| 2022-05-24 09:54:08 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:22050264 |
| | ADD: 500 S. AUSTRALIAN AVE. SUITES 825 & 850 |
| | CONT: KARLCORP CONSTRUCTION SERVICES |
| | TEL: 561-718-5569 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/24/2022 |
| | ACTION: DENIED |
| | |
| | 1) SPEC SHEETS FROM SHAW FOR THE INSTALLATION OF LVT TO |
| | REFERENCED STANDARDS TO WHICH THIS PRODUCT WAS TESTED. |
| | ISO 14205, ISO 21930, 2017 AND EN 15804. PLEASE REVIEW |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253 |
| | |
| | 2) SHEET MODIFICATION FLOOR PLAN SHOWS FOR SUITE 850 |
| | THE SECONDARY EGRESS DOOR IN THE BREAK ROOM IN A |
| | CLOSET. 2020 FBC-BUILDING CODE SECTION 1016.2. 5. |
| | EGRESS THROUGH INTERVENING SPACES. EGRESS SHALL NOT PAS |
| | THROUGH STORAGE ROOMS OR ROOMS OR SPACES USED FOR |
| | SIMILAR PURPOSES. |
| | |
| | 3) THE PROJECT INFORMATION LACKS THE FOLLOWING FOR THE |
| | 2 SUITES TO BE REMODELED, SQUARE FOOTAGE OF BOTH |
| | SUITES, OCCUPANT LOAD FACTOR AND OCCUPANT LOAD. 2020 |
| | FBC-BUILDING TABLE 1004.5 |
| | |
| | 4) THE OCCUPANT LOAD IS NOT GIVEN, COMPLIANCE WITH |
| | TABLE 1006.1.2 MAXIMUM COMMON PATH OF TRAVEL DISTANCE |
| | CAN NOT BE DETERMINED FOR EITHER SUITE, 825 OR 850. |
| | |
| | 5) SUITE 850 PLEASE PROVIDE THE OVERALL DIAGONAL |
| | DISTANCE OF THE SUITE AND THE DISTANCE BETWEEN THE 2 |
| | ENTRY/ EXIT DOORS IN COMPLIANCE WITH 2020 FBC-BUILDING |
| | CODE SECTION 1007.1.1 OF THE 2020 FBC-BUILDING CODE. |
| | |
| | 6 SUITE 800 NOT IN CONTRACT WITH THE NEW CONFIGURATION |
| | OF THE SUITES THE 2 EGRESS DOORS ARE CLOSER THAN THE |
| | 1/3RD DIAGONAL DISTANCE OF THE SUITE, 1007.1.1 |
| | FBC-BUILDING CODE, OCCUPANT LOAD NOT GIVEN THIS |
| | REQUIREMENT MAY NOT BE REQUIRED. PROVIDE THE OCCUPANT |
| | LOAD IN COMPLIANCE WITH 2020 FBC-BUILDING TABLE 1004.5. |
| | |
| | 7) DETAIL REPLACEMENT CABINETS FOR SUITE 850. SHOWS A |
| | BOTTOM OF SHELF TO BE USED FOR A MICROWAVE AT A HEIGHT |
| | OF 54 INCHES, ABOVE THE REACH RANGES FOR EITHER A FRONT |
| | APPROACH OR SIDE APPROACH. 2020 FBC-ACCESSIBILITY CODE |
| | SECTIONS; |
| | |
| | 7A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 7B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS |
| | SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | 8A) THE FLOOR PLAN FOR SUITE 850 DOES NOT SHOW THE |
| | BREAK ROOM CABINETS ON THE FLOOR PLAN NOR COMPLIANCE |
| | WITH THE 2020 FBC-ACCESS. CODE SECTIONS 305.7.1 FORWARD |
| | APPROACH OR 307.5.2 SIDE APPROACH. |
| | |
| | 8B) THE FLOOR PLAN FOR SUITE 825 DOES SHOW THE BREAK |
| | ROOM CABINETS ON THE FLOOR PLAN BUT NOT COMPLIANCE WITH |
| | THE 2020 FBC-ACCESS. CODE SECTIONS 305.7.1 FORWARD |
| | APPROACH OR 307.5.2 SIDE APPROACH. |
| | 8C) THERE IS NO ELEVATION VIEW OF THE BREAK ROOM |
| | CABINETS FOR SUITE 825. 2020 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 9) THE OVERALL FLOOR PLAN OF THE 8TH FLOOR DOES NOT |
| | SHOW ANY DRINKING FOUNTAINS IN THE TENANT SPACES NOR |
| | COMMON ELEMENTS AS THE CORRIDOR. |
| | 9A) DRINKING FOUNTAINS. 2020 FBC-ACCESSIBILITY CODE. |
| | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | |
| | 9B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT |
| | MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE |
| | MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION |
| | PATH. |
| | |
| | 9C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 9D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| | CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |