Plan Review Notes
Plan Review Notes For Permit 22050729
Permit Number 22050729
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-12 17:19:562ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22050729
 7/12/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 01 & 02: THE BUILDING PLAN REVIEWER HAS
 DETERMINED THE TOILET ROOM STRUCTURE IS NOT A TEMPORARY
 INSTALLATION AND HAS CONVERTED THE PERMIT TYPE TO BLD
 RES. THE PLUMBING CANNOT BE APPROVED AT THIS TIME UNTIL
 NEW PLANS DESIGNED IN ACCORDANCE WITH THE FBC RES 2020
 CODE ARE SUBMITTED ADDRESSING ALL OF THE BUILDING PLAN
 REVIEW COMMENTS- SEC. 107.2.1 WPB.
  
 2) SHEET 02: PLEASE NOTE THE CURRENT PLANS DO NOT SHOW
 A FLOOR FOR THE STRUCTURE OR ANY TYPE OF MOUNTING
 SURFACE TO SECURELY ANCHOR THE TOILET DRAIN FLANGE AND
 THE TOILET- SEC. P2705.1 FBC RES. A) REFER TO SEC.
 P3005.1.4 AND NOTE WATER CLOSET CONNECTION BETWEEN
 FLANGE AND PIPE.
 ONE-QUARTER BENDS 3 INCHES IN DIAMETER SHALL BE
 ACCEPTABLE FOR WATER CLOSET OR SIMILAR CONNECTIONS,
 PROVIDED THAT A 4-INCH BY 3-INCH FLANGE IS INSTALLED TO
 RECEIVE THE CLOSET FIXTURE HORN. ALTERNATELY, A 4-INCH
 BY 3-INCH ELBOW SHALL BE ACCEPTABLE WITH A 4-INCH
 FLANGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719