Plan Review Notes
Plan Review Notes For Permit 22050592
Permit Number 22050592
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-16 09:57:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF DRYWALL
 REMOVAL IN A UNIT AND HALLWAY.
  
 HOWEVER, THERE IS NO INDICATION OF THE SUBMITTED PLAN
 SHEETS OF WHERE THE WALLS ARE LOCATED NOT HOW MUCH
 DRYWALL WILL BE REMOVED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE THE
 LOCATIONS OF DRWALL REMOVAL AND THE EXTENT OF REMOVAL.
  
  
 1A) THE HALLWAY IS CONSTRUCTED OF FIRE RATED
 SEPARATION, ANY REMOVAL OF MATERIAL SHALL BE REPLACED
 TO MEET THE REQUIRED RATING WITH A LISTED
 SPEICIFCATION.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE THE APPLICABLE LISTED FIRE RATING
 SPECIFICATION DOCUMENT.
  
  
 1B) THE HALLWAY IS A REQUIRED EXIT EGRESS THAT SHALL BE
 MAINTAINED ACCESSIBLE AT ALL TIMES DURING DEMO AND
 RECONSTRUCTION.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGMENT.
  
  
 2) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  