Plan Review Notes
Plan Review Notes For Permit 22050315
Permit Number 22050315
Review Stop B
Sequence Number 2
Notes
Date Text
2022-08-04 13:27:25ENCLOSE CARPORT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS LISTED ON THE DRAWINGS.
  
 2) R19 BAT INSULATION WILL NOT FIT IN A ROOF JOIST
 THICKNESS OF 2 X 6 AND LEAVE THE REQUIRED AIR GAP - FBC
 R806.3 VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.