2022-05-21 08:33:171ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 107.3.5.3 (12.) - PLEASE SHOW THE
 DRAIN, WASTE AND VENT DIAGRAM IN ISOMETRIC FORM FOR
 CLARITY.
  
 2. 2020 FRC P3108.1 - THE KITCHEN SINK AND LAUNDRY
 CANNOT BE INCLUDED IN WET VENTING. ONLY BATHROOM GROUP
 FIXTURES CAN BE INCLUDED IN A WET VENT SYSTEM. ALL
 OTHER FIXTURES MUST DISCHARGE DOWNSTREAM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  