Plan Review Notes
Plan Review Notes For Permit 22050312
Permit Number 22050312
Review Stop E
Sequence Number 1
Notes
Date Text
2022-05-16 11:07:56ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM DETAILS #3 CU CONDUCTORS WITH A RATED
 AMAPACITY OF 100-AMPS WITH 125-AMP OVERCURRENT
 PROTECTION. PLEASE DETAIL A CONDUCTOR THAT COMPLIES
 WITH NEC 310.15 (7)(B) OR AN OVERCURRENT DEVICE OF
 110-AMPS. NEC 240.6(A)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  