| 2022-08-04 13:27:25 | ENCLOSE CARPORT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE | | | EXTERIOR WINDOWS LISTED ON THE DRAWINGS. | | | | | | 2) R19 BAT INSULATION WILL NOT FIT IN A ROOF JOIST | | | THICKNESS OF 2 X 6 AND LEAVE THE REQUIRED AIR GAP - FBC | | | R806.3 VENT AND INSULATION CLEARANCE. | | | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING, | | | BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW | | | OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE | | | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING | | | AND AT THE LOCATION OF THE VENT. |
|