| Notes |
| Date |
Text |
| 2022-07-27 10:22:28 | SHEET A-3. BUILDING PROVISO: MICROWAVES MUST MEET 2020 | | | FBC- | | | ACCESSIBILITY REQUIREMENTS: 308 REACH RANGES. | | | 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2 | | | OBSTRUCTED HIGH REACH | | | . 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | | OBSTRUCTED HIGH REACH. | | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | | BE PLACED WITHIN | | | ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4 | | | OPERATION. OPERABLE | | | PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT | | | REQUIRE TIGHT GRASPING, | | | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED | | | TO ACTIVATE OPERABLE PARTS | | | SHALL BE 5 POUNDS MAXIMUM. | | | JAMES A. WITMER BN, PX, SFP, CBO 7/27/2022 | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | |
|