| 2022-06-17 12:51:03 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R10 SELECTED SYSTEM NO W-5; EXPOSURE |
| | (C); ENCLOSURE (OPEN); ROOF HEIGHT (30 < H < 40); |
| | ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT |
| | ENCLOSURE FOR THE LISTED ADDRESS IS ENCLOSED. WHEN |
| | USING THE CORRECT ENCLOSURE; ZONE 3 IS MARKED ?N/A? |
| | WHICH INDICATES SYSTEM CANNOT BE USED WITHIN THE |
| | PRESSURE ZONE. PLEASE PROVIDE A SYSTEM THAT MEETS OR |
| | EXCEEDS ALL CRITERIA FOR THE LISTED ADDRESS. |
| | 2. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. THIRD REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |