2022-05-24 09:54:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:22050264
 ADD: 500 S. AUSTRALIAN AVE. SUITES 825 & 850
 CONT: KARLCORP CONSTRUCTION SERVICES
 TEL: 561-718-5569
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/24/2022
 ACTION: DENIED
  
 1) SPEC SHEETS FROM SHAW FOR THE INSTALLATION OF LVT TO
 REFERENCED STANDARDS TO WHICH THIS PRODUCT WAS TESTED.
 ISO 14205, ISO 21930, 2017 AND EN 15804. PLEASE REVIEW
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 2) SHEET MODIFICATION FLOOR PLAN SHOWS FOR SUITE 850
 THE SECONDARY EGRESS DOOR IN THE BREAK ROOM IN A
 CLOSET. 2020 FBC-BUILDING CODE SECTION 1016.2. 5.
 EGRESS THROUGH INTERVENING SPACES. EGRESS SHALL NOT PAS
 THROUGH STORAGE ROOMS OR ROOMS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 3) THE PROJECT INFORMATION LACKS THE FOLLOWING FOR THE
 2 SUITES TO BE REMODELED, SQUARE FOOTAGE OF BOTH
 SUITES, OCCUPANT LOAD FACTOR AND OCCUPANT LOAD. 2020
 FBC-BUILDING TABLE 1004.5
  
 4) THE OCCUPANT LOAD IS NOT GIVEN, COMPLIANCE WITH
 TABLE 1006.1.2 MAXIMUM COMMON PATH OF TRAVEL DISTANCE
 CAN NOT BE DETERMINED FOR EITHER SUITE, 825 OR 850.
  
 5) SUITE 850 PLEASE PROVIDE THE OVERALL DIAGONAL
 DISTANCE OF THE SUITE AND THE DISTANCE BETWEEN THE 2
 ENTRY/ EXIT DOORS IN COMPLIANCE WITH 2020 FBC-BUILDING
 CODE SECTION 1007.1.1 OF THE 2020 FBC-BUILDING CODE.
  
 6 SUITE 800 NOT IN CONTRACT WITH THE NEW CONFIGURATION
 OF THE SUITES THE 2 EGRESS DOORS ARE CLOSER THAN THE
 1/3RD DIAGONAL DISTANCE OF THE SUITE, 1007.1.1
 FBC-BUILDING CODE, OCCUPANT LOAD NOT GIVEN THIS
 REQUIREMENT MAY NOT BE REQUIRED. PROVIDE THE OCCUPANT
 LOAD IN COMPLIANCE WITH 2020 FBC-BUILDING TABLE 1004.5.
  
 7) DETAIL REPLACEMENT CABINETS FOR SUITE 850. SHOWS A
 BOTTOM OF SHELF TO BE USED FOR A MICROWAVE AT A HEIGHT
 OF 54 INCHES, ABOVE THE REACH RANGES FOR EITHER A FRONT
 APPROACH OR SIDE APPROACH. 2020 FBC-ACCESSIBILITY CODE
 SECTIONS;
  
 7A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 7B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
 8A) THE FLOOR PLAN FOR SUITE 850 DOES NOT SHOW THE
 BREAK ROOM CABINETS ON THE FLOOR PLAN NOR COMPLIANCE
 WITH THE 2020 FBC-ACCESS. CODE SECTIONS 305.7.1 FORWARD
 APPROACH OR 307.5.2 SIDE APPROACH.
  
 8B) THE FLOOR PLAN FOR SUITE 825 DOES SHOW THE BREAK
 ROOM CABINETS ON THE FLOOR PLAN BUT NOT COMPLIANCE WITH
 THE 2020 FBC-ACCESS. CODE SECTIONS 305.7.1 FORWARD
 APPROACH OR 307.5.2 SIDE APPROACH.
 8C) THERE IS NO ELEVATION VIEW OF THE BREAK ROOM
 CABINETS FOR SUITE 825. 2020 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 9) THE OVERALL FLOOR PLAN OF THE 8TH FLOOR DOES NOT
 SHOW ANY DRINKING FOUNTAINS IN THE TENANT SPACES NOR
 COMMON ELEMENTS AS THE CORRIDOR.
 9A) DRINKING FOUNTAINS. 2020 FBC-ACCESSIBILITY CODE.
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 9B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 9C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 9D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  