 22050529 3161 S DIXIE HWY
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 I(3). SECOND REQUEST: MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE FOLLOWING
 SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) PRESSURE REDUCING VALVES
 ***E) SHAMPOO/HAIR WASH SINKS
 ***F) HAIR TRAP
 ***G) CLOTHES WASHER DISCHARGE INTERCEPTOR
 ***H) OWNER PROVIDED WATER DISPENSER
 PER WPB FBC 107.2.1, SUBMITTALS MAY BE DEFERRED.
 DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLANS.
 DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
  
 II(10). P0.0/WATER HEATER DETAIL:
 NEW COMMENT: PROVIDE A CHECK VALVE IN THE COLD WATER
 LINE BETWEEN THE EXPANSION TANK CONNECTION AND THE
 SHUT-OFF VALVE TO PREVENT RECIRCULATION PUMP FROM
 FORCING HOT WATER INTO THE COLD WATER SYSTEM. PLEASE
 NOTE, CHECK VALVE WAS IN THE ORIGINAL DETAIL.
  
 III(20). P1.1/PLUMBING PLAN NOTE 5: PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING; PARTIALLY COMPLIED
 ***B) ROUTING OF HORIZONTAL 3 INCH MAIN VENT TO CHASE.
 TO BE CLEAR, PLEASE SHOW THE LOCATION OF THE CHASE;
 CLARIFY ON THE PLANS THAT IT COMMUNICATES DIRECTLY FROM
 GROUND FLOOR TO THE ROOF AND PROVIDE APPLICABLE FIRE
 RATED DETAILS FOR THE PIPE PENETRATION(S).
  
 IV(23). WASHING MACHINE/DRYER COMBO: PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING:
 ***A) DETAIL SHOWING COMPLIANCE WITH FBC ACC 611.4;
 FRONT LOADING MACHINES SHALL HAVE THE BOTTOM OF THE
 OPENING TO THE LAUNDRY COMPARTMENT LOCATED 15 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 PER FBC ACC 611.4
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR PARALLEL APPROACH SHALL BE PROVIDED. THE
 CLEAR FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE PER FBC ACC 611.2.
 PARTIALLY COMPLIED: THE DETAIL AND NOTES PROVIDED ON
 P1.1/DETAIL 6 ARE APPLICABLE TO A WASHER, BUT WITH NO
 MENTION OF THE DRYER; THE SPEED QUEEN LTEE5ASP173TW01
 NOTED ON A2.2 IS A STACKED COMBO AND IS NOT COMPLIANT.
 PROVIDE A COMPLIANT WASHER/DRYER COMBO AND REVISE
 A14.1/DETAIL 14 TO SHOW COMPLIANCE.
  
 V-(26). PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER
 CONNECTIONS TO HAIR WASH SINK. INCLUDE SHUT-OFF VALVES,
 TMV AND BACKFLOW PREVENTER DEVICES
 PARTIALLY COMPLIED: PROVIDE BACKFLOW PREVENTER DEVICE
  
 VI. NEW COMMENT: P1.1/NOTE 2; IF A DRAIN IS REQUIRED
 FOR THE REFRIGERATOR, IT SHALL DISCHARGE TO THE
 SANITARY THROUGH AN INDIRECT WASTE TO A WASTE
 RECEPTACLE WITH AN AIR GAP PER FBC PL 802.1
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS