Plan Review Notes
Plan Review Notes For Permit 22050716
Permit Number 22050716
Review Stop B
Sequence Number 3
Notes
Date Text
2022-12-06 10:41:23RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22050716
 1222 ALPHA ST
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE BOTTOM
 OF FORM BY THE OWNER/AGENT LINE BEFORE ISSUING THE
 PERMIT.
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS:
  
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. OWNER'S NAME IS INCORRECT. NEED BUILDER'S NAME,
 PERMIT OFFICE AND JURISDICTION (THIS IS 604700
 JURISDICTION). SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C)ITEM # 2 IS INCORRECT. THE STRUCTURE IS NOT ATTACHED.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D)ITEM #9(A) SPECIFIES R-19.0 SLAB ON GRADE EDGE
 INSULATION. PLANS DON'T SHOW THIS INSULATION. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THIS. REVISE PLANS AND ENERGY CALCULATIONS AS
 REQUIRED TO MATCH. ALSO, CLARIFY WHY ITEM #9 SPECIFY
 AREAS (A) AND (B). WHERE ARE THESE TWO AREAS LOCATED ON
 THE FLOOR PLAN?. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E)WALL INSULATION SPECIFIED ON ITEM #10 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, CLARIFY WHERE IS THE
 INTERIOR WALL WITH INSULATION?. SEC. R101.5.1.1.2
 FBC-RESIDENTIAL.
 NOTE: R-19 BATT INSULATION DOESN'T FIT ON 2X4 STUDS.
  
 F)CEILING INSULATION SPECIFIED ON ITEM #11 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED. ALSO, THE CEILING OF
 THIS STRUCTURE IS NOT FLAT. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 G)ITEM #11 SPECIFY VENTED CEILING. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE CROSS VENTILATION IS
 PROVIDED. PLANS DON'T SHOW THIS. ROOF NEEDS CROSS
 VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL.
 R-19 BATT INSULATION DOESN'T FIT ON 2X6 ROOF JOISTS. IT
 DOESN'T ALLOW ROOF CROSS VENTILATION. SEC. R806.3
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 H)ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND
 CROSS VENTILATION CREDITS ON ITEM #16. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE HOUSE
 COMPLIES WITH BOTH CREDITS. SEE SEC. R405.7.6 AND SEC.
 R405.7.4 FBC-ENERGY CONSERVATION FOR SPECIFIC
 REQUIREMENTS.
  
 I)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 J)SPACES INFORMATION ON PAGE 2 SPECIFIES THAT THERE IS
 A KITCHEN IN THIS BUILDING. ACCORDING TO PLANS THERE IS
 NOT A KITCHEN. ALSO, ZONING DOESN'T ALLOW A KITCHEN.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 K)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 L)DOORS INFORMATION SPECIFIED ON PAGE 3 IS INCORRECT.
 SEE PLANS AND PRODUCT APPROVAL AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION).
  
 M)WINDOWS OVERHANG SEPARATION SPECIFIED ON PAGE 3 FOR
 NORTH AND SOUTH ELEVATIONS IS INCORRECT. SEE PLANS AND
 REVISES AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 N) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  