| Plan Review Notes For Permit 22050230 |
| Permit Number |
22050230 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-21 08:11:58 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 105.1 - THIS REVIEW FOR MAIN HOUSE | | | ONLY. CABANA REQUIRES SEPERATE PERMIT. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - THE HALL BATH IS MISSING | | | FROM THE SANITARY RISER DIAGRAMS. | | | | | | 3. 2020 FRC P3108.1 - MASTER BATH - THE SHOWER IS NOT | | | VENTED. CANNOT BE "WET VENTED" FROM THE BUILDING DRAIN. | | | | | | 4. 2020 FRC P3104.4 - MASTER BATH - THE WATER CLOSET | | | HAS A VENT THAT IS HORIZONTAL BELOW THE FLOOD RIM OF | | | THE FIXTURE. VENTS MUST REMAIN VERTICAL UNTIL THEY ARE | | | AT LEAST 6" ABOVE THE FIXTURE(S) SERVED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|