Plan Review Notes
Plan Review Notes For Permit 22050592
Permit Number 22050592
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-14 12:51:13****CORRECTIONS****
 **REVISED 5/16/22**
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE A PLAN THAT SHOWS SCOPE AND
 LOCATION OF DRYWALL REMOVAL. NOTHING IS SHOWN ON THE
 PLAN SUBMITTED.
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE COMMON AREA.
 THE TWO PERMITS (UNIT 303, COMMON AREA) CAN BE ONE
 SUBMITTAL WITH ONE SET OF PLANS. EMAIL A COMPLETED
 PERMIT APPLICATION TO [email protected],
  
 3. IF YOU USE THE ARCHITECT'S PLAN, THE ARCHITECT NEEDS
 TO SIGN AND SEAL (FS481). AN ARCHITECT IS NOT REQUIRED,
 BUT IF PREPARED BY AN ARCHITECT (INCLUDES AN
 ARCHITECT'S TITLE BLOCK) DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. IF THE PLAN IS
 PREPARED BY THE CONTRACTOR, THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN IS REQUIRED.
  
 4. IF FIRE RATED WALLS ARE AFFECTED, HOW WILL THE LIFE
 SAFETY REQUIREMENTS BE MAINTAINED? YOU ARE ASKING TO
 DEMOLISH BUT NOT CLEAR WHAT THE PLAN IS TO RESTORE THE
 FIRE SAFETY REQUIRED. IT APPEARS THAT THE FIRE RATED
 CORRIDORS IN THE COMMON AREA ARE AFFECTED, FBC 708.
 SINCE A FLOOR PLAN FOR UNIT 303 WAS NOT PROVIDED, IT IS
 NOT CLEAR IF FIRE RATED WALLS ARE AFFECTED WITHIN THE
 UNIT.
  
  
  