| 2022-09-23 11:23:59 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22050716 |
| | 1222 ALPHA ST |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| | AGENT TO AVOID CONFLICT/DELAYS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2-OK. |
| | 3-OK. |
| | |
| | ORIGINAL COMMENT: |
| | 4- BEDROOM EGRESS WINDOWS SIZE 36"X48" SINGLE HUNG |
| | SPECIFIED DON'T SEEM TO COMPLY WITH THE MINIMUM CLEAR |
| | OPENING REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. |
| | REVISE AS REQUIRED. TYPICALLY, 48" HEIGHT WINDOW |
| | DOESN'T PROVIDE THE 24" CLEAR HEIGHT OPENING. REVISE |
| | WINDOW SIZE AS REQUIRED OR PROVIDE MANUFACTURER'S |
| | SPECIFICATIONS SHOWING COMPLIANCE. |
| | |
| | RESPONSE: |
| | WINDOW #1 WAS REVISED WITH NEW SIZE 36"X49 5/8" SINGLE |
| | HUNG WINDOW. THIS WINDOW DOESN'T SEEM TO COMPLY. |
| | PROVIDE MANUFACTURER'S CUT SHEETS SHOWING COMPLIANCE |
| | WITH ALL THE EGRESS REQUIREMENTS. |
| | NOTE: FLOOR PLAN CALLS WINDOW #2 AS THE EGRESS WINDOW. |
| | INFORMATION ON THE WINDOW SCHEDULE ON SAME SHEET |
| | DOESN'T MATCH THIS. REVISE AS REQUIRED TO MATCH. |
| | ALSO, TO AVOID CONFLICTS/DELAYS NEED TO COORDINATE |
| | WINDOW NOA'S NUMBERS SPECIFIED ON THE WINDOW SCHEDULE |
| | WITH WINDOWS NOA'S SUBMITTED. REVISE. |
| | ALSO, WINDOWS NUMBER SHOWN ON THE EXTERIOR ELEVATIONS |
| | DON'T MATCH THOSE SHOWN ON THE FLOOR PLAN. REVISE. |
| | |
| | 5- OK. |
| | 6- OK. |
| | 7- OK. |
| | 8- OK. |
| | 9- OK. |
| | 10-OK. |
| | 11-OK. |
| | 12-OK. |
| | 13-OK. |
| | |
| | ORIGINAL COMMENT: |
| | 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: SINGLE HUNG WINDOWS NOA SPECIFIED ON PLANS DON'T |
| | MATCH NOA SUBMITTED. REVISE AS REQUIRED TO MATCH. |
| | |
| | RESPONSE: |
| | NEED TO COORDINATE WINDOW NOA'S NUMBERS SPECIFIED ON |
| | THE WINDOW SCHEDULE WITH WINDOWS NOA'S SUBMITTED. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | ORIGINAL COMMENT: |
| | 15- FLOOD ZONE INFORMATION SHOWN ON SHEET 1 IS |
| | INCORRECT. THE CURRENT FLOOD MAP WENT INTO EFFECT ON |
| | 10/05/2017. REVISE ALL FLOOD INFORMATION AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | INFORMATION IS INCORRECT. THE CURRENT FLOOD MAP WENT |
| | INTO EFFECT ON 10/05/2017. REVISE INFORMATION AS |
| | REQUIRED BASED ON CURRENT MAPS. |
| | NOTE: THIS HOUSE IS NO LOCATED ON A SPECIAL FLOOD ZONE. |
| | FLOOD ZONE IS NOT REQUIRED TO BE SUBMITTED. PROVIDE |
| | CORRECT INFORMATION OR DELETE TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. REVISE VALUATION TO INCLUDE EVERYTHING , |
| | INCLUDING THE DESIGN PROFESSIONAL FEES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. |
| | |
| | NEW COMMENT: |
| | 17- IT WAS NOTED THAT SITE PLAN INFORMATION IS |
| | INCORRECT. ENGINEER OF RECORD IS SHOWING THIS LOT AS A |
| | CORNER LOT. ACCORDING TO PROPERTY APPRAISER RECORDS |
| | THIS IS NOT CORNER LOT. THE CORNER LOT ADDRESS IS 1290 |
| | ALPHA ST. AND BELONGS TO ANOTHER OWNER. THIS DRAWING IS |
| | SUBMITTED FOR PUBLIC RECORDS AND NEEDS TO BE ACCURATE. |
| | ENGINEER OF RECORD TO JUSTIFY WHY ALTERING THE |
| | INFORMATION TO MAKE BELIEVE THE LOT IS 100 FEET WIDE |
| | AND SHOWING ONLY ONE HOUSE AND THE ACCESSORY STRUCTURE. |
| | REVISE SITE PLAN AND PROVIDE CURRENT SURVEY TO VERIFY |
| | CORRECT INFORMATION. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |