| 2022-09-26 14:18:38 | NEW HI RISE OFFICE BLDG. |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | |
| | 1) GROUND FLOOR AND MEZZANINE PARKING - PLEASE SHOW |
| | PARKING GARAGE OPEN OR CLOSED AND PROVIDE THE |
| | CALCULATIONS (EACH TIER) FOR THE OPEN GARAGE FBC |
| | 406.5.2 OPENINGS. |
| | FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF |
| | THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS |
| | ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| | THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| | PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| | PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| | SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| | DISTRIBUTED OPENINGS. |
| | |
| | 2) BUILDING SOUTH ELEVATION - PLEASE SHOW THE ALLOWABLE |
| | EXTERIOR WALL OPENING PROTECTION CALCULATIONS (EACH |
| | STORY) ( SOLID WALLS VS DOOR, LOUVERS, OPEN AREAS AT |
| | GARAGE AND WINDOWS ETC.) PER FBC 705.8.1 ALLOWABLE AREA |
| | OF OPENINGS. |
| | THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| | PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| | BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| | TABLE 705.8. |
| | |
| | 3) BUILDING WEST ELEVATION - GROUND FLOOR SHOWS A DOOR, |
| | LOUVERS WHICH ARE NOT SHOWN ON YOUR CALCULATIONS. - |
| | (EACH STORY) PLEASE SHOW THE ALLOWABLE EXTERIOR WALL |
| | OPENING PROTECTION CALCULATIONS ( SOLID WALLS VS DOOR, |
| | LOUVERS, OPEN AREAS AT GARAGE AND WINDOWS ETC.) PER FBC |
| | 705.8.1 ALLOWABLE AREA OF OPENINGS. |
| | THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| | PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| | BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| | TABLE 705.8. |
| | |
| | 4) ELEVATOR HOISTWAY FOR ELEVATOR #3 AND #4 REQUIRES |
| | HOISTWAY PROTECTION ( A SINGLE SHAFT WHICH APPEARS TO |
| | RUN FROM GROUND TO THE 11TH FLOOR) FBC 3006.2 |
| | |
| | 5) DRAWING LS.20.1 - DETAIL 2 - SHOULD SAY EAST TO |
| | WEST. |
| | |
| | 6) PLEASE SHOW THE PASSENGER LOADING LOCATIONS PER FBC |
| | ACCESSIBILITY 209.2.1 PASSENGER LOADING ZONES. |
| | PASSENGER LOADING ZONES, EXCEPT THOSE REQUIRED TO |
| | COMPLY WITH 209.2.2 AND 209.2.3, SHALL PROVIDE AT LEAST |
| | ONE PASSENGER LOADING ZONE COMPLYING WITH 503 IN EVERY |
| | CONTINUOUS 100 LINEAR FEET (30 M) OF LOADING ZONE |
| | SPACE, OR FRACTION THEREOF. FBC A 503.2 VEHICLE PULL-UP |
| | SPACE. |
| | PASSENGER LOADING ZONES SHALL PROVIDE A VEHICULAR |
| | PULL-UP SPACE 96 INCHES (2440 MM) WIDE MINIMUM AND 20 |
| | FEET (6100 MM) LONG MINIMUM. |