| 2022-12-06 10:41:23 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22050716 |
| | 1222 ALPHA ST |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY. |
| | |
| | ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE BOTTOM |
| | OF FORM BY THE OWNER/AGENT LINE BEFORE ISSUING THE |
| | PERMIT. |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| | AGENT TO AVOID CONFLICT/DELAYS. |
| | |
| | RESPONSE: |
| | REVISE ENERGY CALCULATIONS: |
| | |
| | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. OWNER'S NAME IS INCORRECT. NEED BUILDER'S NAME, |
| | PERMIT OFFICE AND JURISDICTION (THIS IS 604700 |
| | JURISDICTION). SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | C)ITEM # 2 IS INCORRECT. THE STRUCTURE IS NOT ATTACHED. |
| | REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | D)ITEM #9(A) SPECIFIES R-19.0 SLAB ON GRADE EDGE |
| | INSULATION. PLANS DON'T SHOW THIS INSULATION. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE |
| | WITH THIS. REVISE PLANS AND ENERGY CALCULATIONS AS |
| | REQUIRED TO MATCH. ALSO, CLARIFY WHY ITEM #9 SPECIFY |
| | AREAS (A) AND (B). WHERE ARE THESE TWO AREAS LOCATED ON |
| | THE FLOOR PLAN?. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | E)WALL INSULATION SPECIFIED ON ITEM #10 DOESN'T MATCH |
| | PLANS. REVISE AS REQUIRED. ALSO, CLARIFY WHERE IS THE |
| | INTERIOR WALL WITH INSULATION?. SEC. R101.5.1.1.2 |
| | FBC-RESIDENTIAL. |
| | NOTE: R-19 BATT INSULATION DOESN'T FIT ON 2X4 STUDS. |
| | |
| | F)CEILING INSULATION SPECIFIED ON ITEM #11 DOESN'T |
| | MATCH PLANS. REVISE AS REQUIRED. ALSO, THE CEILING OF |
| | THIS STRUCTURE IS NOT FLAT. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | G)ITEM #11 SPECIFY VENTED CEILING. PROVIDE DETAILS AND |
| | SPECIFICATIONS SHOWING HOW THE CROSS VENTILATION IS |
| | PROVIDED. PLANS DON'T SHOW THIS. ROOF NEEDS CROSS |
| | VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| | R-19 BATT INSULATION DOESN'T FIT ON 2X6 ROOF JOISTS. IT |
| | DOESN'T ALLOW ROOF CROSS VENTILATION. SEC. R806.3 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | H)ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND |
| | CROSS VENTILATION CREDITS ON ITEM #16. PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS SHOWING HOW THE HOUSE |
| | COMPLIES WITH BOTH CREDITS. SEE SEC. R405.7.6 AND SEC. |
| | R405.7.4 FBC-ENERGY CONSERVATION FOR SPECIFIC |
| | REQUIREMENTS. |
| | |
| | I)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS |
| | AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION. |
| | |
| | J)SPACES INFORMATION ON PAGE 2 SPECIFIES THAT THERE IS |
| | A KITCHEN IN THIS BUILDING. ACCORDING TO PLANS THERE IS |
| | NOT A KITCHEN. ALSO, ZONING DOESN'T ALLOW A KITCHEN. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | K)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | L)DOORS INFORMATION SPECIFIED ON PAGE 3 IS INCORRECT. |
| | SEE PLANS AND PRODUCT APPROVAL AND REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE |
| | WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| | CONSERVATION). |
| | |
| | M)WINDOWS OVERHANG SEPARATION SPECIFIED ON PAGE 3 FOR |
| | NORTH AND SOUTH ELEVATIONS IS INCORRECT. SEE PLANS AND |
| | REVISES AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | N) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |