Plan Review Notes
Plan Review Notes For Permit 22050559
Permit Number 22050559
Review Stop G
Sequence Number 1
Notes
Date Text
2022-05-16 11:08:38 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22050559
 5/16/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $3000.00 VALUE ON THE APPLICATION IS LOW FOR A
 NEW GAS SERVICE, PIPING AND APPLIANCE INSTALLATIONS.
 PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES, SITE WORK
 AND DESIGN FEES- SEC. 109.3 WPB. PLEASE PROVIDE AN
 ITEMIZED COST BREAKDOWN TO VERIFY TOTAL COSTS.
  
 2) PROVIDE A BASIC SITE OR FLOOR PLAN SHOWING THE
 PHYSICAL LOCATIONS OF THE APPLIANCES AND THE PIPING
 RUNS- SEC. 107.2.1 WPB, SEC. G2406.1 FBC RES.
  
 3) THE GAS RISER SHALL BEAR THE ADDRESS OF THE
 PROPERTY, AND THE PRINTED NAME, LICENSE NUMBER AND
 SIGNATURE OF THE PERSON WHO PREPARED THE DRAWING- SEC.
 107.2.1 WPB.
  
 4) GAS RISER- FBC RES CHAPTER 24
 A) PROVIDE THE DELIVERY PRESSURE AT THE METER AND THE
 PIPE SIZING TABLE ON THE DRAWING- SEC. G2413.4.
 B) THE LETTERS A & M ARE PRINTED BY SHUTOFF VALVES.
 ONLY MANUAL SHUTOFFS ARE REQUIRED FOR THE SYSTEM AT THE
 METER. THERE IS NO REQUIREMENT FOR AN AUTO VALVE IF
 THAT IS WHAT THE A STANDS FOR- SEC. G2420.2 & TABLE
 G2420.1.1. IF AN AUTO VALVE IS TO BE INSTALLED PLEAE
 SUBMIT MANUFACTURER'S SPECIFICATIONS IN ACCORDANCE WITH
 SEC. G2408.1.
 C) PROVIDE THE SIZE AND LENGTH OF THE PIPES FROM THE
 METER TO THE WATER HEATER, AND THE LENGTH OF THE PIPE
 RISER TO THE WATER HEATER- SEC. G2413.4.1 FBC RES.
 BASED ON THE SUBMITTED TABLE 402.4(3) FBC FG A MINIMUM
 1-INCH MAIN SUPPLY PIPE IS REQUIRED FOR A 320,000 BTU
 SYSTEM WITH A TOTAL DEVELOPED LENGTH OF 78 FT.
 D) SHOW ELECTRICAL BONDING METHOD FOR THE SCHEDULE 40
 PIPING- SEC. G2411.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS
 WATER HEATER THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE
 OF THE APPLIANCE- SEC. G2448.1 FBC RES. PROVIDE ON THE
 PLAN THE REQUIRED INSTALLATION CLEARANCES- SECS.
 G2427.1 & G2448.1 FBC RES.
  
 6) PROVIDE TANKLESS WATER HEATER CONDENSATE DISPOSAL
 PLANS INCLUDING INSTALLATION OF THE MANUFACTURER'S
 RECOMMENDED NEUTRALIZING DEVICE PER SEC. G2408.1 FBC
 RES. INCLUDE THE SPECS FOR THE DEVICES IN THE EQUIPMENT
 SCHEDULE AND MODIFY THE DRAWINGS TO SHOW TYPE AND SIZE
 OF PIPING, PIPING RUN AND DISCHARGE LOCATIONS- SECS.
 307.2-307.3 FBC FG.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND
 LISTING OF THE APPLIANCE- SEC. G2447.1 FBC RES. A)
 PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE- SEC.
 G2407.1 FBC RES.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND
 LISTING OF THE APPLIANCE- SEC. G2447.1 FBC RES. A)
 PROVIDE COMBUSTION AIR CALCULATIONS AND VENTING PLANS
 FOR THE RANGE- SEC. G2407.1 FBC RES & SEC. 107.2.1 WPB.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 DRYER THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND
 LISTING OF THE APPLIANCE- SEC. G2439.1 FBC RES. A)
 PROVIDE COMBUSTION AIR CALCULATIONS AND VENTING PLANS-
 SEC. G2407.1 FBC RES & SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  