| Date |
Text |
| 2022-06-28 15:44:07 | CONCRETE RESTORATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR SEPARATE |
| | BUILDINGS. |
| | |
| | 2) 777 S FLAGLER DR IS IN A FLOOD ZONE - PLEASE PROVIDE |
| | THE SEPARATE JOB COST FOR THIS BUILDING - PLEASE |
| | PROVIDE BUILDING ONLY AS IS MARKET VALUE (FROM PALM |
| | BEACH COUNTY PROPERTY APPRAISER - OR A LICENSED |
| | APPRAISER) - WILL NEED TO DETERMINE IF THE JOB IS A |
| | SUBSTANTIAL IMPROVEMENT - FBC 202 - SUBSTANTIAL |
| | IMPROVEMENT. ANY REPAIR, RECONSTRUCTION, |
| | REHABILITATION, ALTERATION, ADDITION OR OTHER |
| | IMPROVEMENT OF A BUILDING OR STRUCTURE, THE COST OF |
| | WHICH EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET VALUE |
| | OF THE STRUCTURE BEFORE THE IMPROVEMENT OR REPAIR IS |
| | STARTED. IF THE STRUCTURE HAS SUSTAINED SUBSTANTIAL |
| | DAMAGE, ANY REPAIRS ARE CONSIDERED SUBSTANTIAL |
| | IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK |
| | PERFORMED. |
| | |
| | 3) ANY REPAIRS TO THRESHOLD BUILDINGS ARE REQUIRED TO |
| | COMPLY WITH FS 553.79. THRESHOLD BLDG. REQUIRED |
| | STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 FLORIDA STATUTES. |
| | |
| | 4) THRESHOLD INSPECTOR FORMS NEED TO BE FILLED OUT - |
| | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE |
| | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| | YOU CAN E MAIL ME AND ASK FOR A COPY. |