| Plan Review Notes For Permit 22050470 |
| Permit Number |
22050470 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-28 07:21:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, COORDINATE WITH [email protected] TO | | | REMOVE THE DOCUMENT STATING WORK WAS DONE. IF THE WORK | | | WAS DONE WITHOUT A PERMIT, A STOP WORK ORDER WILL BE | | | ISSUED AND A 4X FEE ASSESSED. | | | | | | 2. PROVIDE A COST BREAKDOWN FOR THIS JOB, FBC 109. | | | | | | 3. THE WALL DETAIL DOES NOT INCLUDE SHEATHING OR | | | WATERPROOFING, SEE DETAIL 3-A102, REVISE TO INCLUDE, | | | FBC 107. REVISE TO INCLUDE FASTENING PATTERN. | | | | | | 4. REVISE PLAN TO INCLUDE A DETAIL FOR THE STEPS, FBC R | | | 311. THE ORIGINAL APPLICATION WAS FOR A KITCHEN | | | RENOVATION, BUT IT APPEARS THAT WORK THAT AFFECTS THE | | | BUILDING FOOTPRINT IS PROPOSED (EXTERIOR STAIR). ZONING | | | REVIEW IS REQUIRED AND WILL BE DONE AT THIS TIME. | | | | | | 5. SINCE THE WORK NOW INCLUDES THE EXTERIOR, REVISE | | | PLAN TO STATE WIND DESIGN CRITERIA. FBC R 301. | | | | | | | | | | | | | | | |
|