| 2022-05-19 13:30:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF A CHANGE OF OCCUPANCY BUT |
| | THERE IS NO INDICATION OF WHAT THE PREVIOUS OCCUPANCY |
| | WAS AND THE TYPE / CLASSIFICATION OF THIS PROPOSED |
| | DAYCARE. |
| | |
| | 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, |
| | KINDERGARTENS, |
| | AND OTHER SCHOOLS WHOSE PURPOSE IS PRIMARILY |
| | EDUCATIONAL FOR CHILDREN |
| | 24 MONTHS OF AGE OR OLDER, EVEN THOUGH THE CHILDREN WHO |
| | ATTEND SUCH |
| | SCHOOLS ARE OF PRESCHOOL AGE, SHALL COMPLY WITH THE |
| | PROVISIONS OF |
| | CHAPTER 14 |
| | |
| | THE REQUIREMENTS OF CHAPTER 16 ARE BASED ON THE NEED TO |
| | ADEQUATELY |
| | PROTECT THE OCCUPANTS IN CASE OF FIRE. THE REQUIREMENTS |
| | ASSUME THAT |
| | ADEQUATE STAFFING WILL BE AVAILABLE AND ARE BASED ON |
| | STAFFING SIMILAR TO |
| | THAT OUTLINED IN TABLE A.16.1.1. |
| | |
| | PLEASE PROVIDE THE CLASSIFICATION OF DAYCARE AND AGE |
| | GROUPS IF APPLICABLE. |
| | |
| | |
| | |
| | 2) THIS PROPOSED LOCATION APPEARS TO HAVE A FEW |
| | SUITES/UNITS THAT ARE NOT INDICATED ON THE BUILDING |
| | PLAN. |
| | |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE BARRIERS, |
| | AS SPECIFIED IN TABLE 6.1.14.4.1(A), TABLE |
| | 6.1.14.4.1(B), AND 6.1.14.4.2 |
| | THROUGH 6.1.14.4.4, UNLESS SEPARATION IS PROVIDED BY |
| | APPROVED EXISTING |
| | SEPARATIONS OR AS OTHERWISE PERMITTED BY 6.1.14.4.6. |
| | |
| | PLEASE PROVIDE THE ADJACENT OCCUPANCY(IES) WITH THE |
| | LOCATION OF THIS PROPOSED OCCUPANCY AND THE REQUIRED |
| | FIRE RATED SEPARATION PER THE TABLE. |
| | |
| | |
| | 3) THERE ARE DOORS INDICATED ON THE FLOOR PLAN HOWEVER, |
| | THERE ARE NO IDNCATIONS OF DOOR HARDWARE COMPLYING WITH |
| | THE REQUIREMENTS. |
| | |
| | 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, |
| | STORAGE AREAS, |
| | KITCHENS, AND OTHER SIMILAR SPACES OR AREAS SHALL BE |
| | SUCH THAT CLIENTS CAN |
| | OPEN THE DOOR FROM INSIDE THE SPACE OR AREA |
| | |
| | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE |
| | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| | OUTSIDE BY AN |
| | OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE |
| | STAFF. |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE |
| | APPLICABLE. |
| | |
| | |
| | 3A) THEE ARE NO INDICATIONS OF DDOR LOCKS/LATCHES OF |
| | THE 2 EXTERIOR EXIT DOORS. |
| | |
| | 16.2.2.2 DOORS. |
| | 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE |
| | APPLICABLE. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF EXIT SIGNS ON THE FLOOR |
| | PLAN OVER HTE REQUIRED EXITS. |
| | |
| | 16.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL BE |
| | ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.9 IN THE FOLLOWING AREAS: |
| | (1) INTERIOR STAIRS AND CORRIDORS |
| | (2) ASSEMBLY USE SPACES |
| | (3) FLEXIBLE AND OPEN PLAN BUILDINGS |
| | (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS |
| | (5) SHOPS AND LABORATORIES |
| | |
| | |
| | 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 |
| | |
| | PLEASE PROVIDE PER THE REQUIREMENTS |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS OF SMOKE ALARMS. |
| | |
| | 6.6.3.4.4 SINGLE-STATION OR MULTIPLE-STATION SMOKE |
| | ALARMS OR SMOKE |
| | DETECTORS SHALL BE PROVIDED IN ALL ROOMS USED FOR |
| | SLEEPING IN ACCORDANCE |
| | WITH 9.6.2.10 |
| | |
| | PLEASE PROVIDE DETAILS IF THERE WILL BE A PROPOSED |
| | SLEEPING AREA AND FOR THE REQUIRED SMOKE ALARMS. |
| | |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF ELECTRICAL OUTLETS NOR |
| | FOR THEIR PROTECTION. |
| | |
| | 16.5.1.2 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE |
| | INSTALLED IN ALL AREAS OCCUPIED BY CLIENTS. |
| | |
| | |
| | PLEASE PROVIDE DETAILS OF THE LOCATIONS AND |
| | REQUIREMENT. |
| | |
| | |
| | 7) THERE ARE NO INDICATIONS OF WHAT THE WALL AND FLOOR |
| | FINISHES WILL BE. |
| | |
| | 16.3.3 INTERIOR FINISH. |
| | 16.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | 16.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR |
| | WALL AND CEILING |
| | FINISH MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE |
| | CLASS A IN STAIR WAYS, CORRIDORS, AND LOBBIES; IN ALL |
| | OTHER OCCUPIED AREAS, INTERIOR WALL |
| | AND CEILING FINISH SHALL BE CLASS A OR CLASS B. |
| | |
| | 16.3.3.3 INTERIOR FLOOR FINISH. |
| | 16.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 16.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS COR RIDORS AND SPACES NOT SEPARATED FROM |
| | THEM BY WALLS COMPLYING WITH |
| | 14.3.6 SHALL BE NOT LESS THAN CLASS II. |
| | 16.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR 10.2.7.2, |
| | AS APPLICABLE |
| | |
| | PLEASE PROVIDE DETAILS FOR THE FINISH MATERIAL |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | 8) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS. |
| | |
| | F.A.C. 69A - 36 |
| | |
| | (2) PORTABLE FIRE EXTINGUISHERS. THE SELECTION, |
| | PLACEMENT, DISTRIBUTION, MAINTENANCE AND SERVICING OF |
| | PORTABLE FIRE EXTINGUISHERS SHALL COMPLY WITH NFPA 10 |
| | AS ADOPTED BY CHAPTER 69A-3, F.A.C., AND WITH THE |
| | PROVISIONS OF CHAPTER 69A-21, F.A.C., EXCEPT THAT THE |
| | MINIMUM RATING OF ANY EXTINGUISHER INSTALLED IN A CHILD |
| | CARE FACILITY SHALL NOT BE LESS THAN 2A-10B:C. |
| | |
| | PLEASE PROVIDE THE LOCATIONS(S) AND SIZES OF REQUIRED |
| | FIRE EXTINGUISHERS. |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |