| 2022-10-10 08:14:08 | PROVISOS FOR 22050714 |
| | 1. PAGE P1.0.1 - OIL/WATER/SAND SEPARATOR REQUIRES |
| | SEPARATE PERMIT. SPECS TO BE SUBMITTED WITH MASTER |
| | PERMIT AS WELL AS STAND ALONE PERMIT. |
| | 2. PAGE P1.0.1; P4.0.2 - THE VENTING FOR THE |
| | OIL/WATER/SAND SEPARATOR CANNOT USE AIR ADMITTANCE |
| | VALVES. (2020 FPC 918.8) AN ENLARGED DETAIL IS |
| | REQUIRED. |
| | 3. PAGE A9.2.1 - 2020 FAC SEC. 213.2(4) - A MINIMUM OF |
| | 50% OF THE CLUSTERED BATHROOMS FOR EACH USE SHALL BE |
| | ACCESSIBLE. REVISION TO BE MADE TO MEET MINIMUM |
| | STANDARDS. |
| | 4. P1.01; P4.02 - ELEVATOR SUMP DISCHARGE TO BE |
| | INDIRECTLY CONNECTED TO SANITARY WASTE. DISCHARGE NOT |
| | IN THE VICINITY OF SUMP DISCHARGE OUTLETS. WASTE |
| | RECEPTOR TO BE PROVIDED. |
| | 5. P5.0.2; P6.0.1 - QUAD CLOSE TRAP SEAL DETAIL ON PAGE |
| | P5.0.2 AND EQUIPMENT SCHEDULE ON PAGE P6.0.1 FOR TD-1 |
| | SHOWING MIFAB MI-GARD DO NOT MATCH. |
| | 6. PAGE P1.0.1 - POOL WASTEWATER DISCHARGING INTO HD-1 |
| | SHALL BE DECHLORINATED TO MEET CITY???S STANDARDS THEN |
| | DISCHARGED INTO STORM SYSTEM. DICHLORINATION DETAILS TO |
| | BE PROVIDED AND APPROVED BY CITY???S STORMWATER |
| | DEPARTMENT. |
| | 7. PROVIDE DETAILS ON MASTER FOR CITY???S REQUIRED |
| | BACKFLOW PROTECTION PER UTILITY DEPARTMENT???S |
| | REQUIREMENTS. |
| | 8. PAGE P4.1.2 - PROVIDE PAGE 4.1.5 AS CALLED OUT AT |
| | THE TOP OF THE RISER ON PAGE P4.1.2 |
| | 9. HOT WATER AND HOT WATER RETURN PIPING INSULATION |
| | DETAILS TO BE PROVIDED. |
| | 10. PAGE P6.0.1 - ISOLATION BACKFLOW PREVENTION DEVICES |
| | TO BE LISTED ON SCHEDULE |
| | 11. PAGE P1.12.1, P2.01 - FD-2 APPEARS TO BE COLLECTING |
| | STORM WATER AND DISCHARGING TO THE SANITARY. DETAILS TO |
| | BE SHOWN TO CLARIFY. |
| | 12. P4.01, P4.02, P4.03, P4.04: THE VENT STACKS SHALL |
| | CONNECT TO THE BASE OF STACKS (SEE OVERALL SANITARY |
| | RISER - (1/P4.0.3)) - 2020 FPC 904.4 |
| | 13. PAGE P4.03 - DETAILS TO BE ADDED SHOWING VENTS FOR |
| | THE STACK OFFSETS (2020 FPC 711) |
| | 14. PAGE P4.1.4 AND DETAILS PAGES - TO BE ADDED TO THE |
| | PLUMBING DETAILS AND THE DOMESTIC RISERS SHOWING |
| | COMPLIANCE WITH 607.1.1 AND 613.1. THE THERMOSTAT ON |
| | THE WATER HEATER CANNOT BE THE LIMIT FOR HOT OR |
| | TEMPERED WATER DELIVERY AND THE DEVICE SHALL BE |
| | INSTALLED AT THE HOT WATER SOURCE. |