| Plan Review Notes For Permit 22050577 |
| Permit Number |
22050577 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-28 11:49:56 | THE OCCUPANT COUNT FOR THE OUTDOOR AIR CALCULATIONS | | | MUST MEET THE MINIMUM OCCUPANT COUNT FROM FMC TABLE | | | 403.3.1.1. PROVIDE THE OUTDOOR AIR CALCULATIONS BASED | | | ON THE OCCUPANT COUNT FOR EACH USE OF SPACE FROM TABLE | | | 403.3.1.1. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|