS, |
| | PROVIDED THAT A 4-INCH BY 3-INCH FLANGE IS INSTALLED TO |
| | RECEIVE THE CLOSET FIXTURE HORN. ALTERNATELY, A 4-INCH |
| | BY 3-INCH ELBOW SHALL BE ACCEPTABLE WITH A 4-INCH |
| | FLANGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |