Date Text
2022-05-25 13:38:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 0.0 - THERE IS AN INDICATION OF AN EXIT PATH
 TO A SINGLE FRONT EXIT DOOR; HOWEVER, THERE ARE OTHER
 ROOMS TO EXIT FROM WITH NO INDICATIONS OF EXIT MARKINGS
 TO THAT SAME EXIT OR TO A REAS EXTERIOR DOOR.
  
 PER NFPA 101 CH 38, NEW BUSINESS OCCUPANCIES AND CH 7
 MEANS OF EGRESS,
  
 38.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 38.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO THAT
 EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN OPEN
 FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR
 CORRIDORS LEADING DIRECTLY
 TO EVERY EXIT SHALL BE MAINTAINED AND SHALL BE ARRANGED
 TO PROVIDE ACCESS
 FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY
 SEPARATE WAYS OF TRAVEL,
 UNLESS OTHERWISE PROVIDED IN 7.5.1.1.3 AND 7.5.1.1.4
  
 PLEASE REVIEW AND CORRECT THE EXIT ACCESS/MARKINGS FROM
 THE 2 ROOMS(STORAGE & BREAK)'
  
  
  
 2) SHEET GN.0 - THERE IS AN INDICATION THAT THE
 BUILDING IS SPRINKLED HOWEVER, THIS IS NO INDICATION OF
 FIRE SPRINKLER MODIFICATIONS.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDEGMENT
  
  
 2A) THERE IS NO INDICATIONS THAT THIS BUILDING HAS A
 FIRE ALARM WHICH IS EXISTING.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE
 DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDEGMENT
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  