Plan Review Notes
Plan Review Notes For Permit 22050713
Permit Number 22050713
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-27 09:47:45BUILDING PROVISO: 2020 FBC-BUILDING CODE: SECTION
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2. SECTION 1210.2.2 WALLS &
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
 THIS PROVISO IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  