 1) SMOKE ALARMS REQUIRED BY FBC R314
  
 2) 120V OUTLETS IN LAUNDRY TO BE GFI PROTECTED 210.8(A)
  
 3) CABANA WILL REQUIRE A SEPARATE FEEDER PER 225.30,
 AND A SEPARATE GROUNDING ELECTRODE PER 250.32
  
 225.30 NUMBER OF SUPPLIES. A BUILDING OR OTHER
 STRUCTURE
 THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE
 LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE
 FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN 225.30(A)
 THROUGH (E). FOR THE PURPOSE OF THIS SECTION, A
 MULTIWIRE
 BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR
 BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING
 ELECTRODE OR GROUNDING ELECTRODE SYSTEM INSTALLED IN
 ACCORDANCE WITH PART III OF ARTICLE 250. THE GROUNDING
 ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE,
 THE GROUNDING ELECTRODE(S) REQUIRED IN 250.50 SHALL BE
 INSTALLED.