2022-05-17 11:58:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE INSTALLATION OF ACCESS
 CONTROL HOWEVER THERE IS NO PLAN SHEET, FLOOR PLAN NOR
 DOOR LOCATION.
  
 PER NFPA 1
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN,
 LOCATION OF DEVICES AND DOOR LOCATIONS.
  
  
 1A) ACCESS CONTROL WITHI A MEANS OF EGRESS SHALL COMPLY
 WITH THE APPLICABLE REQUIREMENTS OF NFPA 101, CH 7,
 MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLDGMENT.
  
  
  
 1B) THERE ARE NO INDICATIONS OF AN ELECTRICAL POWER
 SUPPLY AND WIRE SIZES.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE THE ELECTRICAL POWER PLAN AND APPLICABLE
 EQUIPMENT AND DIAGRAMS IN COMPLIANCE WITH NPFA CODES
 AND MANUFACTURES SPECIFIACATIONS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  