| 2022-05-17 12:02:56 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - THE PLUMBING DRAWING SEEMS | | | TO BE MISSING THE CLOTHES WASHER AND KITCHEN | | | CONNECTIONS. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - NOTED ON THE PLANS IS A | | | "BEVERAGE BAR T.B.D." AND APPEARS TO BE UPSTREAM OF THE | | | BATHROOM CONNECTIONS. PER P3108.1, THE BAR SINK (IF | | | THERE IS ONE) WOULD NEED TO BE DISCHARGED DOWNSTREAM OF | | | THE WET VENT SYSTEM AND NOT CONNECTED TO WHAT IS | | | DETAILED ABOVE THE NEW CONNECTION OF THE WATER CLOSET | | | THAT IS THERE NOW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|