| 2022-06-07 12:42:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE SMOKE CONTROL RATIONAL ANALYSIS AND SEQUENCE OF |
| | OPERATION ARE NOT ATTACHED |
| | |
| | NFPA 101 CH 11 |
| | |
| | 11.8.2.3 ALL NEW VERTICAL EXIT ENCLOSURES SERVING THE |
| | HIGH-RISE PORTION |
| | OF THE BUILDING SHALL BE SMOKEPROOF ENCLOSURES IN |
| | ACCORDANCE WITH 7.2.3. |
| | |
| | 9.3 SMOKE CONTROL |
| | 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS CODE, |
| | SMOKE CONTROL SYSTEMS SHALL BE DESIGNED, INSTALLED, |
| | INSPECTED, TESTED, |
| | AND MAINTAINED IN ACCORDANCE WITH NFPA 92, NFPA 204, OR |
| | NATIONALLY |
| | RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR |
| | RECOMMENDED PRACTICES, |
| | AS APPROVED BY THE AUTHORITY HAVING JURISDICTION |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 2) SHEET LS 01.1 - THE FIRE COMMAND CENTER DOES NOT |
| | HAVE ACCESS FROM AN EXTERIOR WALL. |
| | |
| | THE FIRE COMMAND CENTER SHOULD HAVE DIRECT UNIMPEDED |
| | ACCESS FROM AN EXTERIOR WALL AND IN A LOCATION APPROVED |
| | BY THE AHJ |
| | |
| | PER NFPA 101 CH 11 |
| | |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A LOCATION |
| | APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT WITH COORDINATION WITH THE |
| | OFFICE OF THE FIRE MARSHAL. |
| | |
| | |
| | |
| | 3) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT |
| | TRAVEL ACCESS DOOR THROUGH AN OUTDOOR STORAGE AREA, # |
| | 113 AND OUTDOOR TERRACE # 112 |
| | |
| | IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR |
| | EXIT SIGNAGE FROM THAT AREA. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.5 ARRANGEMENT OF MEANS OF EGRESS |
| | 7.5.1 GENERAL. |
| | 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL |
| | BE ARRANGED, SO THAT |
| | EXITS ARE READILY ACCESSIBLE AT ALL TIMES. |
| | 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE |
| | FROM AN OPEN |
| | FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR |
| | CORRIDORS LEADING DIRECTLY |
| | TO EVERY EXIT SHALL BE MAINTAINED AND SHALL BE ARRANGED |
| | TO PROVIDE ACCESS |
| | FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY |
| | SEPARATE WAYS OF TRAVEL, |
| | UNLESS OTHERWISE PROVIDED IN 7.5.1.1.3 AND 7.5.1.1.4 |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS |
| | |
| | 7.7 DISCHARGE FROM EXITS |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC |
| | WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| | PROVIDED IN 7.7.1.2 |
| | THROUGH 7.7.1.4. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT |
| | PATH TO THE PUBLIC WAY. |
| | |
| | |
| | 3A) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT |
| | STAIRS INTO THE OUTDOOR TERRACE # 112 |
| | |
| | THE EXIT STARI DISCHARGE IS TO LEAD TO A PUBLIC WAY OR |
| | TO A PROTECTED AREA LEADING TO A PUBLIC WAY. |
| | |
| | IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR |
| | EXIT SIGNAGE FROM THAT AREA. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC WAY, |
| | INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC |
| | WAY, OR INTO AN EXIT |
| | PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT |
| | OPENINGS, OTHER |
| | THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| | DOOR OPENING TO |
| | THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT |
| | PASSAGEWAY SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY A |
| | 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED |
| | TO DISCHARGE |
| | THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF |
| | THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPER VISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7. |
| | (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL |
| | LEAD TO A FREE |
| | AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY |
| | SHALL BE |
| | READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF |
| | DISCHARGE FROM |
| | THE SMOKEPROOF ENCLOSURE. |
| | (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND |
| | CAPACITY OF |
| | EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL |
| | DISCHARGE THROUGH |
| | INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2. |
| | |
| | 7.7 DISCHARGE FROM EXITS |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC |
| | WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| | PROVIDED IN 7.7.1.2 |
| | THROUGH 7.7.1.4. |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS |
| | |
| | PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT |
| | PATH TO THE PUBLIC WAY. |
| | |
| | |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF CARD READERS/ACCESS CONTROL |
| | THROUGHOUT THE OCCUPANCY. |
| | |
| | ALL CARD READER/ACCESS CONTROL SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT & SHOP DRAWINGS AND COMPLY WITH NFPA |
| | 101, CH 7 AS APPLICABLE. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| | THE LIFE SAFETY & ELECTICAL NOTE SHEETS. |
| | |
| | |
| | |
| | |
| | 5) SHEET LS 06.1 - THERE IS EXIT DOOR (STAIR B) FROM |
| | THE PARKING GARAGE ENTERING INTO THE EXIT PASSAGE WAY. |
| | TO AVOID EXIT CONFUSION THERE SHOULD BE A SING ON THE |
| | WALL OPPOSITE THAT EXIT DOOR STATING EXIT DOWN(OR |
| | EQUAL) WITH AN ARROW POINTING IN THE DIRECTION OF THE |
| | STAIR. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS |
| | |
| | THIS WOULD REDUCE THE CONFUSION OF GOING THE WRONG WAY |
| | DOWN THE EXIT PASSAGE WAY AND UP TO ANOTHER FLOOR |
| | LEVEL. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| | THE LIFE SAFETY SHEET. |
| | |
| | |
| | |
| | 6) SHEET LS 08.1 - THERE APPEARS TO BE A SINGLE |
| | EXIT/SIGN FROM THE COMMON TERRACE # 813 AREA. |
| | |
| | AS THIS IS AN ASSEMBLY OCCUPANCY SPACE, TWO EXITS ARE |
| | REQUIRED PER NFPA 101, CH 12 & CH 7 REMOTELY LOCATED |
| | FROM EACH OTHER. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | NARRATIVE AND CODE REFERENCES. |
| | |
| | |
| | |
| | |
| | 7) SHEET E 1.1.3 & E 4.0.2 - THE ARE INDICATIONS OF |
| | FAAP HOWEVER, THERE IS NO INDICATION OF THE FACP THAT |
| | IS REQUIRED TO BE THE FIRE COMMAND CENTER |
| | |
| | SHEET E 4.0.2 SHOWS LIMITED EQUIPMENT. |
| | |
| | PER NFPA 1 & 101 |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND CENTER. |
| | |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE A NOTE OF |
| | ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 7A) SHEET E 1.1.3 - THERE ARE NO INDICATIONS OF ANY |
| | EQUIPMENT WITHIN THE FIRE COMMAND CENTER. |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE |
| | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL |
| | BE APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER |
| | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| | HOUR. |
| | |
| | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| | 10 FT (3050 MM). |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE. |
| | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION |
| | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | NFPA 101 |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE TO INSTALL. |
| | |
| | PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 8) SHEET E 6.0.5 - THERE ARE INDICATIONS OF A BDA TYPE |
| | 2-WAY COMMUNCATIONS SYSTEM. |
| | |
| | ANY BDA SYSTEM SHALL BE INSTALLED UNDER SEPARATE |
| | PERMIT. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| | FIRE DEPARTMENT. TESTING SHALL BE BY AN ACCEPTABLE |
| | NATIONAL STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE |
| | AND BY ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE |
| | MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| | AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| | 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | HOWEVER, A SYSTEM MAY NOT BE REQUIRED. |
| | |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, [email protected], |
| | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR |
| | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. |
| | |
| | BEFORE SUBMITTING FOR A PERMIT, PLEASE PROVIDE ALL THE |
| | TESTING DATA TO MR. FILLA AND THE OFFICE OF THE FIRE |
| | MARSHAL FOR REVIEW. |
| | |
| | PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | 9) SHEET E 0.1.1 - THERE ARE INDICATIONS OF A FIRE |
| | ALARM SYSTEM AND EQUIPMENT. |
| | |
| | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT |
| | DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE ALARM, SHALL BE DONE UNDER |
| | SEPARATE PERMITS & SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 10) SHEET F 0.0.1 - THERE ARE INDICATIONS OF A FIRE |
| | SPRINKLER SYSTEM AND EQUIPMENT. |
| | |
| | THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED |
| | THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKER SYSTEM, SHALL BE DONE |
| | UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| | |
| | PER NFPA 14 |
| | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 11) SHEET E 5.0.1 - THERE IS AN INDICATION OF A |
| | GENERATOR EXHAUST PIPING DIAGRAM. |
| | |
| | PER NFPA 110 AND 37 |
| | |
| | PLEASE CONFIRM THE GENERATOR CLASS/TYPE, FUEL SOURCE |
| | AND THAT THE ELECTRIC FIRE PUMP IS CONNECTED TO THE |
| | GENERATOR WITH AN AUTOMATIC TRANSFER SWITCH. |
| | |
| | |
| | |
| | 11A) PER NFPA 110 AND 37, PLEASE ENSURE THAT THE |
| | GENERATOR EXHAUST IS LOCATED TO AN AREA THAT THE FUMES |
| | DONOT REENTER THE BUILDING THROUGH NEARBY WINDOWS, |
| | DOORS, OR INTAKES OF ANY KIND. |
| | |
| | PROVIDE DETAILS INCLUDING APPLICABLE DIMENSIONS |
| | |
| | |
| | 12) SHEET C 4.1 - THERE IS AN INDICATION OF AN 8" FIRE |
| | LINE THAT APPEARS TO GO UNDER THE FOOT PRINT OF THE |
| | BUILDING. |
| | |
| | PER NFPA 24 |
| | |
| | 10.1.4.1* UNDERGROUND PIPING SHALL BE PERMITTED TO |
| | EXTEND |
| | INTO THE BUILDING THROUGH THE SLAB OR WALL NOT MORE |
| | THAN 24 IN. |
| | (600 MM). |
| | |
| | 10.4.3 PRIVATE FIRE SERVICE MAINS UNDER BUILDINGS. |
| | EXCEPT AS |
| | ALLOWED BY 10.4.3, PRIVATE FIRE SERVICE MAINS SHALL NOT |
| | BE AL LOWED TO RUN UNDER BUILDING |
| | |
| | 10.4.3.1* PRIVATE FIRE SERVICE MAINS SUPPLYING FIRE |
| | PROTECTION |
| | SYSTEMS WITHIN THE BUILDING SHALL BE PERMITTED TO |
| | EXTEND NO |
| | MORE THAN 10 FT (3.0 M), AS MEASURED FROM THE OUTSIDE |
| | OF THE |
| | BUILDING, UNDER THE BUILDING TO THE RISER LOCATION |
| | |
| | 10.4.3.1.1* PIPE JOINTS SHALL NOT BE LOCATED DIRECTLY |
| | UNDER |
| | FOUNDATION FITTINGS. |
| | 10.4.3.1.2* PIPING SHALL BE INSTALLED A MINIMUM OF 12 |
| | IN. |
| | (300 MM) BELOW THE BOTTOM OF BUILDING FOUNDATIONS OR |
| | FOOTERS. |
| | |
| | 10.4.3.2* WHERE APPROVED, PRIVATE FIRE SERVICE MAINS |
| | SUPPLY ING SYSTEMS WITHIN THE BUILDING SHALL BE |
| | PERMITTED TO EXTEND |
| | MORE THAN 10 FT (3.0 M) UNDER THE BUILDING WHEN ALL THE |
| | RE QUIREMENTS OF 10.4.3.2.1, THROUGH 10.4.3.2.4 ARE |
| | MET. |
| | 10.4.3.2.1 WHERE THE PIPING IS INSTALLED UNDER THE |
| | BUILDING, ALL |
| | FOUNDATIONS OR FOOTERS OVER THE PRIVATE FIRE SERVICE |
| | MAIN SHALL BE |
| | ARCHED TO CREATE A MINIMUM OF 24 IN (600 MM) CLEARANCE. |
| | 10.4.3.2.2 IT SHALL BE ACCEPTABLE TO INSTALL THE PIPING |
| | IN COV ERED TRENCHES WHERE THE TRENCHES ARE ACCESSIBLE |
| | FROM WITHIN |
| | THE BUILDING |
| | |
| | PLEASE REVIEW AND PROVIDE DEAILS IN COMPLIANCE. |
| | |
| | |
| | 13A) THERE IS A FDC LOCATED ALONG BANYAN BLVD WWITH |
| | INDICATIONS OF TWO EXISTING HYDRANT LOCATIONS |
| | |
| | THERE ARE NO DIMENSIONS TO THOS EXISTING FIRE HYDRANTS |
| | SHOWING COMPLIANCE WITH NFPA 14. |
| | |
| | PER NFPA 14 |
| | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| | |
| | |
| | PLEASE PROVIDE THE DIMENSIONS AND CORRECT THE FDC |
| | LOCATION AS APPLICABLE. |
| | |
| | |
| | |
| | 13B) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT & SHOP DRAWINGS IN COMPLIANCE WITH AND |
| | TESTED PER NFPA 24 AND MANUFACTURES SPECIFICATIONS. |
| | |
| | DO NOT COVER OVER ANY FIRE LINE PRIOR TO FIRE |
| | INSPECTION, JOINTS SAHLL BE LEFT EXPOSED FOR |
| | VERIFICATION & CONFIRMATION, |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 14) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 15) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |