| Plan Review Notes For Permit 22050595 |
| Permit Number |
22050595 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-20 11:07:10 | PLAN IS FOR INSTALLATION OF TWO ADDITIONAL DIESEL | | | GENERATORS FOR THE SITE. NOT INDICATED IS THE FUEL | | | STOPRAGE SYSTEM FOR THE NEW UNITS. | | | | | | PLEASE INDICATE LOACTION OF FUEL STORAGE FOR NEW | | | GENERATORS ON SITE IF EXISTING, OR LOCATION OF NEW FUEL | | | STORAGE. IF NEW FUEL STORAGE IS BEING ADDED, PLEASE | | | ENSURE FUEL TANKS MEET NFPA STANDARDS AS NOTED: | | | | | | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED | | | AND MAINTAINED | | | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE | | | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION | | | AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|