Plan Review Notes
Plan Review Notes For Permit 22050315
Permit Number 22050315
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-01 16:37:24ENCLOSE CARPORT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS LISTED ON THE DRAWINGS.
  
 2) THE ADDRESS ON THE DRAWINGS NEEDS TO MATCH THE
 ADDRESS ON THE BUILDING PERMIT APPLICATION.
  
 3) FBC R806.1 VENTILATION REQUIRED. ENCLOSED ATTICS AND
 ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL
 HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST
 DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, PERFORATED VINYL OR SIMILAR MATERIAL
 WITH OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH
 (1.6 MM) MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM.
 OPENINGS IN ROOF FRAMING MEMBERS SHALL CONFORM TO THE
 REQUIREMENTS OF SECTION R802.7. REQUIRED VENTILATION
 OPENINGS SHALL OPEN DIRECTLY TO THE OUTSIDE AIR AND
 SHALL BE PROTECTED TO PREVENT THE ENTRY OF BIRDS,
 RODENTS, SNAKES AND OTHER SIMILAR CREATURES.
  
 4) FBC R806.3 VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.