| 2022-05-14 12:51:13 | ****CORRECTIONS**** |
| | **REVISED 5/16/22** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC 107, PROVIDE A PLAN THAT SHOWS SCOPE AND |
| | LOCATION OF DRYWALL REMOVAL. NOTHING IS SHOWN ON THE |
| | PLAN SUBMITTED. |
| | |
| | 2. A SEPARATE PERMIT IS REQUIRED FOR THE COMMON AREA. |
| | THE TWO PERMITS (UNIT 303, COMMON AREA) CAN BE ONE |
| | SUBMITTAL WITH ONE SET OF PLANS. EMAIL A COMPLETED |
| | PERMIT APPLICATION TO [email protected], |
| | |
| | 3. IF YOU USE THE ARCHITECT'S PLAN, THE ARCHITECT NEEDS |
| | TO SIGN AND SEAL (FS481). AN ARCHITECT IS NOT REQUIRED, |
| | BUT IF PREPARED BY AN ARCHITECT (INCLUDES AN |
| | ARCHITECT'S TITLE BLOCK) DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED, DATED ORIGINALS. IF THE PLAN IS |
| | PREPARED BY THE CONTRACTOR, THE PRINTED NAME AND |
| | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR |
| | THE DESIGN IS REQUIRED. |
| | |
| | 4. IF FIRE RATED WALLS ARE AFFECTED, HOW WILL THE LIFE |
| | SAFETY REQUIREMENTS BE MAINTAINED? YOU ARE ASKING TO |
| | DEMOLISH BUT NOT CLEAR WHAT THE PLAN IS TO RESTORE THE |
| | FIRE SAFETY REQUIRED. IT APPEARS THAT THE FIRE RATED |
| | CORRIDORS IN THE COMMON AREA ARE AFFECTED, FBC 708. |
| | SINCE A FLOOR PLAN FOR UNIT 303 WAS NOT PROVIDED, IT IS |
| | NOT CLEAR IF FIRE RATED WALLS ARE AFFECTED WITHIN THE |
| | UNIT. |
| | |
| | |
| | |