Plan Review Notes
Plan Review Notes For Permit 22050716
Permit Number 22050716
Review Stop B
Sequence Number 2
Notes
Date Text
2022-09-23 11:23:59RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22050716
 1222 ALPHA ST
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2-OK.
 3-OK.
  
 ORIGINAL COMMENT:
 4- BEDROOM EGRESS WINDOWS SIZE 36"X48" SINGLE HUNG
 SPECIFIED DON'T SEEM TO COMPLY WITH THE MINIMUM CLEAR
 OPENING REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
 REVISE AS REQUIRED. TYPICALLY, 48" HEIGHT WINDOW
 DOESN'T PROVIDE THE 24" CLEAR HEIGHT OPENING. REVISE
 WINDOW SIZE AS REQUIRED OR PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE.
  
 RESPONSE:
 WINDOW #1 WAS REVISED WITH NEW SIZE 36"X49 5/8" SINGLE
 HUNG WINDOW. THIS WINDOW DOESN'T SEEM TO COMPLY.
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING COMPLIANCE
 WITH ALL THE EGRESS REQUIREMENTS.
 NOTE: FLOOR PLAN CALLS WINDOW #2 AS THE EGRESS WINDOW.
 INFORMATION ON THE WINDOW SCHEDULE ON SAME SHEET
 DOESN'T MATCH THIS. REVISE AS REQUIRED TO MATCH.
 ALSO, TO AVOID CONFLICTS/DELAYS NEED TO COORDINATE
 WINDOW NOA'S NUMBERS SPECIFIED ON THE WINDOW SCHEDULE
 WITH WINDOWS NOA'S SUBMITTED. REVISE.
 ALSO, WINDOWS NUMBER SHOWN ON THE EXTERIOR ELEVATIONS
 DON'T MATCH THOSE SHOWN ON THE FLOOR PLAN. REVISE.
  
 5- OK.
 6- OK.
 7- OK.
 8- OK.
 9- OK.
 10-OK.
 11-OK.
 12-OK.
 13-OK.
  
 ORIGINAL COMMENT:
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: SINGLE HUNG WINDOWS NOA SPECIFIED ON PLANS DON'T
 MATCH NOA SUBMITTED. REVISE AS REQUIRED TO MATCH.
  
 RESPONSE:
 NEED TO COORDINATE WINDOW NOA'S NUMBERS SPECIFIED ON
 THE WINDOW SCHEDULE WITH WINDOWS NOA'S SUBMITTED.
 REVISE AS REQUIRED TO MATCH.
  
 ORIGINAL COMMENT:
 15- FLOOD ZONE INFORMATION SHOWN ON SHEET 1 IS
 INCORRECT. THE CURRENT FLOOD MAP WENT INTO EFFECT ON
 10/05/2017. REVISE ALL FLOOD INFORMATION AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 INFORMATION IS INCORRECT. THE CURRENT FLOOD MAP WENT
 INTO EFFECT ON 10/05/2017. REVISE INFORMATION AS
 REQUIRED BASED ON CURRENT MAPS.
 NOTE: THIS HOUSE IS NO LOCATED ON A SPECIAL FLOOD ZONE.
 FLOOD ZONE IS NOT REQUIRED TO BE SUBMITTED. PROVIDE
 CORRECT INFORMATION OR DELETE TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION TO INCLUDE EVERYTHING ,
 INCLUDING THE DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT.
  
 NEW COMMENT:
 17- IT WAS NOTED THAT SITE PLAN INFORMATION IS
 INCORRECT. ENGINEER OF RECORD IS SHOWING THIS LOT AS A
 CORNER LOT. ACCORDING TO PROPERTY APPRAISER RECORDS
 THIS IS NOT CORNER LOT. THE CORNER LOT ADDRESS IS 1290
 ALPHA ST. AND BELONGS TO ANOTHER OWNER. THIS DRAWING IS
 SUBMITTED FOR PUBLIC RECORDS AND NEEDS TO BE ACCURATE.
 ENGINEER OF RECORD TO JUSTIFY WHY ALTERING THE
 INFORMATION TO MAKE BELIEVE THE LOT IS 100 FEET WIDE
 AND SHOWING ONLY ONE HOUSE AND THE ACCESSORY STRUCTURE.
 REVISE SITE PLAN AND PROVIDE CURRENT SURVEY TO VERIFY
 CORRECT INFORMATION.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  