Plan Review Notes
Plan Review Notes For Permit 22050529
Permit Number 22050529
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-31 13:54:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 22050529 3161 S DIXIE HWY
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, A SEPARATE PERMIT IS REQUIRED
 FOR THE BACKFLOW PREVENTER.
 DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMIT AND
 GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2. THE SPACE APPEARS TO BE ON THE GROUND FLOOR IN A
 MULTI-USE BUILDING WITH RESIDENTIAL APARTMENTS ON THE
 UPPER FLOORS. PER WPB FBC 107.2.1, PLEASE CONFIRM OR
 CLARIFY; NOTE THE FLOOR LEVEL ON PLAN SHEET GN.0.
  
 3. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) PRESSURE REDUCING VALVES
 ***E) SHAMPOO/HAIR WASH SINKS
 ***F) HAIR TRAP
 ***G) CLOTHES WASHER DISCHARGE INTERCEPTOR
  
 4. PLAN SHEET GN.0/MINIMUM PLUMBING FIXTURE
 CALCULATION: COMPLY WITH FLORIDA PLUMBING CODE 2020 7TH
 EDITION, TABLE 403.1 AND SECTION 403.2, NOT 2902.2.4
  
 5. PLAN SHEET GN.0/ACCESSIBILITY CODE: PER WPB FBC
 107.2.1, PLEASE LIST FLORIDA ACCESSIBILITY CODE 2020
 7TH EDITION
  
 6. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL
 SPECIFICATION FOR EACH SYSTEM INCLUDING BUT NOT LIMITED
 TO SANITARY DRAINS AND VENTS, WATER DISTRIBUTION, AC
 CONDENSATE. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND
 11.
  
 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 8. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION FOR HOT WATER INSULATION. COMPLY WITH FBC
 EC C404.4 (A) AND TABLE C403.2.10.
  
 9. HANGER DETAIL- PER WPB FBC 107.2.1, PROVIDE PIPE
 HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 10. P0.0/WATER HEATER DETAIL
 ***A) FBC PL 504.6 (2) (10): T&P DISCHARGE TO FLOOR
 DRAIN SHALL BE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER; TERMINATE NOT MORE THAN 6
 INCHES ABOVE AND NOT LESS THAN TWO TIMES THE DISCHARGE
 PIPE DIAMETER ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE
 WASTE RECEPTOR .
 ***B) PROVIDE WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 504.7, 504.7.1 AND 504.7.2.
 ***C) THE DETAIL INDICATES A THERMAL MIXING VALVE
 (TMV-1) WITH140 DEGREE WATER DISTRIBUTION AND 120
 DEGREE WATER DISTRIBUTION. P1.0 WATER PLAN SHOWS ONLY
 ONE HOT WATER TO DISTRIBUTION. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND NOTE TEMPERATURE TO DISTRIBUTION.
 PLEASE NOTE, LEGIONELLA BACTERIA GROW AND MULTIPLY
 BETWEEN 68 DEGREES F AND 122 DEGREES F; THEY REPRODUCE
 RAPIDLY AND THRIVE BETWEEN 95 DEGREES F AND 115 DEGREES
 F. BELOW 68 DEGREES F, THE BACTERIA SURVIVES, BUT IT
 DOES NOT MULTIPLY. FROM 115 DEGREES F TO ABOUT 122
 DEGREES F, THE BACTERIA GROW SLOWLY. FROM 123 DEGREES F
 TO 131 DEGREES F, THE BACTERIA SURVIVE BUT DO NOT
 MULTIPLY. AT 131 DEGREES F, IT TAKES ABOUT FIVE TO SIX
 HOURS FOR THE BACTERIA TO DIE. AT 140 DEGREES F, THE
 BACTERIA DIES IN 32 MINUTES. ONE OF THE MOST WIDELY
 ACCEPTED AND PREFERRED METHODS OF CONTROLLING
 LEGIONELLA BACTERIA IS TO MAINTAIN THE HOT WATER SYSTEM
 STORAGE TANK TEMPERATURE AT OR ABOVE 135 DEGREES F TO
 140 DEGREES F.
 ***D) PLEASE NOTE, DUE TO THE WEIGHT (23LBS. EMPTY PLUS
 10.2 GALLON OF WATER AT 8.33 LBS. PER GALLON) THE
 AMTROL ST-25V EXPANSION TANK IS A FREE STANDING TANK
 DESIGNED TO SIT ON THE FLOOR. PER WPB FBC 107.2.1,
 PLEASE SHOW THIS ON THE DETAIL. ADDITIONALLY, SHOW
 LOCATION ON THE FLOOR PLAN AND ASSOCIATED PIPING.
  
 11. P0.0/PLUMBING FIXTURE SCHEDULE/WH-1: PER WPB FBC
 107.2.1, PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
  
  
 12. P0.0/PLUMBING FIXTURE SCHEDULE/EWC-1/ WATER
 COOLER/EZSTL8LC IS A BI-LEVEL ADA COMPLIANT DRINKING
 FOUNTAIN; DESCRIPTION IS OF A WALL HYDRANT. SANITARY
 AND WATER PLANS DO NOT SHOW CONNECTIONS FOR THE
 FIXTURE. THE WATER PLAN DOES SHOW HOT AND COLD WATER TO
 A WATER DISPENSER. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 SPECIFY AND PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER
 DISPENSER.
  
 13. P0.0/PLUMBING FIXTURE SCHEDULE/RPBP/REDUCED
 PRESSURE BACKFLOW PREVENTER: PER FBC PL 605.2 AND
 605.2.1. SPECIFY LEAD FREE BACKFLOW PREVENTER.
  
 14. PER PL 604.9, PROVIDE WATER HAMMER ARRESTORS
 COMPLYING WITH ASSE 1010 FOR THE WATER CONNECTIONS TO
 THE WASHING MACHINE AND TO THE REFRIGERATOR ICE LINE.
  
 15. PER FBC 1210.2.2 AND FBC PL 310.3, THE WALL
 COVERING NOTED (WC-3) IN THE RESTROOM DOES NOT COMPLY.
 WALL FINISH (WC-1) FOR MOP SINK IS COMPLIANT. WPB FBC
 107.2.1, PROVIDE COMPLIANT FINISH WALL SCHEDULE FOR
 RESTROOM SHOWING COMPLIANCE WITH FBC 1210.2.2 AND FBC
 PL 310.3. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE PER FBC-BUILDING SEC.
 1210.2.2. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL
 BE "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 16. THE PLANS ARE UNCLEAR. WILL THERE BE A NEW SLAB ON
 GRADE OR IS THERE AN EXISTING SLAB THAT WILL NEED TO BE
 CUT FOR TRENCHING. PER WPB FBC 107.2.1, PLEASE CLARIFY,
 AND IF APPLICABLE, PROVIDE A SLAB REPAIR DETAIL ON THE
 PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 17. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 18. PLAN SHEET P1.1/NOTE 6: AC CONDENSATE- PER WPB CODE
 OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5,
 A/C CONDENSATE (INTERPRET THIS AS ANY CONDENSATION FROM
 EVAPORATOR COILS) SHALL NOT DISCHARGE TO THE CITY
 UTILITIES SANITARY SEWAGE INFRASTRUCTURE WITHOUT
 PERMISSION FROM THE UTILITIES DEPARTMENT. YOU MAY
 CONTACT 561-494-1128 FOR ADDITIONAL INFORMATION. MOVING
 FORWARD, DISCHARGE THE CONDENSATE TO AN EXTERIOR
 DRYWELL; PER WPB FBC 107.2.1, PROVIDE ROUTING AND
 DRYWELL DETAIL.
  
 19. P1.0/PRV-1: PER FBC PL 604.8, PROVIDE A STRAINER
 AHEAD OF PRV-1.
  
 20. P1.1/PLUMBING PLAN NOTE 5: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING;
 ***A) DETAIL FOR SUPPORT OF 3 INCH VERTICAL VENT IN
 CHASE
 ***B) ROUTING OF HORIZONTAL 3 INCH MAIN VENT TO CHASE.
  
 21. PER WPB FBC 107.2.1, PROVIDE DRAINAGE FIXTURE UNIT
 SCHEDULE. COMPLY WITH FBC PL TABLES 709.1, 709.2.
  
 22. A4.1/FINISH WALL KEY: PER WPB FBC 107.2.1, ADD TAG
 WC-1 WALL COVERING FOR MOP SINK.
  
 23. WASHING MACHINE/DRYER COMBO: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING:
 ***A) DETAIL SHOWING COMPLIANCE WITH FBC ACC 611.4;
 FRONT LOADING MACHINES SHALL HAVE THE BOTTOM OF THE
 OPENING TO THE LAUNDRY COMPARTMENT LOCATED 15 INCHES
 MINIMUM AND 36 INCHESMAXIMUM ABOVE THE FINISH FLOOR PER
 FBC ACC 611.4
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR PARALLEL APPROACH SHALL BE PROVIDED. THE
 CLEAR FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE PER FBC ACC 611.2.
  
 24. PER FBC PL 1002.4, SPECIFY TRAP SEAL PROTECTION FOR
 THE FLOOR DRAIN(S) COMPLYING ONE OF THE METHODS IN
 SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
 ***A) PER WPB FBC 107.2.1, PROVIDE TRAP
 PROTECTION/PRIMER DETAIL.
  
 25. PER FBC PL 1003.6, AN INTERCEPTOR IS REQUIRED FOR
 THE CLOTHES WASHER DRAIN.
 ***A) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION AND A DETAIL FOR THE INSTALLATION.
  
 26. PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER
 CONNECTIONS TO HAIR WASH SINK. INCLUDE SHUT-OFF VALVES,
 TMV AND BACKFLOW PREVENTER DEVICES
  
 27. P1.1/PLUMBING NOTE 4: SPECIFIED HAIR TRAP COMES
 WITH 1-1/2 INCH SLIP JOINT TUBULAR CONNECTIONS
 REQUIRING CONNECTION TO TUBULAR FITTINGS, TAILPIECES,
 ETC. NOTE SAYS NO THIN WALL PVC WILL BE PERMITTED. PER
 WPB FBC 107.2.1, PLEASE CLARIFY. MODIFY NOTE AS NEEDED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  