Plan Review Notes
Plan Review Notes For Permit 22050615
Permit Number 22050615
Review Stop M
Sequence Number 1
Notes
Date Text
2022-06-07 10:04:101ST REVIEW FMC
 PERMIT: 22050615
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE CURRENT OCCUPANCY FOR THIS SPACE.
 LIVE/WORK? IF SO THIS WOULD BE A CHANGE OF USE FOR THIS
 SPACE.
  
 2) THE REFRIGERATION AND WALK-IN COOLER WILL REQUIRE A
 SEPARATE PERMIT AND REVIEW AS IT WILL NOT BE REVIEWED
 UNDER THIS PERMIT. PLEASE ADD A NOTE ON THE PLAN
 SHOWING THIS.
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR BOTH AHU?S.
 THE NUMBER OF OCCUPANTS FOR THIS SPACE MUST BE PROVIDED
 BY USING TABLE 403.3.1.1 AD NOT THE ARCHITECT?S
 OCCUPANT LOAD. FMC TABLE 403.3.1.1
  
 4) PROVIDE INFORMATION ABOUT THE FOOD PREP AREA. THE
 VENTILATIONS CALCULATIONS DO NOT SHOW EXHAUST FOR THIS
 AREA. FMC TABLE 403.3.1.1
  
 5) THE AIR BALANCE REPORT MUST INCLUDE THE EXISTING
 AHU. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  