| 2022-05-17 12:49:21 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22050234 |
| | 5/17/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 3: THE TDH CALCS SHOW FRICTION LOSS FOR A |
| | HEATER. PLEASE SHOW THE HEATER LOCATION AND PIPING IN |
| | THE SCHEMATIC, AND PROVIDE AN EQUIPMENT SCHEDULE- MAKE, |
| | MODEL, ELECTRIC OR GAS POWER, EFFICIENCY RATING- SEC. |
| | 107.2.1 WPB. PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR A GAS WATER HEATER- SEC. 105.1 WPB. |
| | |
| | 2) SHEETS 2 OR 3: INDICATE THE WATER SUPPLY SOURCE FOR |
| | THE POOL- SEC. R4501.9 FBC RES. PLEASE NOTE |
| | INSTALLATION OF AN AUTO FILL AND THE REQUIRED AVB |
| | BACKFLOW PREVENTER AT THE DEVICE SHALL BE INSTALLED BY |
| | A FL. LICENSED PLUMBER- CFC NOT CPC. THE INSTALLATION |
| | CAN BE DONE AS A SUB-PERMIT FOR THE MASTER, OR UNDER A |
| | SEPARATE PERMIT. |
| | |
| | 3) INSTALLATION OF THE NEW POOL AT THE RESIDENCE |
| | REQUIRES INSTALLATION OF A POTABLE WATER SERVICE RPZ |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SEC. D & E WPB |
| | CROSS CONNECTION MANUAL. |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |